| 2006-12-17 13:42:19 | *** UNSAT *** |
| | |
| | TD AMERITRADE |
| | |
| | ** PLEASE SEE COMMENTS BELOW ARE IN NO WAY ALL POSSIBLE |
| | COMMENTS FOR THE ISSUANCE AS SOME ITEMS NOT SUBMITTED |
| | OR CLARIFIED ON PLANS CAN BE REVIEWED FOR CODE |
| | COMPLIANCE AT THIS TIME. |
| | PLEASE KNOW THERE MAY BE COMMENTS ON THE FOLLOWING |
| | REVIEW BASED ON PLANS SUBMITTED AND POSSIBLE CHANGES |
| | MADE IN THE DESIGNS ETC. |
| | |
| | 1) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS |
| | FOR ARCHITECT AND ARCHITECTURAL FIRM AS REQUIRED UNDER |
| | FLORIDA ADMINISTRATIVE CODE 61G1-16.004 AND FLORIDA |
| | STATUTES 481.219 |
| | PLEASE SEE MISSING FIRM LICENSE NUMBER ALSO KNOWN AS |
| | THE CERTIFICATE OF AUTHORIZATION NUMBER. |
| | PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER |
| | OF THE ARCHITECT OF RECORD. |
| | ** THIS INFORMATION IS REQUIRED FOR ALL SHEETS AND FOR |
| | ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | TRADE REVIEWER(S). |
| | |
| | 2) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS |
| | FOR ENGINEER AND ENGINEERING FIRM AS REQUIRED UNDER |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA |
| | STATUTES 471.023. |
| | PLEASE SEE MISSING FIRM LICENSE NUMBER ALSO KNOWN AS |
| | THE CERTIFICATE OF AUTHORIZATION NUMBER. |
| | PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER |
| | OF THE ENGINEER OF RECORD. |
| | ** THIS INFORMATION IS REQUIRED FOR ALL SHEETS AND FOR |
| | ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | TRADE REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE SEE ONLY ONE SET OF THE PLANS SUBMITTED |
| | ARE SIGNED AND SEALED BY THE ENGINEER OF RECORD. PLEASE |
| | SEE FAC 61G15-23.002 WHICH REQUIRED BOTH SETS AND ALL |
| | DOCUMENTS TO BE SIGNED, DATED AND SEALED. |
| | |
| | 4) NOTE: PLEASE SEE BOTH THE ARCHITECTURAL AND |
| | ENGINEERING SHEETS WERE NOT DATED BY THE DESIGN |
| | PROFESSIONALS WHEN SIGNED AND SEALED AS REQUIRED IN |
| | SECTIONS AS NOTED ABOVE. |
| | FS 481, 471, FAC 61G15-23.002, 61G1-16.004. |
| | THIS IS REQUIRED OF ALL SHEETS AND TRADES. |
| | |
| | 5) NOTE: PLEASE SEE ENERGY CALCULATIONS SUBMITTED SHALL |
| | BE SIGNED, DATED AND SEALED BY THE DESIGNER/ENGINEER |
| | RESPONSIBLE. PLEASE ALSO SEE OTHER COMMENTS BASED ON |
| | THESE SHEETS. |
| | PLEASE ALSO SEE SECTION ON THE ENERGY CALCULATIONS |
| | WHICH REQUIRES THE OWNER/AGENT TO ALSO SIGN. |
| | |
| | 6) NOTE: PLEASE SEE THAT ALL OF THE FOLLOWING RELEVANT |
| | CODES SHALL BE STATED ON SAID PLANS. PLEASE KNOW, |
| | STATEMENTS WHICH MENTIONS "LATEST EDITION" SHALL NOT BE |
| | MADE AS CODE CHANGES AND DATE SUBMITTED DICTATE WHICH |
| | CODES PROJECT IS UNDER AND THE "LATEST ADOPTED EDITION" |
| | AT TIME OF APPLICATION MAY NOT BE RELEVANT. |
| | PLEASE SEE THE FOLLOWING SHALL BE LISTED AT A MINIMUM. |
| | PLEASE ALSO SEE ANY CODES WHICH MAY BE STATED FROM |
| | OTHER TRADES. |
| | 2002 NFPA-70 (NEC), 2002 NFPA-72, 2003 NFPA-101 AND THE |
| | 2004 FBC. THIS SHALL BE STATED ON THE ELECTRICAL PLANS |
| | ALSO. |
| | |
| | 7) NOTE: PLEASE SEE MINIMUM FIRE ALARM PLANS SHOWING |
| | LAYOUT OF NEW OR EXISTING DEVICES MEETING THE 2004 FBC |
| | AND 2002 NFPA-72 SHALL BE SUBMITTED. PLEASE KNOW, EVEN |
| | AS SCOPE OF WORK IS REQUIRED UNDER SEPARATE PLANS AND |
| | PERMIT THE BASE SYSTEM SHALL BE SHOWN IN BASE BUILD OUT |
| | PLANS. |
| | PLEASE INDICATE NEW OR EXISTING HORN AND STROBES |
| | MEETING 2004 FBC 11-4.28.1,.2.3(4). |
| | PLEASE SEE .3(4) WHICH REQUIRE A MINIMUM OF 75 CANDELAS |
| | WHICH IS ABOVE THE MINIMUMS REQUIRED IN NFPA-72. FBC |
| | ADMIN SECTION 106.1.2, 106.1.1.1 |
| | |
| | 8) NOTE: PLEASE SEE THE TWO BATH ROOMS SHALL INDICATE A |
| | BATTERY BACK UP FIXTURE OF SOME SORT TO MEET NFPA-101 |
| | 7.8, 7.9. |
| | PLEASE SEE POSSIBLE COMMENTS FROM FIRE MARSHAL'S OFFICE |
| | ALSO. |
| | |
| | 9) NOTE: PLEASE SEE ENERGY CALCULATIONS SUBMITTED DO |
| | NOT CORRELATE WITH THE PLANS SUBMITTED. PLEASE SEE THE |
| | NUMBER OF FIXTURES AND WATTAGE DO NOT MATCH. THERE IS A |
| | SUBSTANTIAL DIFFERENCE. |
| | PLEASEFBC 2004 13-415.2..ABC.1, AND PLEASE INDICATE |
| | THE MAXIMUM LIGHTING POWER DENSITIES. |
| | PLEASE KNOW, BASED ON METHOD "A" THIS WILL NOT GIVE YOU |
| | THE CORRECT INFORMATION AS NEEDED AS THE SQ FT WILL BE |
| | ENTERED UNDER 5K SQ FT. |
| | PLEASE ALSO SEE THE AREAS WHERE CONTROL MENTIONS |
| | MANUAL, INSTEAD OF THE REQUIRED AUTO SHUT OFF. PLEASE |
| | SEE THE FOLLOWING COMMENT. |
| | |
| | 10) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1, |
| | .1.2 AND .1.3. |
| | PLEASE PROVIDE AN AUTOMATED MEANS OF SHUTTING OFF |
| | LIGHTING AFTER NORMAL SCHEDULED HOURS. |
| | PLEASE PROVIDE SYSTEM OR METHODS OF CONTROL. PLEASE BE |
| | SURE THAT ALL DEVICE SYMBOLS ON PLANS CORRELATE WITH |
| | THE SYMBOL LEGEND PROVIDE. |
| | PLEASE INDICATE THE MAXIMUM TIMES ON ANY OVER RIDE |
| | DEVICES AS REQUIRED. |
| | (PLEASE KNOW A MAXIMUM 30MINS IS PERMITTED ON OCCUPANCY |
| | TYPE DEVICES AND 4HRS MAX ON TIMER TYPE OVER RIDES). |
| | PLEASE PROVIDE TIME OF SCHEDULING. |
| | ETC. |
| | |
| | 11) NOTE: PLEASE SEE THE ROOM BEING NOTED AS THE "TECH |
| | ROOM" SEEMS TO POSSIBLY MEET CLASSIFICATION OF AN "IT" |
| | ROOM AS STATED IN NFPA-75 CHAPTER 2. PLEASE CLARIFY USE |
| | OF ROOM AND EQUIPMENT BEING INSTALLED. AS THE BUSINESS |
| | AND USE MOST CERTAINLY DOES INVOKE POSSIBLY "IT" ROOM |
| | REQUIREMENTS. |
| | PLEASE SEE CONSTRUCTION OF WALLS, REQUIREMENTS FOR |
| | DISCONNECTION OF POWER, AND POSSIBLE FIRE DAMPERS MAY |
| | BE REQUIRED. |
| | PLEASE SEE NFPA-75, AND NFPA-70 (NEC) 645. |
| | |
| | 12) NOTE: PLEASE SEE AS SHOWN ON PLANS, THE ELECTRICAL |
| | EQUIPMENT BEING NOTED AS EXISTING AND BEING NOTED IN AN |
| | EXISTING ELECTRICAL CLOSET DOES NOT MEET CODE. PLEASE |
| | SEE THE MINIMUM CLEARANCES FOR ALL EQUIPMENT SHALL MEET |
| | 110.26. |
| | THIS ARE SHALL NOT BE STORAGE ALSO. |
| | |
| | 13) NOTE: PLEASE SEE THE CONDUCTORS AS SHOWN ON THE |
| | SECONDARY SIDE OF THE TRANSFORMER DO NOT MEET 310.16, |
| | AND 240.21C FOR THE RATINGS REQUIRED. PLEASE SEE THE |
| | NEXT COMMENT AS THE CONDUCTORS ON THE SECONDARY SIDE OF |
| | THE TRANSFORMER ARE REQUIRED TO TERMINATE IN OVER |
| | CURRENT PROTECTION. |
| | PLEASE SEE TAP RULES. |
| | |
| | 14) NOTE: PLEASE SEE 408.16, 240.21 AS NOTED ABOVE, |
| | PANEL AS SHOWN ON RISER INDICATES THIS PANEL BEING OF |
| | MLO, WITH NO MCB. PLEASE VERIFY THIS AT THE JOB-SITE. |
| | PLEASE KNOW IF A MCB( MAIN CIRCUIT BREAKER) IS NOT |
| | LOCATED ON THE SECONDARY SIDE OF THE TRANSFORMER ONE |
| | WILL BE REQUIRED AND THE OVER CURRENT PROTECTION WILL |
| | NOT ONLY BE REQUIRED TOLIMIT THE LOAD ON THE |
| | CONDUCTORS AS SHOWN, IT WILL ALSO BE REQUIRED TO BE |
| | SIZED PER THE LOAD. |
| | 240.4, 310.16 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |