2007-01-03 17:03:17****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO
 PERMIT PICKUP, FS713.13.
  
 2.)DECLARE GOVERNING CODE, INCLUDING FBC 2004
 EXISTING BUILDING CODE.
  
 3.)DECLARE LEVEL OF ALTERATION, FBC EXISTING BUILDING
 CODE CH 3.
  
 4.)PROVIDE WIND DESIGN CRITERIA FBC1603.1.4.
  
 5.)PROVIDE A CODE SUMMARY; BUILDING TYPE FBC CHAPTER
 5 INCLUDING A OR B, OCCUPANCY FBC 3, SPRINKLED OR
 UNSPRINKLED, BUILDING HEIGHT.
  
 6.)D1, A COLUMN IS SHOWN WITH THE NOTE "REMOVE
 EXISTING DRYWALL TO FRAMING SYSTEM."HOW IS FIRE
 RATING AFFECTED?WAS THE BUILDING BUILT AS PROTECTED
 OR UNPROTECTED, AND IS THIS STRUCTURAL?
  
 7.)D1, ON TENANT SEPARATION WALLS THERE IS A NOTE
 "REMOVE EXISTING DRYWALL TO FRAMING."HOW WILL THE 1
 HOUR TENANT SEPARATION BE MAINTAINED?PROVIDE A TESTED
 ASSEMBLY OR CALCULATED FIRE RESISTANCE.
  
 8.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 9.)FIRE SPRINKLER PLANS REQUIRED IF SPRINKLERS ARE
 REQUIRED FOR CODE COMPLIANCE, FBC*106.3.5.1.1(5),
 FS553.79 (2).
  
  