Plan Review Notes For Permit 06120040
Permit Number 06120040
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-12-22 16:21:40*****DENIED*****
  
  
  
 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND / OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY RESPONDER ACCESS TO
 THE SAID PROPERTY OR PROPERTIES IN THE VICINITY THEREOF
 (INCLUDING FIRE LANES).
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.SHOW/DISPLAY THE SUITE NUMBER ON THE BUILDING TO BE
 VISIBLE FROM SOUTH ROSEMARY AVENUE.AS PER WEST PALM
 BEACH CODE, SUITE/TENANT SPACE NUMBERS SHALL BE NO LESS
 THAN 3" IN HEIGHT AND 1" IN WIDTH.COORDINATION WITH
 CITYPLACE MANAGEMENT MAY BE NEEDED TO MAITAIN
 CONSISTENCY AS TO THE SIZE AND STYLE OF CHARACTERS.
  
 6.SUBMITTED PLANS AND APPLICATION REFLECT THAT THE
 SCOPE OF WORK IS FOR STOREFRONT ALTERATION ONLY,
 HOWEVER, DOORS WITH PANIC HARDWARE WILL BE REQUIRED IN
 OCCUPANCY OF 100 OR MORE PERSONS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722