2009-03-09 15:14:11PLUMBING PLAN REVIEW:
 DENIED:
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. THE NOTE AT GAS METER & REGULATOR ASSEMBLY SHOULD BE
 CHANGED TO 2050 CFH @ 2 LB- 213'
  
 2. THE NOTE AFTER THE FIRST TEE SHOULD BE 1" GAS @ 650
 CFH
  
 3. THE NEW RISER DIAGRAM IS MISSING THE PIPING FOR THE
 FIREPLACE. IF THE FIREPLACE HAS NOT BEEN DELETED THE
 NOTE AFTER THE FIRST TEE SHOULD BE 1" @ 730 CFH
  
 4 UNDERGROUND PIPING NEEDS TO BE LABELED AS TO WHAT
 MATERIAL IS BEING USED.
  
 6. ***NOTE*** THE PIPE SIZES ARE NOT CONSISTENT. FOR
 EXAMPLE, UNDERGROUND PIPE IS SHOWN STARTING OUT AS 3/4"
 , YET CONTINUING ON BECOMES 2" PIPE.
  
 REVIEW BY LARRY WAGNER