| | PERMIT #06120001 ELECTRICAL PLAN REVIEW |
| | 290 BARCELONA ROAD 4/14/09 |
| | WEST PALM BEACH, FL. |
| | |
| | |
| | |
| | |
| | NOTE- ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| | OTHERWISE NOTED. |
| | SHEET E2.1 |
| | 1} PANEL "P" IS LISTED AS 150 AMP ON THE PANEL |
| | SCHEDULE, SHOWN AS BEING FED FROM A 80 AMP BREAKER IN |
| | PANEL "C" AND NOTE #13 LISTS IT AS A 80 AMP PANEL. |
| | CORRELATE THESE NUMBERS TO INDICATE THE INTENDED |
| | INSTALLATION. 408.4, AND RECALCULATE THE LOAD FOR PANEL |
| | C PER 220. |
| | |
| | 2} NOTE #12 LISTS 3-#3 CU AS FEEDERS FOR PANEL P, THE |
| | LOAD IS SHOWN AS 145.41 AMPS IN THE TOTAL SERVICE |
| | CALCULATION (LISTED AS 145.21 KVA IN PANEL P ESTIMATED |
| | DEMAND LOAD) ON THE PANEL SCHEDULE. SEE 310.16 FOR WIRE |
| | SIZES AND ALLOWABLE AMPERAGES. |
| | |
| | 3} THE PANEL AMPERAGES IN THE TOTAL SERVICE CALCULATION |
| | ARE LISTED IN AMPS AND AS KVA ON THE PANEL SCHEDULES, |
| | PLEASE CORRECT. 408.4 |
| | |
| | 4} THE FEEDERS TO FOR DISCONNECT DP ARE ONLY RATED FOR |
| | 350 AMPS AND THE LOAD IS LISTED AS 393.5 AMPS. SEE |
| | 310.15(B)(6) FOR FEEDER SIZES. |
| | |
| | 5} THERE SHOULD NOT BE A GROUNDING ELECTRODE CONDUCTOR |
| | ON PANEL "P". PANELS P AND C ARE ON THE SAME STRUCTURE, |
| | P IS FED FROM C AND A GROUNDING ELECTRODE IS SHOWN |
| | INSTALLED ON THAT PANEL PER 250.32. PANEL P SHOULD BE |
| | GROUNDED FROM THE EQUIPMENT GROUND RAN WITH THAT |
| | FEEDER. SEE 250.122 FOR SIZE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |