| 2008-07-28 16:13:07 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC,2004 FBC CHAPTER |
| | 1 AS AMENDED AND FOUND NONCOMPLIANT WITH THE |
| | FOLLOWING: |
| | |
| | REVISION DENIED |
| | |
| | 1} SHEET E1.1 THE LOW VOLTAGE PANEL IN THE STAIRWELL OF |
| | THE CABANA DOES NOT COMPLY WITH THE CLEARANCE |
| | REQUIREMENTS OF 110.26. |
| | |
| | 2} A SMOKE ALARM IS REQUIRED ".OUTSIDE EACH SEPARATE |
| | SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE |
| | BEDROOMS" THE STUDY IS BY DEFINITION.A BEDROOM. NFPA-72 |
| | REQUIRES ALARMS OR DETECTORS WITHIN 20 FEET OF COOKING |
| | APPLIANCES BE SILENCING OR PHOTOELECTRIC. SEE |
| | 11.8.3.5(4). |
| | |
| | 3} THE RECEPTACLES ON THE COUNTERTOP ON EITHER SIDE OF |
| | THE RANGE ARE REQUIRED TO BE GFI PROTECTED PER |
| | 210.8(A)(6). I HAVE REDLINED COMMENTS 2 & 3 ON THE |
| | PREVIOUS REVISION WHICH THE ARCHITECT PROBABLY WAS NOT |
| | AWARE. |
| | |
| | NOTE: SHEET E1.2 APPEARS TO BE COMPLIANT AND WILL NOT |
| | NEED TO BE RESUBMITTED. |
| | |
| | 5} SHEET E2.1THE 350 MCM FEEDERS TO PANEL "DP" ARE NOT |
| | LARGE ENOUGH TO CARRY THE 393 AMP LOAD. SEE NOTE #4 FOR |
| | THE RISER DIAGRAM.SEE TABLE 310.15(B)(6). |
| | |
| | 6} THE DISCONNECT "DP" IS RATED FOR 300 AMPS, NOT LARGE |
| | ENOUGH FOR THE LOAD.SEE NOTE #16, ALSO REVISE NOTE #3T |
| | |
| | 7} THERE IS NO FEED FOR PANELS "C" AND "P" LISTED IN |
| | "DP PANEL SCHEDULE.NOTE #12 INDICATES PANEL "C" MAY BE |
| | FEEDING PANEL"P",CONTRARY TO NOTE #7, AND NOT SHOWN ON |
| | PANEL"C" SCHEDULE. |
| | |
| | 8} PANEL "DP" IS LISTED AS 300 AMPS, SEE NOTE #19. |
| | |
| | 9} THE ESTIMATED LOADS AT THE BOTTOM OF THE SCHEDULES |
| | IS RATED IN KVA. THE "TOTAL SERVICE FOR THE MAIN HOUSE |
| | AND CABANA" THE BOTTOM MIDDLE OF THE SHEET LISTS RATING |
| | IN AMPS "DP" AND "P" ARE INCORRECT. RECHECK ALL |
| | CALCULATIONS AND CORRELATE THE LOADS. |
| | |
| | 10} THE TANKLESS HEATERS ON SHEET E1.1 ARE NOT ON ANY |
| | OF THE SCHEDULES, INDICATE IF THEY ARE GAS. IF THEY ARE |
| | ELECTRIC THEY WILL POSSIBLY LOAD THE SERVICE OVER 400 |
| | AMPS. |
| | |
| | 11} LOCATE PANEL "P" ON THE PLAN. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |