2007-02-06 18:27:59DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3)SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS.
 EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM)
 SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE
 RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL
 NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM
 AN ADJACENT PROJECTION OR WALL. SPECIFY THE DISTANCE
 BETWEEN THE ADDITION AND THE EXISTING GARAGE ON THE
 SITE PLAN.
  
 4) SPECIFY THE PITCH OF THE SLOPED ROOF ON THE PLANS.
 FBC * 106.1.2.
  
 5) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WIT H 1 /
 8 INCH (3.2 MM) MINIMUM TO ? INCH (6.4 MM) MAXIMUM
 OPENINGS
  
 6) SUBMIT ENERGY CALCULATIONS AS REQUIRED BY FBC
 CHAPTER 13.
  
 7)THE STRUCTURAL NOTES ON A4 REFERENCE THE 2001 FBC.
 PLEASE CORRECT. SEE MARKS ON PLAN.
  
 8) THE 2004 FBC REFRENCES THE 2002 EDITIONS OF ACI 318
 AND 315. PLEASE CORRECT.
  
 9) SECTION B ON A4 SPECIFIES " HELTA 20 " CONNECTORS.
 ARE THESE SUPPOSED TO BE SIMPSON HETAL 20 CONNECTORS?
 PLEASE CORRECT.
  
 10) ON SECTION B ON A4 THERE IS A HUC 412 ANCHOR
 SPECIFIED FOR THE BEAM TO 6 X 6 COLUMN CONNECTION. I
 COULD NOT LOCATE THIS ANCHOR IN THE USP OR SIMPSON
 CATALOGS. PLEASE SPECIFY THE MANUFACTURER AND SUBMIT
 PRODUCT APPROVALS FOR IT. THE ROOF FRAMING PLAN ON A5
 SPECIFIES A USP KCCQ525-6 AT THIS LOCATION PLEASE
 CLARIFY.
  
 11)A PB66 COLUMN ANCHOR IS SPECIFIED AT THE BASE OF
 THE 6 X 6 COLUMNS ON A4. THE UPLIFT FOR THIS ANCHOR IS
 1640 #. THE UPLIFT AT THE TOP OF THE COLUMNS IS 5440#
 ON A5. PLEASE REVIEW THESE ANCHORS TO ENSURE THE UPLIFT
 LOAD TRANSFER.
  
 12) R613.6.2 MASONRY, CONCRETE OR OTHER STRUCTURAL
 SUBSTRATE.
 WHERE THE WOOD SHIM OR BUCK THICKNESS IS LESS THAN 1?
 INCHES (38 MM), WINDOW AND DOOR ASSEMBLIES SHALL BE
 ANCHORED THROUGH THE MAIN FRAME OR BY JAMB CLIP OR
 SUBFRAME SYSTEM, IN ACCORDANCE WITH THE MANUFACTURERS
 PUBLISHED INSTALLATION INSTRUCTIONS. ANCHORS SHALL BE
 SECURELY FASTENED DIRECTLY INTO THE MASONRY, CONCRETE
 OR OTHER STRUCTURAL SUBSTRATE MATERIAL. UNLESS
 OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME TO THE
 ROUGH OPENING SUBSTRATE.
 WHERE THE WOOD BUCK THICKNESS IS 1? INCHES (38 MM) OR
 GREATER, THE BUCK SHALL BE SECURELY FASTENED TO
 TRANSFER LOAD TO THE MASONRY, CONCRETE OR OTHER
 STRUCTURAL SUBSTRATE AND THE BUCK SHALL EXTEND BEYOND
 THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME. WINDOW
 AND DOOR ASSEMBLIES SHALL BE ANCHORED THROUGH THE MAIN
 FRAME OR BY JAMB CLIP OR SUBFRAME SYSTEM OR THROUGH THE
 FLANGE TO THE SECURED WOOD BUCK IN ACCORDANCE WITH THE
 MANUFACTURERS PUBLISHED INSTALLATION INSTRUCTIONS.
 UNLESS OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT
 FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE
 MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE
 LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF
 SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED
 TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME ASSEMBLY
 TO THE SECURED WOOD BUCK. PLEASE REVISE THE BUCK
 DETAILS ON A5 TO COMPLY WITH CODE.
  
 13) THE VALUES LISTED IN THE COMPONENT AND CLADDING
 TABLE ON A5 IS FOR ROOFS WITH A > 10 TO 30 DEGREE
 SLOPE. THE PRESSURES WILL BE HIGHER FOR THE FLAT ROOF.
 PLEASE CORRECT. SEE TABLE R 301.2(2).
  
 14) THE ROOF ZONE FASTENING ZONE FIGURE ON A5 IS
 INCORRECT. SEE FIGURE R 301.2(8) AND FIGURE 1609.6.2.2.
 THE OUTSIDE CORNERS OF FLAT AND HIP ROOFS ARE ZONE 3.
  
 15) THE WALL ZONE FIGURE ON A5 IS INCORRECT. THE
 CORNERS ARE ZONE 5 AND THE INTERIOR IS ZONE 4. PLEASE
 CORRECT. SEE FIGURES LISTED ABOVE.
  
 16)THE "HELTA 20"CONNECTORS SPECIFIED ON A5 SHOULD
 BE HETAL 20. PLEASE CORRECT.
  
 17) HETAL 20 CONNECTORS ARE EMBED TYPE AND CAN NOT BE
 USED AS SPECIFIED IN THE EXISTING WALL TIE BEAM AT THE
 COVERED PORCH. PLEASE CORRECT.
  
 18) THE H10 CONNECTORS ARE WOOD TO WOOD CONECTORS AND
 CAN NOT BE USED WHERE SPECIFIED AT THE EXISTING WALL OR
 THE NEW CONCRETE WALL OF THE LAUNDRY ROOM. PLEASE
 SPECIFY A MASONRY TO TRUSS CONNECTOR.
  
 19) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 20) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 21) SUBMIT PRODUCT APPROVALS FOR THE FLAT ROOF OF
 COVERED PORCH. SPECIFY THE APPROVED SYSTEM AND THE BASE
 SHEET FASTENING SYSTEM AND DESIGN PRESSURES FROM THE
 PRODUCT APPROVAL. CIRCLE THE APPROPRIATE INFORMATION.
 IF ENHANCED FASTENING IS REQUIRED, SUBMIT RAS 117
 CALCULATIONS PER LIMITATION #7 OF PRODUCT APPROVAL.
  
 22)THE PRODUCT APPROVAL FOR THE PGT SH-701 IMPACT
 WINDOWS IS EXPIRED. PLEASE SUBMIT CURRENT PRODUCT
 APPROVALS. SEE FL239-R7 AND NOA 05-1018.01.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  