Plan Review Notes
Plan Review Notes For Permit 06111071
Permit Number 06111071
Review Stop L
Sequence Number 9
Notes
Date Text
2009-07-29 18:01:27***LANDSCAPE ELECTRICAL REVIEW FAILED***
  
 1. LANDSCAPE PLAN SHALL BE REVISED TO REFLECT THE NEW
 LOCATIONS OF THE SITE LIGHTING SHOWN ON THE REVISED
 ELECTRICAL PLAN.
  
 2. THE PROPOSED LIGHTING ALONG THE ENTRY ROAD ON THIS
 SITE IS SHOWN IN A DIFFERENT LOCATION ON THE SPRINGHILL
 SUITES (06111067) PLAN. ALL PLANS MUST BE CONSISTANT.
  
 3. THE PROPOSED LIGHT IN THE TERMINAL LANDCAPE ISLAND
 AT THE SOUTH END OF THE PARKING ROW SHALL BE LOCATED AT
 THE EDGE OF THE ISLAND TO MATCH THE LOCATION OF THE
 LIGHT POLE IN THE ISLAND TO THE EAST. THE PROPOSED
 LIGHT ADJACENT TO THE DUMPSTER ENCLOSURE WILL BE IN
 CONFLICT WITH THE PROPOSED TREE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.