Plan Review Notes
Plan Review Notes For Permit 06111087
Permit Number 06111087
Review Stop E
Sequence Number 2
Notes
Date Text
2007-01-15 11:13:12*** UNSAT 2ND REVIEW***
  
 TD AMERITRADE
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED ALONG WITH SOME NEW COMMENTS BASED
 ON CHANGES MADE TO PLANS.
  
 ** PLEASE SEE THE COMMENTS BELOW ARE TAKEN DIRECTLY
 FROM PREVIOUS REVIEW IN THE SAME NUMERICAL ORDER. THEY
 WILL CONTAIN A NO, OK, OR NO/OK.
 A) NO WILL BE FOLLOWED BY FURTHER EXPLANATION OF THE
 PREVIOUS COMMENT.
 B) OK, MAY REFERENCE TO ANY NEW NOTES, HOWEVER WILL
 HAVE PREVIOUS NOTE REMOVED.
 C) NO/OK, WILL BE FOLLOWED BY FURTHER EXPLANATION AS
 PART OF THE COMMENT MAY NOT HAVE BEEN ADDRESSED FULLY
 AND PART OF THE PREVIOUS COMMENT MAY BE OK.
  
 ** ANY NEW NOTES WILL BE AT THE BOTTOM AND IDENTIFIED
 AS*** NEW NOTES ***.
  
 ** PLEASE KNOW THAT A DETAILED RESPONSE TO THE COMMENTS
 IN THE SAME NUMERICAL ORDER WOULD HELP IN THE REVIEW
 PROCESS. PLEASE SEE THE RESPONSES DO NOT CORRELATE TO
 THE PREVIOUS REVIEW COMMENTS.
  
  
 1) NOTE:NO/OK. PLEASE SEE THAT MOST OF THE TITLE
 BLOCKS ON EACH SHEET WAS REVISED; HOWEVER PLEASE SEE
 COVER SHEET WHICH STILL CONTAINS THE ARCHITECTURAL FIRM
 WHICH DOES NOT CONTAIN A CERTIFICATE OF AUTHORIZATION
 NUMBER ALSO KNOWN AS A FIRM LICENSE NUMBER THROUGH THE
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION.
 THIS COMMENT IS MADE AS IT IS REQUIRED TO BE CORRECTED
 EVEN THOUGH IT WILL NOT AFFECT THE ELECTRICAL PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS FOR
 ARCHITECT AND ARCHITECTURAL FIRM AS REQUIRED UNDER
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004 AND FLORIDA
 STATUTES 481.219
 PLEASE SEE MISSING FIRM LICENSE NUMBER ALSO KNOWN AS
 THE CERTIFICATE OF AUTHORIZATION NUMBER.
 PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER
 OF THE ARCHITECT OF RECORD.
 ** THIS INFORMATION IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADE REVIEWER(S).
  
 2) NOTE: OK.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE:OK/NO THIS WAS DONE; HOWEVER SEE COMMENTS
 BELOW AS THIS WILL BE REQUIRED FOR NEW ENERGY
 CALCULATIONS. PLEASE SEE TWO DIFFERENT SETS OF
 ENERGY/COM-CHECK SUBMISSIONS.
 ** THIS PREVIOUS NOTE VERBIAGE WILL BE LEFT FOR
 INFORMATION ONLY AS COMMENT WAS ADDRESSED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE ENERGY CALCULATIONS SUBMITTED SHALL BE
 SIGNED, DATED AND SEALED BY THE DESIGNER/ENGINEER
 RESPONSIBLE. PLEASE ALSO SEE OTHER COMMENTS BASED ON
 THESE SHEETS.
 PLEASE ALSO SEE SECTION ON THE ENERGY CALCULATIONS
 WHICH REQUIRES THE OWNER/AGENT TO ALSO SIGN.
  
 6) NOTE: OK.
  
 7) NOTE:NO. PLANS WERE SUBMITTED; HOWEVER COMPLIANCE
 WITH THE MINIMUM REQUIREMENTS OF THE SECTIONS GIVEN IN
 PREVIOUS REVIEW HAS NOT BEEN MET. PLEASE SEE THAT THE
 FBC CHAPTER 11 FOR ADA REQUIREMENTS EXCEED THAT OF THE
 NFPA-72 AND THE MORE RESTRICTIVE SHALL APPLY. PLEASE
 SEE THE LIGHTING LEVELS FOR STROBES MUST MEET
 11-4.28.3(4).
 PLEASE SEE THE MINIMUM LEVELS FOR AUDIBLE DEVICES ARE
 NOT SHOWN. PLEASE SEE 11-4.28.2.
 PLEASE SEE A NOTE WAS ADDED TO THE PLAN WHICH STATES A
 4.28 FOR ADA REQUIREMENTS? PLEASE SPECIFY THE CODE
 SECTIONS WHICH ARE RELEVANT AND AS GIVEN IN THIS TEXT
 NOTE AND PREVIOUS TEXT NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MINIMUM FIRE ALARM PLANS SHOWING LAYOUT OF
 NEW OR EXISTING DEVICES MEETING THE 2004 FBC AND 2002
 NFPA-72 SHALL BE SUBMITTED. PLEASE KNOW, EVEN AS SCOPE
 OF WORK IS REQUIRED UNDER SEPARATE PLANS AND PERMIT THE
 BASE SYSTEM SHALL BE SHOWN IN BASE BUILD OUT PLANS.
 PLEASE INDICATE NEW OR EXISTING HORN AND STROBES
 MEETING 2004 FBC 11-4.28.1,.2.3(4).
 PLEASE SEE .3(4) WHICH REQUIRE A MINIMUM OF 75 CANDELAS
 WHICH IS ABOVE THE MINIMUMS REQUIRED IN NFPA-72. FBC
 ADMIN SECTION 106.1.2, 106.1.1.1
  
 8) NOTE: OK, HOWEVER SEE NEW NOTES.
  
 9) NOTE:NO, PLEASE SEE THERE ARE NOW TWO SUBMITTED
 LIGHTING COMPLIANCE CALCULATIONS SUBMITTED. PLEASE SEE
 EITHER ONE CAN BE REVIEWED FOR COMPLIANCE AND
 COORDINATION WITH THE PLANS.
 PLEASE SEE ONE DOES NOT SUPPLY THE INFORMATION AND IS
 STILL INDICATING METHOD A AND IT IS NOT KNOWN TO THIS
 OFFICE HOW METHOD A APPLIES.
 PLEASE ALSO SEE A COM-CHECK VERSION WAS ALSO SUBMITTED
 WHICH STATES 90.1/2001 EDITION. PLEASE KNOW THAT ANY
 VERSIONS MUST BE DONE AND STATE THE 2004 FBC. PLEASE
 ALSO SEE THE OCCUPANCY SPECIFIED IN CALCULATIONS STATE
 "RETAIL". THIS IS NOT POSSIBLE AS THIS IS NOT A RETAIL
 SPACE. PLEASE SEE TABLES 415.2.C.1, 415.2.B.1, THESE
 TABLES DO CONTAIN THE OCCUPANCY AND USE AS REQUIRED.
 PLEASE BE SURE TO CORRELATE ALL OF THE FIXTURE WATTAGES
 WITH THAT WHICH IS PERMITTED.
 ** IF THIS WERE A RETAIL SPACE, THEN PLANS WOULD BE
 REQUIRED TO BE CHANGED TO MERCANTILE OCCUPANCY. PLEASE
 SEE ARCHITECTURAL SHEETS WHICH CONTAIN THE STATED
 OCCUPANCY.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE ENERGY CALCULATIONS SUBMITTED DO NOT
 CORRELATE WITH THE PLANS SUBMITTED. PLEASE SEE THE
 NUMBER OF FIXTURES AND WATTAGE DO NOT MATCH. THERE IS A
 SUBSTANTIAL DIFFERENCE.
 PLEASE SEE FBC 2004 13-415.2.ABC.1, AND PLEASE INDICATE
 THE MAXIMUM LIGHTING POWER DENSITIES.
 PLEASE KNOW, BASED ON METHOD "A" THIS WILL NOT GIVE YOU
 THE CORRECT INFORMATION AS NEEDED AS THE SQ FT WILL BE
 ENTERED UNDER 5K SQ FT.
 PLEASE ALSO SEE THE AREAS WHERE CONTROL MENTIONS
 MANUAL, INSTEAD OF THE REQUIRED AUTO SHUT OFF. PLEASE
 SEE THE FOLLOWING COMMENT.
  
 10) NOTE:NO/OK, PLEASE SEE SOME COMPLIANCE HAS BEEN
 MET HOWEVER THE OVER RIDES TIMES ON ALL DEVICES SHALL
 BE STATED. THE MAXIMUM TIMES WERE GIVEN ON PREVIOUS
 REVIEW DEPENDING ON THE DEVICE CHOSEN.
 PLEASE SEE SOME ROOMS WHICH ARE CONSIDERED SEPARATE
 SPACES DO NOT CONTAIN ANY CONTROL DEVICES AS REQUIRED
 PER 13-415.1.ABC.1.2.
 PLEASE ALSO SEE THE INGRESS/EGRESS AREA AT MAIN
 ENTRANCE, COULD NOT LOCATE ANY DEVICES TO OVER RIDE
 SYSTEM. 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE WHAT APPEARS TO BE A MOTION DEVICE SHOWN ON
 PLANS WHICH DOES NOT SHOW ANY CONNECTION POINT.
 (HALLWAY AREA).
 ** PLEASE SEE THE DETAIL PROVIDED FOR THE CONNECTION OF
 EMERGENCY AND EXIT LIGHTS. THE NOTE MENTIONS TO CONNECT
 AHEAD OF THE SWITCHING DEVICE; HOWEVER THE EM/EXT LTS
 AS SHOWN APPEAR TO BE SHOWN ON THE LOAD SIDE OF THE
 SWITCH IN DETAIL. PLEASE KNOW THAT THIS IS SOMETHING
 THAT IS COMMON AND SHOULD BE KNOWN, HOWEVER PLEASE KNOW
 THAT SINCE THE IMPLEMENTATION OF CHAPTER 13 OF THE FBC,
 THE AHJ HAS HAD NUMEROUS SITUATIONS WHERE THE EMERGENCY
 AND EXIT LIGHTS ARE BEING CONNECTED ON THE LOAD SIDE OF
 THE OCCUPANCY SENSORS, THE LOAD OF SIDE OF THE LCP AND
 THE OVER RIDES DEVICES.PLEASE ADJUST DETAIL OR CALL
 THIS REVIEWER TO GO OVER THIS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE PROVIDE AN AUTOMATED MEANS OF SHUTTING OFF
 LIGHTING AFTER NORMAL SCHEDULED HOURS.
 PLEASE PROVIDE SYSTEM OR METHODS OF CONTROL. PLEASE BE
 SURE THAT ALL DEVICE SYMBOLS ON PLANS CORRELATE WITH
 THE SYMBOL LEGEND PROVIDE.
 PLEASE INDICATE THE MAXIMUM TIMES ON ANY OVER RIDE
 DEVICES AS REQUIRED.
 (PLEASE KNOW A MAXIMUM 30MINS IS PERMITTED ON OCCUPANCY
 TYPE DEVICES AND 4HRS MAX ON TIMER TYPE OVER RIDES).
 PLEASE PROVIDE TIME OF SCHEDULING.
 ETC.
  
 11) NOTE:OK. *** NOT TO BE USED OR CONTAIN EQUIPMENT
 AS DEFINED FOR AN IT ROOM.
  
 12) NOTE: NO/OK, PLEASE SEE A NOTE HAS BEEN ADDED TO
 PLANS AND THE WALLS SEEM TO HAVE BEEN MOVED AS PER
 SCALE THE CLEARANCE FOR EACH PANEL AND DIFFERENT
 VOLTAGES SEEM TO BE MET.
 PLEASE SEE HOWEVER THAT NOW THAT THE RISER HAS BEEN
 REVISED (SEE NEW MAIN), THE LOCATION OF NEW EQUIPMENT
 ADDED TO RISER WHICH IS STATED AS EXISTING IS NOT
 LOCATED ON PLANS. PLEASE SEE THAT VERIFICATION FOR
 COMPLIANCE WITH 110.26 STILL CAN NOT BE CONFIRMED.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE AS SHOWN ON PLANS, THE ELECTRICAL EQUIPMENT
 BEING NOTED AS EXISTING AND BEING NOTED IN AN EXISTING
 ELECTRICAL CLOSET DOES NOT MEET CODE. PLEASE SEE THE
 MINIMUM CLEARANCES FOR ALL EQUIPMENT SHALL MEET
 110.26.
 THIS ARE SHALL NOT BE STORAGE ALSO.
  
 13) NOTE: OK, HOWEVER SEE NOTE ABOVE WITH RESPECT TO
 CLEARANCES.
  
 14) NOTE: OK, HOWEVER SEE NOTE #12 ABOVE WITH RESPECT
 TO CLEARANCES.
  
 ** NEW NOTES **
  
 15) NOTE: PLEASE CLARIFY THE NEW LOCATION OF THE NEW
 LCP WHICH HAS BEEN ADDED TO PLANS. PLEASE CLARIFY IF
 THIS TYPE OF PANEL CONTAINS OVER CURRENT PROTECTION OF
 ANY KIND OR NOT? PLEASE KNOW IF IT DOES, IT WILL BE
 REQUIRED TO BE RELOCATED PER 110.26, 408.7, 240.24(C)
 AND (D).
  
 16) NOTE: PLEASE CLARIFY CIRCUITING FROM THE PANEL H TO
 THE LCP AS THE THERE IS NO SCHEDULE ETC SHOWN FOR
 THIS.
 PLEASE KNOW THE PANEL DIRECTORIES SHOULD BE SPECIFIC TO
 THE ROOMS AND AREAS IN WHICH THEY CIRCUITED TO. IE;
 OFFICE 1 RECEPTS, BREAKRM RECEPTS, ETC
  
 17) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE
 COMPLIANCE. THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
 ONE SET OF PLANS MAY BE RETAINED BY THE OFFICE AT THIS
 TIME.
  
 18) NOTE: PLEASE SEE THAT FEES OF $2.397.60 ARE DUE TO
 VALUE FOR SCOPE OF WORK ADJUSTMENT.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]