Plan Review Notes
Plan Review Notes For Permit 06111071
Permit Number 06111071
Review Stop P
Sequence Number 5
Notes
Date Text
2008-05-08 12:33:31 
 DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2001 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS: 3RD REVIEW:
  
 ********FROM PREVIOUS REVIEWS: 4TH REVIEW:
  
 **********FROM PREVIOUS REVIEWS: 5TH REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK (INFORMATIONAL ONLY)
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
 16. OK
 17. OK
 18. OK
 19. RESPONSE NOTED, NOT APPLICABLE
 20. OK.
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
 28. OK
 29. OK
 30. OK
 31. OK
 32. OK
 33. OK
  
 34. INDICATE A NUMBER DESIGNATION FOR EACH RISER
 INCLUDING ALL SANT., WATER, STORM, CONDENSATE. (EXAMPLE
 SANT-1, SANT-2, RWL-1, RWL-2, CON-1, CON-2, W-1, W-2
 ETC.). THIS WILL AID IN TRACKING ALL RISERS FROM THE
 UNDERGROUND PIPING THROUGH THE ROOF. SECTIONS
 106.3.5.1.3 & SECTION 106.1.1.--INDICATE WHICH
 RISER IS TYPICAL OF WHICH RISER ISOMETRIC DIAGRAM.
 (EXAMPLE SANT-1 SANT-4 TYPICAL OF DETALI 4 SHT P401) --
 INDICATE ROOM NUMBER EACH RISER CAN BE LOCATED.
 ****RESPONSE NOTED, BUT SHEET P503 HAS NOT BEEN
 SUBMITTED.
 ******RESPONSE NOTED, BUT RESPONSE DOES NOT ADDRESS THE
 WATER RISERS, STORM RISERS, OR CONDENSATE RISERS.
 ********RESPONSE NOTED, BUT THERE ARE STILL RISER
 DESIGNATIONS MISSING ON THE FIRST FLOOR.
 **********RESPONSE NOTED, BUT THERE ARE TWO RISERS
 DESIGNATED AS CW-76 AND NO RISER CW-75 INDICATED ON THE
 FLOOR PLAN AND NO RISER HW/CW-86 SHOWN ON THE FLOOR
 PLAN.
  
 35. OK
 36. OK
 37. OK
  
 *****NEW COMMENTS 3RD REVIEW*****
  
  
 1B. OK
  
 2B. SHT G-001 NOT ALL SHEETS SHOWN ON THE DRAWING INDEX
 HAVE BEEN SUBMITTED, AND SOME SHEETS ARE OUT OF ORDER.
 PLEASE CORRELATE THE SHEETS SUBMITTED WITH THE DRAWING
 INDEX. SECTION 106.1.1.
 ********RESPONSE NOTED, BUT ONE SET OF PLANS HAS TWO
 SHEETS P507 ONE SEAL DATED 12/18/07 AND THE OTHER
 SEALED 12/19/07. ALSO ONE SET IS MISSING SHTS P101C &
 P101D. PLEASE SUBMIT 3 SETS OF PLANS THAT HAVE ALL
 SHEETS PER DRAWING INDEX.
 **********RESPONSE NOTED, BUT THE SHEETS ARE STILL OUT
 OF ORDER AND THERE ARE STILL OLD SHEETS STILL IN THE
 SET. PLEASE HAVE THE SHEETS CORRELATE WITH THE DRAWING
 INDEX AND REMOVE ALL SHEETS THAT ARE NOT CURRENT.
  
 3B. OK
 4B. OK
 5B. OK
 6B. OK
 7B. OK
 8B. OK
 9B. OK
 10B. OK
 11B. OK
 12B. OK
 13B. OK
 14B. OK
 15B. OK
 16B. OK
 17B. OK
 18B. OK
 19B. OK
 20B. OK
 21B. OK
 22B. OK
 23B. OK
 24B. OK
 25B. OK
  
 **********NEW COMMENTS**********
  
 1C. OK
 2C. OK
  
 3C. SHT P101C FIRST FLOOR PLAN DOMESTIC WATER & GAS.
 MANY WATER RISERS SHOW NO WATER LINES CONNECTING TO THE
 WATER MAIN. SHOW ALL PIPING ON THE FLOOR PLAN.--
 ACCESSIBLE STUDIO REFERS TO DETAIL 5, SHEET P401, BUT
 DETAIL 5 HAS NOT BEEN SUBMITTED.--THREE OTHER
 REFERENCES TO DETAIL 4, SHT P402, BUT THESE DETAILS ARE
 FOR SANITARY WASTE & VENT, NOT WATER INFORMATION.
 CLARIFY-- ACCESSIBLE STUDIO (125), SHOWER IS NOT
 SHOWN ON THE FLOOR PLAN.--RISER CW-92 IS NOT SHOWN
 ON THE FLOOR PLAN.--SHOW THE LOCATION OF RISERS 85,
 86 & 87 ON THE FLOOR PLAN SO THE RISERS CAN BE TRACKED.
 --FLOOR PLAN REFERENCES RISER CW-94, BUT NO CW-94 WAS
 SUBMITTED,--3" HOT WATER MAIN LINE HAS BEEN
 MISLABELED AS 3" COLD WATER. SECTIONS 106.1.1 106.1.2 &
 604.
 **********RESPONSE NOTED, BUT THERE IS STILL NO PIPING
 TO RISER CW-112 AND RISER 86 IS STILL NOT INDICATED ON
 THE FLOOR PLAN.
  
 4C. SHT P101D FIRST FLOOR PLAN DOMESTIC WATER & GAS.
 SOME RISER DESIGNATIONS ARE NOT LEGIBLE.--SOME
 RISERS SHOW NO PIPING TO THE RISER--SHOWER NOT
 SHOWN ON THE FLOOR PLAN FOR THE ACCESSIBLE QUEEN (101).
 --RISER CW-104 NOT SUBMITTED.--BOTH HOT AND COLD
 WATER FOR CW-50 CONNECT TO THE HOT WATER MAIN. SECTIONS
 106.1.1, 106.1.2 & 607.4.
 **********RESPONSE NOTED, BUT NOW RISER HW/CW-59 IS NOT
 INDICATED ON THE FLOOR PLAN.
  
 5C. SHT P102 SECOND FLOOR PLUMBING. ACCESSIBLE STUDIO
 (225) IS INDICATED AS KING UNIT ON THE ARCHITECTURAL
 FLOOR PLAN. PLEASE CORRELATE.--RISER SAN-13 IS
 LABELED AS SAN-3. PLEASE CORRELATE.--NO RISERS
 INDICATED FOR THE SHOWER IN STUDIO 105 THRU 505.-- NO
 LAV SHOWN IN ACCESSIBLE QUEEN (201).--THE RISERS
 BEHIND WHERE THE LAV SHOULD BE IN THE ACCESSIBLE QUEEN
 ARE NOT SHOWN ON THE FIRST FLOOR, NOR ARE THEY SHOWN ON
 THE THIRD FLOOR. PLEASE CLARIFY. IDENTIFY RISERS.--
 INFORMATION AT THE RIGHT SIDE OF THE KEY NOTES IS NOT
 LEGIBLE.SECTIONS 106.1.1, 106.1.2. **********RESPONSE
 NOTED, BUT THE ARCHITECTURAL SHEETS AND THE PLUMBING
 SHEETS STILL DO NOT CORRELATE FOR ROOM 225.
  
 6C. OK
 7C. OK
 8C. OK
 9C. OK
 10C. OK
  
 11C. SHT P501 SANITARY RISER DIAGRAMS PLUMBING. EVERY
 VENT STACK SHALL CONNECT TO THE BASE OF THE DRAINAGE
 STACK. SECTION 903.4. SEE STACKS 3, 6, 12, 17, 23 & 30.
 --ALL SINK AND LAV RISERS SHOW TRAPS UNDER THE SLABS
 FOR THESE FIXTURES. PLEASE CLAIRFY. SECTIONS 106.1.1 &
 1002.1.--DETAIL 1 REFERENCES ACCESSIBLE STUDIO 2BD,
 1ST THRU 5TH FLOOR ONLY, BUT THE ARCHITECURAL SHEETS
 INDICATE THAT THE 2ND FLOOR IS A STANDARD STUDIO AND
 THE 3RD THRU 5TH FLOORS ARE ACCESSIBLE KINGS. PLEASE
 CORRELATE.--SAN-1 DOES NOT REFLECT THE FLOOR PLAN.
 ALL FLOORS INDICATE ACCESSIBLE SHOWERS, BUT THE FIRST
 FLOOR SHOWS AN ACCESSIBLE SHOWER, THE SECOND FLOOR
 SHOWS A STANDARD TUB, AND THIRD FLOOR THRU FIFTH FLOOR
 SHOWS ACCESSIBLE TUB. PLEASE CORRELATE.--SAN-2,
 SAN-3 & SAN-4 DO NOT REFLECT THE FLOOR PLAN BECAUSE OF
 THE SAME CONDITION OF CHANGING FLOOR PLANS BUT THE
 RISER SHOWS THE SAME FOR EACH FLOOR. CORRELATE.--
 SAN-22 DOES NOT REFLECT THE FLOOR PLAN.SECTION
 106.1.1.
 **********RESPONSE NOTED, BUT THE VENT STACKS ARE SHOWN
 CONNECTING TO THE BRANCH LINE NOT THE SANITARY STACK.
 ALSO THE VENT CONNECTION IS A DRY HORIZONTAL VENT WHICH
 IS NOT ALLOWED PER SECTION 905.3. THIS CAN BE REMEDIED
 BY CONNECTING A FULL SIZE VENT TO THE SANITARY STACK
 ABOVE THE FIRST FLOOR FIXTURES AND CONNECTING THE LAV
 VENT FROM THE FIRST FLOOR TO THE VENT.--STACK 8
 STILL SHOWS THE TRAPS BELOW THE SLAB, STACK 18 SHOWS
 THE 5TH FLOOR TRAP BELOW THE SLAB, AND STACK 2 IS
 MISSING THE WASTE LINE AND TRAP FOR THE 5TH FLOOR.--
 THE ARCHITECTURAL SHEET STILL SHOWS A KING UNIT FOR
 UNIT 225. CORRELATE.--(NEW) RISERS 6, 12, 17, 23 &
 30 SHOW THE SECOND FLOOR FIXTURES CONNECTING TO THE WET
 VENT OF THE FIRST FLOOR. THIS IS NOT APPROVED PER
 SECTIONS 908.3 & 909.1. CONNECT THE BRANCH LINE FOR THE
 2ND FLOOR FIXTURES TO THE SANITARY STACK.
  
 12C. SHT P502SANITARY RISER DIAGRAMS PLUMBING. EVERY
 VENT STACK SHALL CONNECT TO THE BASE OF THE DRAINAGE
 STACK. SECTION 903.4. SEE STACKS 37, 44, 46, 54 & 60.
 --ALL SINK AND LAV RISERS SHOW TRAPS UNDER THE SLABS
 FOR THESE FIXTURES. PLEASE CLAIRFY. SECTIONS 106.1.1 &
 1002.1.--DETAIL ONE SHOWS THE SECOND SAN-31 RISER
 SUBMITTED. THE RISER 31 ON THE PREVIOUS SHEET SHOWS
 SINKS, THE RISER 31 ON THIS SHEET SHOWS TUBS. PLEASE
 CLARIFY.--SAN-36 RISER DOES NOT REFLECT THE FLOOR
 PLAN.--SAN-48 DOES NOT REFLECT THE FLOOR PLAN AS IT
 INDICATES A SHOWER ON THE FIRST FLOOR THAT IS NOT SHOWN
 ON THE FLOOR PLAN, THEN CHANGES INTO W/C'S & TUBS FROM
 THE 3RD FLOOR TO THE 5TH FLOOR.--SAN-46 DOES NOT
 REFLECT THE FLOOR PLAN AS IT DOES NOT SHOW THE W/C ON
 THE FIRST FLOOR, DOES NOT SHOW THE OFFSET BETWEEN THE
 2ND AND 3RD FLOORS AND SHOWS LAVS ON THE 3RD THRU 5TH
 FLOORS.--SAN-48/SAN-46 SHOW NO VENT THRU ROOF.
 SECTIONS 106.1.1 & 903.3.
 **********RESPONSE NOTED, BUT THE VENT STACKS ARE SHOWN
 CONNECTING TO THE BRANCH LINE NOT THE SANITARY STACK.
 ALSO THE VENT CONNECTION IS A DRY HORIZONTAL VENT WHICH
 IS NOT ALLOWED PER SECTION 905.3. THIS CAN BE REMEDIED
 BY CONNECTING A FULL SIZE VENT TO THE SANITARY STACK
 ABOVE THE FIRST FLOOR FIXTURES AND CONNECTING THE LAV
 VENT FROM THE FIRST FLOOR TO THE VENT.--RISERS
 SAN-42, SAN-55 & SAN-62 STILL SHOW THE TRAPS UNDER THE
 SLAB AS WELL AS THE FIRST FLOOR ON SAN-47.--(NEW)
 THERE ARE TWO RISERS WITH THE DESIGNATION OF SAN-33
 INDICATED ON SHTS P501 & P502, BUT NO SAN-34 SUBMITTED.
 PLEASE CLARIFY. SECTIONS 106.1.1 & 701.1 WITH TABLE
 710.1(2).--(NEW) RISERS 37, 44, 48, 54 & 60 SHOW
 THE SECOND FLOOR FIXTURES CONNECTING TO THE WET VENT OF
 THE FIRST FLOOR. THIS IS NOT APPROVED PER SECTIONS
 908.3 & 909.1. CONNECT THE BRANCH LINE FOR THE 2ND
 FLOOR FIXTURES TO THE SANITARY STACK.
  
 13C. SHT P503 SANITARY RISER DIAGRAMS PLUMBING. EVERY
 VENT STACK SHALL CONNECT TO THE BASE OF THE DRAINAGE
 STACK. SECTION 903.4. SEE STACKS 66, 74, 77, 84, 91 &
 87.--ALL SINK AND LAV RISERS SHOW TRAPS UNDER THE
 SLABS FOR THESE FIXTURES. PLEASE CLAIRFY. SECTIONS
 106.1.1 & 1002.1.--RISER SAN-76 DOES NOT REFLECT
 THE FLOOR PLAN.--SAN-91 RISER DOES NOT REFLECT THE
 FLOOR PLAN.--SAN-90 RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN.--SAN-89 RISER DOES NOT REFLECT THE
 FLOOR PLAN. SECTIONS 106.1.1 & 106.3.5.1.3.
 **********RESPONSE NOTED, BUT THE VENT STACKS ARE SHOWN
 CONNECTING TO THE BRANCH LINE NOT THE SANITARY STACK.
 ALSO THE VENT CONNECTION IS A DRY HORIZONTAL VENT WHICH
 IS NOT ALLOWED PER SECTION 905.3. THIS CAN BE REMEDIED
 BY CONNECTING A FULL SIZE VENT TO THE SANITARY STACK
 ABOVE THE FIRST FLOOR FIXTURES AND CONNECTING THE LAV
 VENT FROM THE FIRST FLOOR TO THE VENT.--SAN-79,
 SAN-81, SAN-82 STILL SHOW TRAPS BELOW THE SLAB. SOME
 2ND THRU 5TH FLOOR.--(NEW) RISERS SAN-74, SAN-77,
 SAN-84 & SAN-87 SHOW THE SECOND FLOOR FIXTURES
 CONNECTING TO THE WET VENT OF THE FIRST FLOOR. THIS IS
 NOT APPROVED PER SECTIONS 908.3 & 909.1. CONNECT THE
 BRANCH LINE FOR THE 2ND FLOOR FIXTURES TO THE SANITARY
 STACK.--THERE ARE TWO SAN-89 RISERS SUBMITTED.
 PLEASE CLARIFY.
  
 14C. SHT P504 HOT & COLD WATER RISER DIAGRAM PLUMBING.
 ALL RISERS DO NOT REFLECT THE FLOOR PLAN AS THEY SHOW
 PIPING UNDERGROUND TO EACH RISER BUT THE FLOOR PLAN
 SHOWS THE WATER IN THE CEILING FEEDING DOWN TO THE
 FIRST FLOOR AND UP TO THE 2ND, 3RD, 4TH & 5TH FLOORS.
 --CW-1/HW-1 DOES NOT REFLECT THE FLOOR PLAN AS IT
 SHOWS THE SUPPLY PIPING UNDERGROUND.--CW-4/HW-4
 DOES NOT REFLECT THE FLOOR PLAN.--NO WATER RISER
 FOR THE SHOWER IN THE STUDIO UNITS 113 THRU 513.
 SECTIONS 106.1.1 & 106.3.5.1.3.
 **********RESPONSE NOTED, NEW RISER FOR THE SHOWERS IN
 STUDIO UNITS 113 THRU 513 IS INDICATED AS A "SINK"
 RISER. PLEASE CORRELATE.--NOW ALL RISERS HAVE SIX
 SETS OF SUPPLY STUBOUTS FOR 5 FLOORS OF FIXTURES.
 PLEASE CORRELATE.
  
 15C. SHT P505 HOT & COLD WATER RISER DIAGRAM PLUMBING.
 ALL RISERS DO NOT REFLECT THE FLOOR PLAN AS THEY SHOW
 PIPING UNDERGROUND TO EACH RISER BUT THE FLOOR PLAN
 SHOWS THE WATER IN THE CEILING FEEDING DOWN TO THE
 FIRST FLOOR AND UP TO THE 2ND, 3RD, 4TH & 5TH FLOORS.
 --NO RISER FOR THE SHOWER IN DETAIL 2/505.--
 CW-43/HW-43 RISER SHOWS THE SUPPLY PIPING UNDERGROUND.
 --CW-41/HW-41 RISER DOES NOT REFLECT THE FLOOR PLAN.
 --DETAIL 3/505 SHOWS TWO CW-43 RISERS. PLEASE
 CLARIFY.--DETAIL 4/505 DOES NOT SHOW A LAV RISER
 DIAGRAM.--CW-48/HW-48 RISER DOES NOT REFLECT THE
 FLOOR PLAN.--CW-45/HW-45 DOES NOT REFLECT THE FLOOR
 PLAN.--DETAIL 5/505 DOES NOT SHOW A WATER CLOSET
 RISER DIAGRAM.--CW-51/HW-51 RISER DOES NOT REFLECT
 THE FLOOR PLAN. SECTIONS 106.1.1 & 106.3.5.1.3.
 **********RESPONSE NOTED, BUT RISER 34 IS MISSING THE
 5TH FLOOR SUPPLY AND RISER 37 HAS 6 SETS OF SUPPLY
 STUBOUTS FOR 5 FLOORS. PLEASE CORRELATE.--THE
 COMMENT ABOUT THE SHOWER DETAIL 2/505 HAS NOT BEEN
 ADDRESSED.
  
 16C. OK
  
 17C. SHT P507 HOT & COLD WATER RISER DIAGRAM PLUMBING.
 ALL RISERS DO NOT REFLECT THE FLOOR PLAN AS THEY SHOW
 PIPING UNDERGROUND TO EACH RISER BUT THE FLOOR PLAN
 SHOWS THE WATER IN THE CEILING FEEDING DOWN TO THE
 FIRST FLOOR AND UP TO THE 2ND, 3RD, 4TH & 5TH FLOORS.
 --DETAIL 3/507 RISERS CW-89/HW-89, CW-90/HW-90 &
 CW-91/HW-91 DO NOT REFLECT THE FLOOR PLANS.--DETAIL
 4/507 RISER CW-92 DOES NOT REFLECT THE FLOOR PLAN, NO
 ICE MACHINE SHOWN ON THE FLOOR PLAN.--DETAIL 5/507
 RISERS CW-95 THRU CW-101 AND CW-103 THRU CW-114 DO NOT
 REFLECT THE FLOOR PLAN. ICE MAKER SHOWN ON THE 1ST
 FLOOR FLOOR PLAN BUT NOT SHOWN ON THE RISER DIAGRAM. --
 CW-93 & CW-103 DOES NOT REFLECT THE FLOOR PLAN AS THE
 FLOOR PLANS SHOWS ICE MAKERS, WHERE AS THE RISER DOES
 NOT INDICATE 1ST FLOOR ICE MAKERS. --ALL ICE MAKER
 RISERS SHALL SHOW A WATER HAMMER ARRESTOR AT EACH ICE
 MAKER.--THERE IS NO RISER CW-102 SUBMITTED,TWO
 RISERS CW-98 SUBMITTED AND TWO RISERS 103 SUBMITTED.
 PLEASE CLARIFY. SECTIONS 106.1.1, 106.1.2 & 604.9.
 **********RESPONSE NOTED, BUT THE COMMENT CONCERNING
 DETAIL 3/507 RISERS HAS NOT BEEN ADDRESSED. THERE ARE
 NO 1ST FLOOR FIXTURES & ON RISERS 85 & 87 THE 5TH FLOOR
 FIXTURES ARE MISSING.--COMMENT CONCERNING THE ICE
 MAKER LINES ON DETAIL 5/507 HAVE NOT BEEN ADDRESSED.
 (CW-94 ALSO).--RISERS CW-75 & CW-76 ARE NOT
 SUBMITTED.--CW-93 & CW-103 DO NOT REFLECT THE FLOOR
 PLAN AS THERE IS NO ICE MAKER ON THE 1ST FLOOR.
  
 18C. SHT P508 RISER DIAGRAM OVERALL FIRST FLOOR
 SANITARY. FIXTURE P6 FOR EMPLOYEE BREAK ROOM SINK,
 PLEASE INDICATE WHERE IT CONNECTS TO THE BRANCH LINE.
 --BRANCH LINE FOR SAN-86 NOT SHOWN.--RISERS
 SAN-82 & SAN-83 ARE NOT REFLECTING THE CONNECTION ON
 THE FLOOR PLAN. --RISERS SAN-89, SAN-90 & SAN-91 ARE
 NOT SHOWN ON THE RISER DIAGRAM.--RISERS SAN-9,
 SAN-10 & SAN-11 ARE NOT SHOWN ON THE RISER DIAGRAM.--
 PIPING TO SAN-13 RISER DOES NOT REFLECT THE FLOOR PLAN.
 --SOME RISER LOCATIONS ON THE RISER DIAGRAM DO NOT
 REFLECT THE FLOOR PLAN. (EXAMPLES 14, 15, 77, 78)--
 SAN RISER TO WASH MACHINES DO NOT REFLECT THE FLOOR
 PLAN SHT P101A. (FOUR RISERS SHOWN).--SUBMIT A
 FLOOR PLAN WITH SANITARY AND WATERRISER DIAGRAMS FOR
 THE WASH MACHINES IN GUEST LAUNDRY ROOM 218. SHOW PIPE
 SIZE, TRAPS, CLEANOUTS, VENTING FOR THE SANITARY RISER,
 AND SHOW PIPE SIZE, VALVES, WATER HAMMER ARRESTORS ETC
 FOR THE WATER RISER DIAGRAM.--CLEANOUT MISSING
 UPSTREAM OF SAN-34 THAT IS SHOWN ON THE FLOOR PLAN.--
 SEVEN RISERS ALL SHOW RISER NUMBER SAN-34. THIS DOES
 NOT REFLECT THE FLOOR PLAN.--SAN-57 RISER DOES NOT
 REFLECT THE FLOOR PLAN AS IT DOES NOT SHOW A DOUBLE
 COMBO CONNECTION.--TWO SAN-48 RISER SHOWN ON THE
 RISER DIAGRAM. THAT DOES NOT REFLECT THE FLOOR PLAN. --
 FIRST FIXTURE, (FLOOR DRAIN), UPSTREAM OF TOILET ROOMS
 28 & 29 IS NOT SHOWN ON THE FLOOR PLAN SHT P101B. ALSO
 FIXTURE SHOWS A HORIZONTAL DRY VENT WHICH IS
 PROHIBITED.--FIRST FIXTURE, (FLOOR DRAIN). IN THE
 KITCHEN SHALL BE A FLOOR SINK, OR HUB DRAIN IF INDIRECT
 WASTE.--HORIZONTAL DRY VENT IS PROHIBITED PRIOR TO
 CLEANOUT AT THE UPSTREAM END OF THE KITCHEN FIXTURES.
 --RISER DIAGRAM SHOWS A SAN-47 RISER. THIS IS NOT
 SHOWN ON ANY FLOOR PLAN, NOR WAS THERE A RISER SAN-47
 SUBMITTED. PLEASE CLARIFY.--THE SANITARY RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLANS IN MANY AREAS.
 PLEASE RECHECK AND CORRELATE. SECTIONS 106.1.1,
 106.2.1, 106.3.5.1.3, 604, 604.9, PDI-WH 201, TABLES
 604.5, 604.10.1, 709.1, 710.1(1), 710.1(2), 905.3 &
 905.4.
 **********RESPONSE NOTED, BUT THERE ARE TWO SAN-87
 RISERS SHOWN AND NO SAN-86 RISER.--SAN-75 NOT
 SHOWN.--SAN 34 & SAN-63 ARE INDICATED UPSTREAM OF
 SAN-33 & SAN-64 ON THE RISER DIAGRAM, BUT DOWNSTREAM OF
 SAN-33 & SAN-64 ON THE FLOOR PLAN.--NO RESPONSE TO
 THE WATER REQUIREMENT FOR THE WASH MACHINES IN THE
 GUEST LAUNDRY ROOM 218.--PLEASE CORRELATE.
  
 19C. SHT P509 RISER DIAGRAM OVERALL FIRST FLOOR WATER.
 ALL WATER HAMMER ARRESTORS SHALL BE LOCATED IN AN
 "EFFECTIVE RANGE",NOT IN THE CEILING AS SHOWN.--
 RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN IN MANY
 AREAS AND RISERS DO NOT REFLECT THE FLOOR PLAN IN MANY
 AREA WHERE THE RISERS CONNECT TO THE WATER MAIN. PLEASE
 RECHECK THE ENTIRE RISER DIAGRAM PRIOR TO RESUBMITTING
 AS FAR AS RISER LOCATIONS AND RISER CONNECTIONS TO
 WATER MAIN.--RISER INDICATED HW/CW TO RISER 60, BUT
 RISER 60 ONLY HAS COLD WATER. CORRELATE.--RISERS
 45, 46, 48, 49, 50 & 51 NOT SHOWN ON THE RISER DIAGRAM
 BUT ON THE FLOOR PLAN.--RISER 44 DOES NOT REFLECT
 THE FLOOR PLAN. SECTIONS 106.1.1, 106.1.2, PDI-WH 201,
 TABLES 604.5, 604.10.1. PDI-WH 201 & MANUF.
 INSTALLATION INSTRUCTIONS.
 **********RESPONSE NOTED, BUT THE WATER HAMMER
 ARRESTORS ARE STILL SHOWN IN THE CEILING AT THE TOP OF
 THE DROP OR UP IN THE DROP, NOT NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE" AS REQUIRED. ALL WATER HAMMER
 ARRESTORS SHALL BE LOCATED WHERE REQUIRED. --WATER
 SUPPLY LINE TO THE DRINKING FOUNTAIN BY THE POOL SHOWER
 DOES NOT REFLECT THE FLOOR PLAN, NOR DOES THE WATER
 RISER DIAGRAM FOR THE KITCHEN.--THE 4" COLD WATER
 LINE SUPPLYING THE PUMP ON THE SECOND FLOOR IS NOT
 SHOWN ON THE FLOOR PLAN AND THE WATER SUPPLY LINE TO
 THE WALL HYDRANT SHOWN ON THE FLOOR PLAN NEAR WHERE THE
 4" WATER MAIN ENTERS THE BUILDING IS NOT SHOWN ON THE
 RISER DIAGRAM.--RISERS 40, 41, 42 & 43 ARE NOT
 INDICATED ON THE RISER DIAGRAM.--RISERS HW/CW-49 &
 HW/CW-51 ARE NOT SHOWN ON THE RISER DIAGRAM.--THERE
 ARE TWO CW-103 RISERS SHOWN ON THE RISER DIAGRAM.--
 CW RISERS 75 & 76 ARE NOT SHOWN ON THE RISER DIAGRAM.
 --PLEASE CORRELATE.
  
 20C. OK
  
 21C. SHT P602 PLUMBING DETAILS. DETAIL NUMBER 1 DOES
 NOT COMPLY WITHTHE UTILITY STANDARD FOR GREASE
 INTERCEPTORS. PLEASE SEE ATTACHED SHEET. DETAIL
 INDICATES PREFAB TANKS. PLEASE SUBMIT MANUF.
 SPECIFICATIONS FOR GREASE INTERCEPTOR. ARTICLE III
 SECTION 90-124(7)(E)(F).--DETAIL 4 SHOWS A DOUBLE
 CHECK BACKFLOW PREVENTOR FOR THE DOMESTIC WATER
 BACKFLOW PREVENTOR. THIS IS NOT APPROVED. THE PROPER
 BACKFLOW PREVENTOR FOR THE DOMESTIC IS AN RPZV BACKFLOW
 PREVENTOR. SECTION 608.13.2.
 **********RESPONSE NOTED, BUT NEW DETAIL IS NOT
 LEGIBLE. SECTION 106.1.1.
  
 **********NEW COMMENT**********
  
 1D. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONALS AND FS 553.80(2)(B).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 -PLEASE RESUBMIT ONE SET OF OLD SHEETS
 FOR COMPARISON.
  
 ********NO RESPONSE, NOT ADDRESSED
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  