| Plan Review Notes For Permit 06120023 |
| Permit Number |
06120023 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-11 11:32:29 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT | | | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE | | | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS | | | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. | | | | | | 2} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|