2006-12-08 09:17:09*** DENIED ***
 1) SHOW A EQUIPMENT LISTING WITH ALL PERTINENT
 INFORMATION ON THE MECHANICAL PLANS.
  
 2) NEED TO SHOW THE CFM'S AT ALL SUPPLY AIR GRILLS.
  
 3) NEED TO SHOW THE SIZE OF THE GRILLS FOR THE RETURN
 AIR TRANSFER DUSTS.
  
 4) NEED TO SHOW THE SIZE OF ALL THE RETURN AIR TRANSFER
 DUCTS BALANCED RETURN AIR.
 MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.