| Plan Review Notes For Permit 06120001 |
| Permit Number |
06120001 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-09-26 13:47:04 | THE ORIGINAL SCOPE OF WORK IS BEING EXPANDED TO INCLUDE | | | REPLACING THE ROOF ASSEMBLY OF THE EXISTING STRUCTURE. | | | | | | REVISED TRUSS DRAWINGS ARE DENIED. | | | | | | 1) SUBMIT TWO SETS OF SIGNED AND SEALED ROOF FRAMING | | | PLANS SPECIFYING THE CONNECTORS THAT WILL BE USED TO | | | ATTACH THE NEW TRUSSES TO THE EXISTING BUILDING. | | | | | | 2) SUBMIT TWO SETS OF TRUSS DRAWINGS AND TRUSS LAYOUTS | | | THAT HAVE BEEN SIGNED AND SEALED BY THE TRUSS ENGINEER | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR | | | THE STRUCTURE. | | | | | | 3) SPECIFY THE COSTS OF THIS ADDITIONAL WORK SO THAT | | | THE VALUE OF THE JOB CAN BE ADJUSTED AND ADDITIONAL | | | PERMIT FEES CAN BE DETERMINED. | | | | | | 4) SUBMIT PRODUCT APPROVALS FOR ROOFING IF IT WILL BE | | | DIFFERENT THAN THE ONES THAT WERE APPROVED WHEN THE | | | PERMIT WAS ISSUED. | | | | | | - ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|