| Plan Review Notes For Permit 06120001 |
| Permit Number |
06120001 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-21 11:57:38 | *** DENIED *** | | | 1) RETURN AIR TRANSFER DUCT TO MASTER SUITE NEEDS TO BE | | | 16". BALANCED RETURN AIR MAY BE ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND | | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | | (SQUARE INCHES) OF THE SUPPLY DUCT | | | ENTERING THE ROOM OR SPACE IT'S SERVING | | | AND THE DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | | PROPER RETURN AIR BALANCE. | | | (C)HABITABLE ROOMS ONLY SHALL BE | | | REQUIRED TO MEET THESE REQUIREMENTS FOR | | | PROPER BALANCED RETURN AIR EXCLUDING | | | BATHROOMS, CLOSETS, STORAGE ROOMS AND | | | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY | | | AIR INTO THE MASTER SUITE SHALL BE | | | INCLUDED. PER 2004 FBC/R M1602.4 . | | | | | | 2) NOT ALL SUPPLY AND RETURN AIR DUCTS ARE SIZED SEE | | | HIGH LIGHTED DUCTS ON PLANS PAGE M1.1 AND M1.2, PLEASE | | | SIZE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|