| Plan Review Notes For Permit 06120040 |
| Permit Number |
06120040 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-01-03 17:03:17 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO | | | PERMIT PICKUP, FS713.13. | | | | | | 2.)DECLARE GOVERNING CODE, INCLUDING FBC 2004 | | | EXISTING BUILDING CODE. | | | | | | 3.)DECLARE LEVEL OF ALTERATION, FBC EXISTING BUILDING | | | CODE CH 3. | | | | | | 4.)PROVIDE WIND DESIGN CRITERIA FBC1603.1.4. | | | | | | 5.)PROVIDE A CODE SUMMARY; BUILDING TYPE FBC CHAPTER | | | 5 INCLUDING A OR B, OCCUPANCY FBC 3, SPRINKLED OR | | | UNSPRINKLED, BUILDING HEIGHT. | | | | | | 6.)D1, A COLUMN IS SHOWN WITH THE NOTE "REMOVE | | | EXISTING DRYWALL TO FRAMING SYSTEM."HOW IS FIRE | | | RATING AFFECTED?WAS THE BUILDING BUILT AS PROTECTED | | | OR UNPROTECTED, AND IS THIS STRUCTURAL? | | | | | | 7.)D1, ON TENANT SEPARATION WALLS THERE IS A NOTE | | | "REMOVE EXISTING DRYWALL TO FRAMING."HOW WILL THE 1 | | | HOUR TENANT SEPARATION BE MAINTAINED?PROVIDE A TESTED | | | ASSEMBLY OR CALCULATED FIRE RESISTANCE. | | | | | | 8.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER | | | OF RECORD, FBC*106.3.3. | | | | | | 9.)FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE | | | REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5), | | | FS553.79 (2). | | | | | | |
|