2006-12-05 11:11:16 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
 THE EQUIPMENT GROUNDING}CONDUCTOR MUST COMPLY WITH
 250.66. #4 MINIMUM FOR 200 AMPS.
  
 2}225.32:THE DISCONNECTING MEANS SHALL BE INSTALLED
 EITHER INSIDE OR OUTSIDE OF THE BUILDING OR STRUCTURE
 SERVED OR WHERE THE CONDUCTORS PASS THROUGH THE
 BUILDING OR STRUCTURE. THE DISCONNECTING MEANS SHALL BE
 AT A READILY ACCESSIBLE LOCATION NEAREST THE POINT OF
 ENTRANCE OF THE CONDUCTORS. FOR THE PURPOSES OF THIS
 SECTION, THE REQUIREMENTS IN 230.6 SHALL BE PERMITTED
 TO BE UTILIZED.
  
 3} INDICATE THE SIZE OF THE SERVICE RISER.
  
 4} THE GROUND BEING RAN FROM THE METER MUST BE REMOVED.
 IT VIOLATES 250.6 AND PARALLELS THE GROUNDED NEUTRAL.
 THE ISOLATED NEUTRAL MAY BE RUN WITH GROUND ONLY AFTER
 THE FIRST MEAS OF DISCONNECT.
  
 5} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2.
  