| 2006-12-18 11:14:36 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| | REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. PLEASE NOTE THAT THERE IS AN OPEN GAS PERMIT FOR |
| | THE SAID RESIDENCE. THE OPEN GAS PERMIT IS#06020480 |
| | AND IT IS ATTACHED TO MASTER PERMIT #04101257 WHICH ARE |
| | SIGNED AND SEALED DRAWINGS. THE SUBMITTED GAS DRAWING |
| | FOR THE GENERATOR SHOULD BE SUBMITTED AS A REVISION TO |
| | THE GAS PERMIT AND IT SHALL BE SIGNED AND SEALED BY THE |
| | ARCHITECT OF RECORD FOR THE MASTER PERMIT #04101257. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | NOTE: PLEASE INDICATE THE PIPING MATERIALS. |
| | |
| | 3. TYPE OF GAS, (LP OR NATURAL) MUST BE INDICATED ON |
| | DRAWINGS. |
| | |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | NOTE: PLEASE REFERENCE THE ATTACHED PERMIT INFORMATION |
| | INDICATING GAS AT SAID RESIDENCE. THE BTU LOAD OF THE |
| | EXISTING AS WELL AS THE PROPOSED GENERATOR NEEDS TO BE |
| | INDICATED ON THE RESUBMITTED GAS REVISION. |
| | |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: THIS INCLUDES THE EXISTING AS WELL AS PROPOSD. |
| | |
| | 6. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | |
| | 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 |
| | NOTE: PLEASE SUBMIT MANUFACTURER SHEETS AND |
| | INSTALLATION INSTRUCTIONS OF THE PROPOSED GENERATOR |
| | WITH SETBACKS FROM STRUCTURES. MORE INFORMATION IS |
| | REQUIRED FROM THE SUBMITTED MANUFACTURER SHEETS SUCH AS |
| | THE NAME OF THE MANUFACTURER, THE SIZE OF THE |
| | GENERATOR, AND THE BTU LOAD. IF GAS DELIVERY PRESSURE |
| | INCREASES TO 2PSI PLEASE INCLUDE MANUFACTURER SHEETS OF |
| | THE MP REGULATORS. END OF COMMENTS: |
| | |