| Plan Review Notes For Permit 06120001 |
| Permit Number |
06120001 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2008-04-21 08:52:28 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | REVISION TO MECHANICAL PLANS | | | *** DENIED *** | | | 1) COOLING LOAD CALCULATIONS ON FILE ARE CALLING FOR | | | A/C SYSTEM 1 TO BE A TOTAL OF 36,423 COOLING BTU'S, | | | REVISED MECHANICAL PLANS ARE SHOWING A TOTAL OF 48,500 | | | COOLING BTU'S. PER 2004 FBC 13-607.1.ABC.1.1 THE PLANS | | | CAN ONLY CALL FOR 15% MORE THAN THE COOLING LOAD | | | CALCULATIONS, PLEASE CORRECT. | | | | | | 2) COOLING LOAD CALCULATIONS ON FILE ARE CALLING FOR | | | A/C SYSTEM 2 TO BE A TOTAL OF 41,781 COOLING BTU'S, | | | REVISED MECHANICAL PLANS ARE SHOWING A TOTAL OF 60,000 | | | COOLING BTU'S. PER 2004 FBC 13-607.1.ABC.1.1 THE PLANS | | | CAN ONLY CALL FOR 15% MORE THAN THE COOLING LOAD | | | CALCULATIONS, PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|