2006-12-21 16:49:08*****DENIED*****
  
  
  
 1.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE
 PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
 3.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES).
  
 4. COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.PLEASE INDICATE THE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING IN TERMS OF CLASS
 A, B, OR C IN ACCORDANCE WITH NFPA 101.
  
 6.SHOW THE SUITE NUMBER FOR THIS TENANT SPACE ON THE
 PROPER ELEVATION.AS PER WEST PALM BEACH CODE, NUMBERS
 SHALL BE NO LESS THAN 3" IN HEIGHT AND 1" IN WIDTH.
  
 7.PROVIDE A LIFE SAFETY PLAN SHEET TO INCLUDE ALL
 COMMON PATHS OF TRAVEL TO EXITS AND TO INCLUDE FIRE
 EXTINGUISHER LOCATIONS.
  
 8.INDICATE ON THE PLANS THE LOCATION OF THE FIRE
 PROTECTION SYSTEMS (I.E. FIRE SPRINKLERS, SMOKE
 DETECTORS, ETC.) AND WHETHER THE LISTED SCOPE OF WORK
 WILL AFFECT THEIR OPERATION.
  
 9.IF THE FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM
 IS/ARE MODIFIED DUE TO THE SCOPE OF WORK, SEPARATE
 PERMIT AND PLANS WILL BE REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED.
  
  