2006-12-20 10:42:50DENIED
 REFERENCE: FBC-2004 PLUMBING AND FBC-2004 CHAPTER 1
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. 106.3.5.4 RESIDENTIAL (ONE AND TWO
 FAMILY) SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL
 WASTE, VENTS, TRAPS WITH SIZES, AND
 CLEANOUT LOCATIONS.
 NOTE: NEED SANITARY ISOMETRIC OF NEW LAUNDRY PLUMBING
 WITH THE FOLLOWING REQUIREMENTS FOR THE WASHING
 MACHINE.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE STANDPIPE ON RESUBMITTED
 DRAWINGS.
 (C) 708.9 ACCESS. ACCESS SHALL BE PROVIDED TO ALL
 CLEANOUTS. PLEASE INDICATE THE CLEANOUT FOR THE WASHING
 MACHINE AT FOUR FEET ABOVE FINNISH FLOOR (4' AFF) AND
 KEEP THE CLEANOUT FULL SIZE OF THREE INCH (3") ON THE
 RESUBMITTED DRAWINGS.
  
 END OF COMMENTS:
  