Plan Review Notes
Plan Review Notes For Permit 06120002
Permit Number 06120002
Review Stop G
Sequence Number 1
Notes
Date Text
2007-01-05 17:17:54DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 A. SEE THE FOLLOWING PROVISO FROM THE PLAN REVIEW DATED
 7-7-06 AND REVIEW NOTES FROM SUBSEQUENT REVISIONS
 SUBMITTED 9-1-06, 11-1-06 & 12-19-06:
  
  
 7-7-06
 PASSED/PROVISO
  
 REVISION IS ALSO REQUIRED FOR THE GAS
 ISOMETRIC RISER DIAGRAM, WHICH SHALL
 CORRELATE WITH THE GAS
 EQUIPMENT/CONNECTED LOAD AND THE MANUF. SPECIFICATION
 SHEETS INDICATING THE BTU
 LOAD FOR EACH GAS APPLIANCE.
  
 GAS ISOMETRIC NOT APPROVED AT THIS TIME.
 PLUMBING ONLY APPROVED. SEPARATE GAS
 PERMIT REQUIRED.
  
 9-1-06
 REVISION DENIED
  
 A. SHT P-15 SUBMIT THE FOLLOWING:
  
 1. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 INDICATE THE MODEL NUMBER FOR EACH GAS
 APPLIANCE, AND EACH APPLIANCE MANUF.
 SPECIFICATION SHEET SHALL SHOW LISTING.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
 11-1-06
 REVISIONDENIED
 REFERENCE:
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS P-1, P-5, P-8 PLUMBING TECHNICAL CODES OK, BUT
 THE TITLE BLOCK FOR THE ARCHITECT DOES NOT HAVE THE
 REQUIRED BUSINESS NUMBER, (CERTIFICATE OF
 AUTHORIZATION), IN THE TITLE BLOCK. THIS HAS BEEN
 COMMENTED ON SINCE FEB. 06 IN THE FIRST PLAN REVIEW FOR
 PLUMBING. EIGHT MONTHS IS SUFFICIENT TIME TO APPLY FOR
 A CERTIFICATE OF AUTHORIZTION. EITHER REMOVE "GRW
 ARCHITECTS" FROM THE SHEETS, OR INDICATE THE BUSINESS
 NUMBER IN THE TITLE BLOCK AS REQUIRED IN FAC
 61G1-16.004(2) & FS 481.219.
  
 2. WHEN RESUBMITTING REVISIONS, DISABLE ALL REVISION
 CLOUDS FROM PREVIOUS REVISIONS AND ONLY SHOW THE
 CLOUDED REVISIONS BEING SUBMITTED FOR THE PRESENT
 REVISION. ALSO MAKE SURE THE CLOUDS ARE BOLD ENOUGH TO
 SEE. THE LAST REVISIONS WERE DIFFICULT TO FIND. SECTION
 104.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
 12-19-06
 REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT P-1.AS INDICATED ON PREVIOUS REVISION REVIEW,
 MAKE SURE THE CLOUDS ARE BOLD ENOUGH TO SEE. THE
 REVISION FOR NUMBER 5 IS FAINT & HARD TO SEE. A NEW
 REVISION WAS FOUND ON THE PLAN. THIS NUMBER 6 REVISION
 IS NOT CLOUDED AND NOT INDICATED IN THE REVISION INDEX.
 PLEASE CLOUD ALL REVISIONS WITH A HEAVY CLOUD, AND SHOW
 ALL REVISIONS ON THE REVISION INDEX.
  
 2. SHT P-5. REVISION #6 NOT CLOUDED. PLEASE CLOUD ALL
 REVISIONS. IT APPEARS THAT THERE IS A NEW TOILET ROOM.
 IF SO PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.18, 11-4.19, & 11-4.22 AND ALL
 SUBSECTIONS. SUBMIT A REVISION FOR THE SANITARY RISER
 DIAGRAM THAT REFLECTS THE FLOOR PLAN, SHOWING THE NEW
 TOILET ROOM PIPING AND INDICATING ALL PIPE SIZES,
 TRAPS, VENTS ETC. SECTION 106.3.5.1.3.
  
 3. SHT P-8REVISION 5 NOT SHOWN ON THE REVISION INDEX,
 NOR IS THE REVISION CLOUDED. PLEASE CLOUD ALL REVISIONS
 AND INDICATED THE REVISION NUMBER ON THE REVISION
 INDEX. SECTION 106.1.1. - REVISION 3 IS NOT CLOUDED,
 NOR DOES IT INDICATE WHAT CHANGE HAS BEEN MADE. PLEASE
 CLARIFY. SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
 NO MENTION OF THE GAS PLANS BEING APPROVED HAS BEEN
 INDICATED IN ANY OF THE REVISIONS, OR WHEN THE PERMIT
 WAS ISSUED. PLEASE RESPOND TO THE PROVISO AND WHEN THE
 PROVISO IS ADDRESSED THEN THE GAS PERMIT APPLICATION
 CAN BE RESUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
  
  
  
 .