| Plan Review Notes For Permit 06120064 |
| Permit Number |
06120064 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-08 09:17:09 | *** DENIED *** | | | 1) SHOW A EQUIPMENT LISTING WITH ALL PERTINENT | | | INFORMATION ON THE MECHANICAL PLANS. | | | | | | 2) NEED TO SHOW THE CFM'S AT ALL SUPPLY AIR GRILLS. | | | | | | 3) NEED TO SHOW THE SIZE OF THE GRILLS FOR THE RETURN | | | AIR TRANSFER DUSTS. | | | | | | 4) NEED TO SHOW THE SIZE OF ALL THE RETURN AIR TRANSFER | | | DUCTS BALANCED RETURN AIR. | | | MAY BE ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND | | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING | | | AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | | PROPER RETURN AIR BALANCE. | | | (C)HABITABLE ROOMS ONLY SHALL BE | | | REQUIRED TO MEET THESE REQUIREMENTS FOR | | | PROPER BALANCED RETURN AIR EXCLUDING | | | BATHROOMS, CLOSETS, STORAGE ROOMS AND | | | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY | | | AIR INTO THE MASTER SUITE SHALL BE | | | INCLUDED. PER 2004 FBC/R M1602.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|