Plan Review Notes
Plan Review Notes For Permit 06111087
Permit Number 06111087
Review Stop E
Sequence Number 1
Notes
Date Text
2006-12-17 13:42:19*** UNSAT ***
  
 TD AMERITRADE
  
 ** PLEASE SEE COMMENTS BELOW ARE IN NO WAY ALL POSSIBLE
 COMMENTS FOR THE ISSUANCE AS SOME ITEMS NOT SUBMITTED
 OR CLARIFIED ON PLANS CAN BE REVIEWED FOR CODE
 COMPLIANCE AT THIS TIME.
 PLEASE KNOW THERE MAY BE COMMENTS ON THE FOLLOWING
 REVIEW BASED ON PLANS SUBMITTED AND POSSIBLE CHANGES
 MADE IN THE DESIGNS ETC.
  
 1) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 FOR ARCHITECT AND ARCHITECTURAL FIRM AS REQUIRED UNDER
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004 AND FLORIDA
 STATUTES 481.219
 PLEASE SEE MISSING FIRM LICENSE NUMBER ALSO KNOWN AS
 THE CERTIFICATE OF AUTHORIZATION NUMBER.
 PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER
 OF THE ARCHITECT OF RECORD.
 ** THIS INFORMATION IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADE REVIEWER(S).
  
 2) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 FOR ENGINEER AND ENGINEERING FIRM AS REQUIRED UNDER
 FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA
 STATUTES 471.023.
 PLEASE SEE MISSING FIRM LICENSE NUMBER ALSO KNOWN AS
 THE CERTIFICATE OF AUTHORIZATION NUMBER.
 PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER
 OF THE ENGINEER OF RECORD.
 ** THIS INFORMATION IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADE REVIEWER(S).
  
 3) NOTE: PLEASE SEE ONLY ONE SET OF THE PLANS SUBMITTED
 ARE SIGNED AND SEALED BY THE ENGINEER OF RECORD. PLEASE
 SEE FAC 61G15-23.002 WHICH REQUIRED BOTH SETS AND ALL
 DOCUMENTS TO BE SIGNED, DATED AND SEALED.
  
 4) NOTE: PLEASE SEE BOTH THE ARCHITECTURAL AND
 ENGINEERING SHEETS WERE NOT DATED BY THE DESIGN
 PROFESSIONALS WHEN SIGNED AND SEALED AS REQUIRED IN
 SECTIONS AS NOTED ABOVE.
 FS 481, 471, FAC 61G15-23.002, 61G1-16.004.
 THIS IS REQUIRED OF ALL SHEETS AND TRADES.
  
 5) NOTE: PLEASE SEE ENERGY CALCULATIONS SUBMITTED SHALL
 BE SIGNED, DATED AND SEALED BY THE DESIGNER/ENGINEER
 RESPONSIBLE. PLEASE ALSO SEE OTHER COMMENTS BASED ON
 THESE SHEETS.
 PLEASE ALSO SEE SECTION ON THE ENERGY CALCULATIONS
 WHICH REQUIRES THE OWNER/AGENT TO ALSO SIGN.
  
 6) NOTE: PLEASE SEE THAT ALL OF THE FOLLOWING RELEVANT
 CODES SHALL BE STATED ON SAID PLANS. PLEASE KNOW,
 STATEMENTS WHICH MENTIONS "LATEST EDITION" SHALL NOT BE
 MADE AS CODE CHANGES AND DATE SUBMITTED DICTATE WHICH
 CODES PROJECT IS UNDER AND THE "LATEST ADOPTED EDITION"
 AT TIME OF APPLICATION MAY NOT BE RELEVANT.
 PLEASE SEE THE FOLLOWING SHALL BE LISTED AT A MINIMUM.
 PLEASE ALSO SEE ANY CODES WHICH MAY BE STATED FROM
 OTHER TRADES.
 2002 NFPA-70 (NEC), 2002 NFPA-72, 2003 NFPA-101 AND THE
 2004 FBC. THIS SHALL BE STATED ON THE ELECTRICAL PLANS
 ALSO.
  
 7) NOTE: PLEASE SEE MINIMUM FIRE ALARM PLANS SHOWING
 LAYOUT OF NEW OR EXISTING DEVICES MEETING THE 2004 FBC
 AND 2002 NFPA-72 SHALL BE SUBMITTED. PLEASE KNOW, EVEN
 AS SCOPE OF WORK IS REQUIRED UNDER SEPARATE PLANS AND
 PERMIT THE BASE SYSTEM SHALL BE SHOWN IN BASE BUILD OUT
 PLANS.
 PLEASE INDICATE NEW OR EXISTING HORN AND STROBES
 MEETING 2004 FBC 11-4.28.1,.2.3(4).
 PLEASE SEE .3(4) WHICH REQUIRE A MINIMUM OF 75 CANDELAS
 WHICH IS ABOVE THE MINIMUMS REQUIRED IN NFPA-72. FBC
 ADMIN SECTION 106.1.2, 106.1.1.1
  
 8) NOTE: PLEASE SEE THE TWO BATH ROOMS SHALL INDICATE A
 BATTERY BACK UP FIXTURE OF SOME SORT TO MEET NFPA-101
 7.8, 7.9.
 PLEASE SEE POSSIBLE COMMENTS FROM FIRE MARSHAL'S OFFICE
 ALSO.
  
 9) NOTE: PLEASE SEE ENERGY CALCULATIONS SUBMITTED DO
 NOT CORRELATE WITH THE PLANS SUBMITTED. PLEASE SEE THE
 NUMBER OF FIXTURES AND WATTAGE DO NOT MATCH. THERE IS A
 SUBSTANTIAL DIFFERENCE.
 PLEASEFBC 2004 13-415.2..ABC.1, AND PLEASE INDICATE
 THE MAXIMUM LIGHTING POWER DENSITIES.
 PLEASE KNOW, BASED ON METHOD "A" THIS WILL NOT GIVE YOU
 THE CORRECT INFORMATION AS NEEDED AS THE SQ FT WILL BE
 ENTERED UNDER 5K SQ FT.
 PLEASE ALSO SEE THE AREAS WHERE CONTROL MENTIONS
 MANUAL, INSTEAD OF THE REQUIRED AUTO SHUT OFF. PLEASE
 SEE THE FOLLOWING COMMENT.
  
 10) NOTE: PLEASE SEE FBC CHAPTER 13, 13-415.1.ABC.1.1,
 .1.2 AND .1.3.
 PLEASE PROVIDE AN AUTOMATED MEANS OF SHUTTING OFF
 LIGHTING AFTER NORMAL SCHEDULED HOURS.
 PLEASE PROVIDE SYSTEM OR METHODS OF CONTROL. PLEASE BE
 SURE THAT ALL DEVICE SYMBOLS ON PLANS CORRELATE WITH
 THE SYMBOL LEGEND PROVIDE.
 PLEASE INDICATE THE MAXIMUM TIMES ON ANY OVER RIDE
 DEVICES AS REQUIRED.
 (PLEASE KNOW A MAXIMUM 30MINS IS PERMITTED ON OCCUPANCY
 TYPE DEVICES AND 4HRS MAX ON TIMER TYPE OVER RIDES).
 PLEASE PROVIDE TIME OF SCHEDULING.
 ETC.
  
 11) NOTE: PLEASE SEE THE ROOM BEING NOTED AS THE "TECH
 ROOM" SEEMS TO POSSIBLY MEET CLASSIFICATION OF AN "IT"
 ROOM AS STATED IN NFPA-75 CHAPTER 2. PLEASE CLARIFY USE
 OF ROOM AND EQUIPMENT BEING INSTALLED. AS THE BUSINESS
 AND USE MOST CERTAINLY DOES INVOKE POSSIBLY "IT" ROOM
 REQUIREMENTS.
 PLEASE SEE CONSTRUCTION OF WALLS, REQUIREMENTS FOR
 DISCONNECTION OF POWER, AND POSSIBLE FIRE DAMPERS MAY
 BE REQUIRED.
 PLEASE SEE NFPA-75, AND NFPA-70 (NEC) 645.
  
 12) NOTE: PLEASE SEE AS SHOWN ON PLANS, THE ELECTRICAL
 EQUIPMENT BEING NOTED AS EXISTING AND BEING NOTED IN AN
 EXISTING ELECTRICAL CLOSET DOES NOT MEET CODE. PLEASE
 SEE THE MINIMUM CLEARANCES FOR ALL EQUIPMENT SHALL MEET
 110.26.
 THIS ARE SHALL NOT BE STORAGE ALSO.
  
 13) NOTE: PLEASE SEE THE CONDUCTORS AS SHOWN ON THE
 SECONDARY SIDE OF THE TRANSFORMER DO NOT MEET 310.16,
 AND 240.21C FOR THE RATINGS REQUIRED. PLEASE SEE THE
 NEXT COMMENT AS THE CONDUCTORS ON THE SECONDARY SIDE OF
 THE TRANSFORMER ARE REQUIRED TO TERMINATE IN OVER
 CURRENT PROTECTION.
 PLEASE SEE TAP RULES.
  
 14) NOTE: PLEASE SEE 408.16, 240.21 AS NOTED ABOVE,
 PANEL AS SHOWN ON RISER INDICATES THIS PANEL BEING OF
 MLO, WITH NO MCB. PLEASE VERIFY THIS AT THE JOB-SITE.
 PLEASE KNOW IF A MCB( MAIN CIRCUIT BREAKER) IS NOT
 LOCATED ON THE SECONDARY SIDE OF THE TRANSFORMER ONE
 WILL BE REQUIRED AND THE OVER CURRENT PROTECTION WILL
 NOT ONLY BE REQUIRED TOLIMIT THE LOAD ON THE
 CONDUCTORS AS SHOWN, IT WILL ALSO BE REQUIRED TO BE
 SIZED PER THE LOAD.
 240.4, 310.16
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW