| Plan Review Notes For Permit 06120001 |
| Permit Number |
06120001 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-19 15:28:48 | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, METER | | | ENCLOSURE, DISCONNECTS AND PANELS, SO THAT COMPLIANCE | | | WITH ARTICLES 225 AND 230 CAN BE REVIEWED. | | | | | | 2} THE EQUIPMENT GROUNDING CONDUCTOR MUST COMPLY WITH | | | 250.66. SEE NOTE #1 REGARDING THE SUM OF THE SERVICE | | | ENTRANCE CONDUCTORS. MINIMUM #1/0 CU.( SHEET E2.1). | | | | | | 3} PLEASE ADD A NOTE FOR HEXAGONAL #22, SHEET E2.1. | | | | | | 4} PLEASE CORRECT NOTE #16, THE EQUUIPMENT BEING | | | REFERENCED IS A DISCONNECT. | | | | | | 5} PLEASE CORRECT PANEL "DP"LOAD CALC TOTAL.SEE SHEET | | | E2.1. | | | | | | 6} SMOKE ALARMS ARE REQUIRED INSIDE AND IMMEDIATLY | | | OUTSIDE THE " PRIVATE READING ROOM" , WHICH IS A | | | "BEDROOM" BY DEFINITION IN THE FBC. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | | | | |
|