2007-02-07 06:57:20BUILDING PLAN REVIEW
 PERMIT: 06120055
 ADD: 6LACOSTA CIRCLE
 CONT: AM CONSTRUCTION GROUP INC.
 TEL: (561)262-7874
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
  
 3)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 4)109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 5) 110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 -------------------------------------
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) NUMBER OF BEDROOMS
 ) SQ. FT. LIV SPACE/ FL
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) FLOOD ZONE
 ) FLOOD ELEVATION
 )L.O.M.R.
  
 6) 106.3.3* PRODUCT APPROVALS- 2004
 THOSE PRODUCTS THAT ARE RGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. PROVIDE PRODUCT APPROVALS FOR
 WINDOWS/MULLIONS/DOORS AND ROOFING MATERIALS.
  
 7)WPB AMENDMENTS. 108.3THE CLAIM VALUE IS TO LOW.
 IF IN THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION OF THE BUILDING ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED. THE VALUE SHALL BE THE TOTAL COST OF THE
 PROJECT. OU VALUATION REFERENCE IS ICC (BVD),
 MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES.
  
 8)R308.4.THE FOLLOWING SHALL BE CONSIDERED SPECIFIC
 HAZARDOUS LOCATIONS FOR THE PURPOSES OF GLAZING: (5)
 GLAZING IN DOORS AND ENCLOSURE FOR HOT TUBS,
 WHIRLPOOLS, SAUNAS, STEAM ROOMS, BATHTUBS AND SHOWERS.
 GLAZING IN ANY PART OF A BUILDING WALL ENCLOSING THESE
 COMPARTMENTS WHERE THE BOTTOM EXPOSED EDGE OF THE
 GLAZING IS LESS THAN 60 INCHES MEASURED VERTICALL ABOVE
 ANY STANDING OR WALKING SURFACE. GLAZING IN THESE AREAS
 SHALL BE TEMPERED GLAZING.
  
 9)ON SHEET S4, INDICATE WHICHSTEEL COLUMN IS#1 /
 #2 / AND #3.
  
 10)R807.1 ATTIC ACCESS .
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER. SHOW THE ATTIC ACCESS FOR THENEW
 CONSTRUCTION AREA.
  
 11)G2447.1 (623.1) COOKING APPLIANCES .
 COOKING APPLIANCES THAT ARE DESIGNED FOR PERMANENT
 INSTALLATION, INCLUDING RANGES, OVENS, STOVES,
 BROILERS, GRILLS, FRYERS, GRIDDLES, HOT PLATES AND
 BARBECUES, SHALL BE TESTED IN ACCORDANCE WITH ANSI
 Z21.1 OR ANSI Z21.58 AND SHALL BE INSTALLED IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS. PROVIDE THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR THE GRILL. 106.1.2 ADDITIONAL DATA.
 THE BUILDING OFFICIAL MAY REQUIRE DETAILS,
 COMPUTATIONS, STRESS DIAGRAMS, AND OTHER DATA NECESSARY
 TO DESCRIBE THE CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION.
  
 12)PROVIDE ANABBREVATION LEGEND FOR ALL THE
 ABBREVATIONS SHOWN.
  
 13)R802.1.6.1TRUSS DESIGN DRAWINGS, PREPARED IN
 CONFORMANCE WITH SECTION R802.1.6.1 SHALL BE PROVIDED
 TO THE BUILDING OFFICIAL AND APPROVED PRIOR TO
 INSTALLATION.
  
 14)WHAT TYPE OF HURRICANE STRAPS WILL BE USED FOR THE
 TERILLIS RAFTERS?
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER