| 2007-01-11 12:09:23 | DENIED BY BUILDING |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| | MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) THE VALUE APPEARS TO BE QUITE LOW FOR THE APPARENT |
| | SCOPE OF WORK. PLEASE INCREASE THE VALUE TO REFLECT THE |
| | SCOPE OF THE PROPOSED WORK. |
| | |
| | 3) 2004 FL. BLD CODE 1603.1.4 THE |
| | FOLLOWING INFORMATION RELATED TO WIND |
| | SHALL BE SHOWN ON THE CONSTRUCTION |
| | DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 4)SPECIFY THE APPLICABLE CODES ON THE PLANS. |
| | |
| | 5) SPECIFY THE WINDLOAD PRESSURES AT THE WINDOW |
| | OPENINGS ON THE PLANS. |
| | |
| | 6) SUBMIT THE INSTALLATION INSTRUCTIONS WITH DESIGN |
| | PRESSURES FOR THE IMPACT WINDOWS. PROVIDE DOCUMENTATION |
| | THAT WINDOWS HAVE BEEN TESTED FOR LARGE MISSILE |
| | IMPACT. |
| | |
| | 7) SUBMIT PRODUCT APPROVALS FOR THE WINDOW MULLIONS |
| | BETWEEN CASEMENT AND FIXED ARCHED WINDOWS. |
| | |
| | 8)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 9) SPECIFY THE WINDOW SIZES ON THE PLANS. |
| | |
| | 10) THE DEMO PLAN ON D-1.1 SHOWS SIX WINDOW OPENINGS |
| | AND NOTE 3.8 STATES REMOVE EXISTING CONCRETE WALL FOR |
| | WINDOW INSTALLATION. THE ELEVATION ON A1-1 SHOWS FOUR |
| | WINDOWS. THE WALL SECTION ON A-1.2 SPECIFIES WOOD |
| | FRAME. PLEASE CORRECT. |
| | |
| | 11) PLEASE CLARIFY THE DRAWINGS ON A-1.2INDICATE WHAT |
| | IS EXISTING AND WHAT IS NEW. PROVIDE A WALL SECTION |
| | SHOWING THIS WALL IN ITS EXISTING CONDITION. |
| | |
| | 12) IT APPEARS THAT THE SECOND FLOOR IS BEING BUILT |
| | OUT. INDICATE WHERE THE PROPERTY LINE IS IN RELATION TO |
| | THE EXTERIOR WALL AT THE SECOND FLOOR. THE SECOND FLOOR |
| | CAN NOT PROJECT OVER THE PROPERTY LINE. |
| | |
| | 13)PROVIDE AN ELEVATION SHOWING THE HEADERS AND |
| | FRAMING DETAILS AT THE NEW WINDOW OPENINGS. SPECIFY |
| | STRAPPING AND CONNECTORS. PROVIDE PRODUCT APPROVALS FOR |
| | CONNECTORS. |
| | |
| | 14)SPECIFY THE VAPOR RETARDER REQUIRED BY FBC 1403.3 |
| | BEHIND THE NEW CULTURED BRICK VENEER. |
| | |
| | 15) PROVIDE THE TECHNICAL DATA AND STANDARDS, INCLUDING |
| | FIRE RESISTANCE AND WINDLOAD INFORMATION , AS WELL AS |
| | THE INSTALLATION (ATTACHMENT) INFORMATION FOR THE OWENS |
| | CORNING CB-4054 BRICK VENEER. |
| | |
| | 16)PROVIDE THE TECHNICAL DATA AND STANDARDS, |
| | INCLUDING FIRE RESISTANCE AND WINDLOAD INFORMATION , AS |
| | WELL AS THE INSTALLATION (ATTACHMENT) INFORMATION FOR |
| | THE LIGHTWEIGHT CORNICE, SILL, ROWLOCK COURSE AND ANY |
| | OTHER TRIM. |
| | |
| | 17) THE TITLE BLOCK ON SHEET D-1.1 IS INCOMPLETE |
| | APPARANTLY DUE TO A PRINTING ERROR. |
| | |
| | 18) THE PRINTED NAME OF THE PERSON SIGNING AND SEALING |
| | THE PLAN IS REQUIRED IN THE TITLE BLOCK BY FAC |
| | 61G1-16.004. |
| | |
| | 19) THERE ARE SOME NOTATIONS ON ONE OF THE PLANS IN RED |
| | PENCIL. |
| | |
| | 20) DUE TO THE LACK OF INFORMATION ON THE PLANS AND |
| | SUBMITTALS, ADDITIONAL COMMENTS MAY RESULT WHEN THESE |
| | ITEMS ARE ADDRESSED. |
| | |
| | 21) TO EXPEDITE PLAN REVIEW PLEASE RETURN ONE SET OF |
| | THE OLD PLANS ALONG WITH A RESPONSE LETTER. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |