2007-04-09 15:51:27BUILDING PLAN REVIEW
 PERMIT:06120055
 ADD: 6 LA COSTA CIRCLE
 CONT: AM CONSTRUCTION GROUP INC.
 TEL: (561)262-7874
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW3 RD
 ACTION: DENIED
  
 NOTE: ONE SET OF THE DRAWINGS WHICH WAS PUT TOGETHER BY
 OUR OFFICE STAFFWILL BE DETAINEDAND IF NECESSARY
 THEY WILL BE SENT TO THE STATE FOR REVIEW DUE TO
 REPATED CODE COMMENTS.
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)OK
  
 3)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 4)OK.
  
 5)OK.
  
 6)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. THE PRODUCT SHALL BE
 APPROVED IN WRITING BY THE DESIGNER.
  
 7)OK.
  
 8)OK.
  
 9)ON SHEET S4, INDICATE WHICH STEEL COLUMN IS #1 / #2
 / AND #3. THE COLUMNS ARE THERE ON THE SHEET BUT THEY
 ARE NOT LABELED.
  
 10)R807.1 INDICATE THE ATTIC ACCESS ON THE DRAWINGS.
 THE ROUGH OPENING SHALL NOT BE LESS THAN 22 INCHES BY
 30 INCHES AND SHALL BE READILY ACCESSIBLE.
  
 11)G2447.1 (623.1) COOKING APPLIANCES .
 COOKING APPLIANCES THAT ARE DESIGNED FOR PERMANENT
 INSTALLATION, INCLUDING RANGES, OVENS, STOVES,
 BROILERS, GRILLS, FRYERS, GRIDDLES, HOT PLATES AND
 BARBECUES, SHALL BE TESTED IN ACCORDANCE WITH ANSI
 Z21.1 OR ANSI Z21.58 AND SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS. PROVIDE THE MANUFACTURER,S INSTALLATION
 INSTRUCTIONS INSTRUCTIONS FOR THE BBQ GRILL. SEE THIS
 SECTION FOR MORE INFORMATION.
  
 12)PROVIDE AN ABBREVATION LEGEND FOR ALL THE
 ABBREVIATION SHOWN ON THE DRAWINGS.106.1.2*THE
 BUILDING OFFICIAL MAY REQUIRE DETAILS, AND OTHER DATA
 NECESSARY TO DESCRIBE THE CONSTRUCTION OR INSTALLATION
 AND THE BASIS OF CALCULATIONS.
  
 13)R802.1.6.1 TRUSS DESIGN DRAWINGS, PREPAARED IN
 CONFORMANCE WITH SECTION R802.1.6.1 SHALL BE PROVIDED
 TO THE BUILDING OFFICIAL AND APPROVED PRIOR TO
 INSTALLATION.
  
 14) OK.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  