| Plan Review Notes For Permit 06111071 |
| Permit Number |
06111071 |
|
| Review Stop |
G |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2009-03-09 15:14:11 | PLUMBING PLAN REVIEW: | | | DENIED: | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. THE NOTE AT GAS METER & REGULATOR ASSEMBLY SHOULD BE | | | CHANGED TO 2050 CFH @ 2 LB- 213' | | | | | | 2. THE NOTE AFTER THE FIRST TEE SHOULD BE 1" GAS @ 650 | | | CFH | | | | | | 3. THE NEW RISER DIAGRAM IS MISSING THE PIPING FOR THE | | | FIREPLACE. IF THE FIREPLACE HAS NOT BEEN DELETED THE | | | NOTE AFTER THE FIRST TEE SHOULD BE 1" @ 730 CFH | | | | | | 4 UNDERGROUND PIPING NEEDS TO BE LABELED AS TO WHAT | | | MATERIAL IS BEING USED. | | | | | | 6. ***NOTE*** THE PIPE SIZES ARE NOT CONSISTENT. FOR | | | EXAMPLE, UNDERGROUND PIPE IS SHOWN STARTING OUT AS 3/4" | | | , YET CONTINUING ON BECOMES 2" PIPE. | | | | | | REVIEW BY LARRY WAGNER | | | (561) 805???6692 | | | FAX (561) 653???2692 | | | E???MAIL [email protected] |
|