| 2006-12-21 16:49:08 | *****DENIED***** |
| | |
| | |
| | |
| | 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE |
| | PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. |
| | |
| | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION SHALL COMPLY WITH NFPA 241. |
| | |
| | 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT |
| | INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID |
| | PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES). |
| | |
| | 4. COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL |
| | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR |
| | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 5.PLEASE INDICATE THE MINIMUM INTERIOR FINISH |
| | CLASSIFICATION FOR WALLS AND CEILING IN TERMS OF CLASS |
| | A, B, OR C IN ACCORDANCE WITH NFPA 101. |
| | |
| | 6.SHOW THE SUITE NUMBER FOR THIS TENANT SPACE ON THE |
| | PROPER ELEVATION.AS PER WEST PALM BEACH CODE, NUMBERS |
| | SHALL BE NO LESS THAN 3" IN HEIGHT AND 1" IN WIDTH. |
| | |
| | 7.PROVIDE A LIFE SAFETY PLAN SHEET TO INCLUDE ALL |
| | COMMON PATHS OF TRAVEL TO EXITS AND TO INCLUDE FIRE |
| | EXTINGUISHER LOCATIONS. |
| | |
| | 8.INDICATE ON THE PLANS THE LOCATION OF THE FIRE |
| | PROTECTION SYSTEMS (I.E. FIRE SPRINKLERS, SMOKE |
| | DETECTORS, ETC.) AND WHETHER THE LISTED SCOPE OF WORK |
| | WILL AFFECT THEIR OPERATION. |
| | |
| | 9.IF THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM |
| | IS/ARE MODIFIED DUE TO THE SCOPE OF WORK, SEPARATE |
| | PERMIT AND PLANS WILL BE REQUIRED. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |