| Plan Review Notes For Permit 06120040 |
| Permit Number |
06120040 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-22 16:21:40 | *****DENIED***** | | | | | | | | | | | | 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE | | | PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.CONSTRUCTION AND / OR DEMOLITION OPERATIONS SHALL | | | NOT INTERFERE OR HINDER EMERGENCY RESPONDER ACCESS TO | | | THE SAID PROPERTY OR PROPERTIES IN THE VICINITY THEREOF | | | (INCLUDING FIRE LANES). | | | | | | 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 5.SHOW/DISPLAY THE SUITE NUMBER ON THE BUILDING TO BE | | | VISIBLE FROM SOUTH ROSEMARY AVENUE.AS PER WEST PALM | | | BEACH CODE, SUITE/TENANT SPACE NUMBERS SHALL BE NO LESS | | | THAN 3" IN HEIGHT AND 1" IN WIDTH.COORDINATION WITH | | | CITYPLACE MANAGEMENT MAY BE NEEDED TO MAITAIN | | | CONSISTENCY AS TO THE SIZE AND STYLE OF CHARACTERS. | | | | | | 6.SUBMITTED PLANS AND APPLICATION REFLECT THAT THE | | | SCOPE OF WORK IS FOR STOREFRONT ALTERATION ONLY, | | | HOWEVER, DOORS WITH PANIC HARDWARE WILL BE REQUIRED IN | | | OCCUPANCY OF 100 OR MORE PERSONS. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|