| Plan Review Notes For Permit 06120028 |
| Permit Number |
06120028 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-05 11:11:16 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | | | | 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. | | | THE EQUIPMENT GROUNDING}CONDUCTOR MUST COMPLY WITH | | | 250.66. #4 MINIMUM FOR 200 AMPS. | | | | | | 2}225.32:THE DISCONNECTING MEANS SHALL BE INSTALLED | | | EITHER INSIDE OR OUTSIDE OF THE BUILDING OR STRUCTURE | | | SERVED OR WHERE THE CONDUCTORS PASS THROUGH THE | | | BUILDING OR STRUCTURE. THE DISCONNECTING MEANS SHALL BE | | | AT A READILY ACCESSIBLE LOCATION NEAREST THE POINT OF | | | ENTRANCE OF THE CONDUCTORS. FOR THE PURPOSES OF THIS | | | SECTION, THE REQUIREMENTS IN 230.6 SHALL BE PERMITTED | | | TO BE UTILIZED. | | | | | | 3} INDICATE THE SIZE OF THE SERVICE RISER. | | | | | | 4} THE GROUND BEING RAN FROM THE METER MUST BE REMOVED. | | | IT VIOLATES 250.6 AND PARALLELS THE GROUNDED NEUTRAL. | | | THE ISOLATED NEUTRAL MAY BE RUN WITH GROUND ONLY AFTER | | | THE FIRST MEAS OF DISCONNECT. | | | | | | 5} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|