| Plan Review Notes For Permit 06111071 |
| Permit Number |
06111071 |
|
| Review Stop |
E |
| Sequence Number |
9 |
|
| Notes |
| Date |
Text |
| 2009-06-01 09:33:51 | *** REDLINED PLANS **** | | | | | | LOCATIONS REDLINED AS TYPICAL. | | | REV FOR 301A, 301B | | | | | | 1) NOTE: ALL LIGHTING CONTROLS IN ANY LOCATION WHICH | | | ARE DEEMED ACCESSIBLE AND FALL UNDER ADA GUIDELINES | | | SHALL MEET 11-4.27.4. THIS MAY REQUIRE SOME DEVICES | | | WHICH STILL REQUIRE AUTOMATED MEANS TO BE OF A | | | PUSHBUTTON TYPE. THIS IS BEING NOTED AS A QUESTION CAME | | | TO THIS OFFICE FOR THE USE OF TWIST TYPE TIMERS. THEY | | | WOULD ONLY BE PERMITTED IN AREAS WHICH ARE NOT ADA. | | | | | | | | | 11-4.27.4 OPERATION. CONTROLS AND OPERATING MECHANISMS | | | SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE | | | TIGHT GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE | | | FORCE REQUIRED TO ACTIVATE CONTROLS SHALL BE NO GREATER | | | THAN 5 LBF (22.2 N). | | | | | | | | | 2) NOTE: IT HAS BEEN DETERMINED THAT LIGHTING IN | | | ELECTRICAL ROOMS, ELEVATOR EQUIPMENTS ROOMS, PUMP ROOM | | | AND OTHER ROOMS CONTAINING ELECTRICAL EQUIPMENT WILL | | | NOT NEED TO BE CONTROLLED PER FBC CHAPTER 13. THERE WAS | | | A REVISION TO THE CHAPTER IN THE CURRENT CODE. HOWEVER | | | THE INTENT OF NEC 110.26D IS MORE RESTRICTIVE AND WAS | | | ALSO REVISED. | | | STANDARD SINGLE POLE SWITCHES MAY BE USED. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|