| Plan Review Notes For Permit 06111087 |
| Permit Number |
06111087 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-01-17 17:00:05 | *****UNSAT***** | | | | | | THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN | | | REVIEW (12/21/2006) STILL NEED TO BE ADDRESSED: | | | | | | | | | 6.SHOW THE SUITE NUMBER FOR THIS TENANT SPACE ON THE | | | PROPER ELEVATION.AS PER WEST PALM BEACH CODE, NUMBERS | | | SHALL BE NO LESS THAN 3" IN HEIGHT AND 1" IN WIDTH. | | | ADD TO PLAN SHEET A5 ON THE APPROPIATE EXTERIOR | | | ELEVATION. | | | | | | 8.INDICATE ON THE PLANS THE LOCATION OF THE FIRE | | | PROTECTION SYSTEMS (I.E. FIRE SPRINKLERS, SMOKE | | | DETECTORS, ETC.) AND WHETHER THE LISTED SCOPE OF WORK | | | WILL AFFECT THEIR OPERATION.PROVIDE A LAYOUT OF THE | | | SPRINKLER SYSTEM.RECTIFY PLAN SHEET FA-1 IN REGARDS | | | TO STROBES CANDELAS MINIMUM (SEE ELECTRICAL COMMENT | | | #7) | | | | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|