| 2007-04-06 07:52:06 | DENIED BY BUILDING (2ND REVIEW) |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) SUBMIT A COPY OF THE PAID RECEIPT FOR THE IMPACT |
| | FEES. |
| | |
| | 3) THE INSTALLATION DRAWINGS AND DESIGN PRESSURE TABLES |
| | IN THE NOA 05-1018.01 SUBMITTED FOR THE PGT SINGLE HUNG |
| | WINDOWS ARE ILLEGIBLE. |
| | |
| | 4)PAGE 5 OF 7 OF THE PRODUCT APPROVAL NOA FOR THE PGT |
| | MULLIONS IS ILLEGIBLE. |
| | |
| | 5) SUBMIT PRODUCT APPROVALS FOR THE TRUSS CONNECTORS, |
| | STRAPS HANGERS AND OTHER SPECIED STRUCTURAL ANCHORS. |
| | SEE COMMENT #22 FROM FIRST REVIEW. |
| | |
| | 6) THE PAGES CONTAINING THE APPROVED ASSEMBLIES ARE |
| | MISSING FROM THE PRODUCT APPROVAL NOA 03-0501.02 FOR |
| | THE GAF MODIFIED ROOF SYSTEM. SPECIFY WHICH ONE OF THE |
| | APPROVED ASSEMBLIES WILL BE INSTALLED. SPECIFY THE |
| | FASTENING OPTION AND DESIGN PRESSURE FOR THE SYSTEM |
| | (CIRCLE THE ITEMS ON THE PAGE OF THE APPROVED ASSEMBLY |
| | SELECTED). ENHANCED FASTENING WILL BE REQUIRED FOR ROOF |
| | ZONE3 (-89PSF) AND POSSIBLY ROOF ZONE 2 (-59.2) |
| | DEPENDING ON THE SYSTEM THAT IS USED. NONE OF THE |
| | ASSEMBLIES THAT HAVE GENERAL LIMITATION #9 WILL WORK |
| | BECAUSE THIS LIMITATION DOES NOT ALLOW ENHANCED |
| | FASTENING. THEREFORE, ONLY THE ASSEMBLIES WITH GENERAL |
| | LIMITATION #7, WHICH ALLOWS THE DESIGN PRESSURE TO BE |
| | INCREASED BY INCREASING THE FASTENER DENSITIES |
| | CALCULATED BY USING ROOFING APPLICATION STANDARD 117 |
| | CALCULATIONS. SUBMIT RAS 117 CALCULATIONS FOR THE |
| | SELECTED ASSEMBLY. SEE ITEM # 23 FROM FIRST REVIEW. |
| | |
| | 7) SUBMIT PRODUCT APPROVALS FOR ARCH TOP WINDOWS. SEE |
| | ITEM # 20 OF FIRST REVIEW. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |