| Date |
Text |
| 2008-05-08 12:33:31 | |
| | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2001 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | ******FROM PREVIOUS REVIEWS: 3RD REVIEW: |
| | |
| | ********FROM PREVIOUS REVIEWS: 4TH REVIEW: |
| | |
| | **********FROM PREVIOUS REVIEWS: 5TH REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | 6. OK (INFORMATIONAL ONLY) |
| | 7. OK |
| | 8. OK |
| | 9. OK |
| | 10. OK |
| | 11. OK |
| | 12. OK |
| | 13. OK |
| | 14. OK |
| | 15. OK |
| | 16. OK |
| | 17. OK |
| | 18. OK |
| | 19. RESPONSE NOTED, NOT APPLICABLE |
| | 20. OK. |
| | 21. OK |
| | 22. OK |
| | 23. OK |
| | 24. OK |
| | 25. OK |
| | 26. OK |
| | 27. OK |
| | 28. OK |
| | 29. OK |
| | 30. OK |
| | 31. OK |
| | 32. OK |
| | 33. OK |
| | |
| | 34. INDICATE A NUMBER DESIGNATION FOR EACH RISER |
| | INCLUDING ALL SANT., WATER, STORM, CONDENSATE. (EXAMPLE |
| | SANT-1, SANT-2, RWL-1, RWL-2, CON-1, CON-2, W-1, W-2 |
| | ETC.). THIS WILL AID IN TRACKING ALL RISERS FROM THE |
| | UNDERGROUND PIPING THROUGH THE ROOF. SECTIONS |
| | 106.3.5.1.3 & SECTION 106.1.1.--INDICATE WHICH |
| | RISER IS TYPICAL OF WHICH RISER ISOMETRIC DIAGRAM. |
| | (EXAMPLE SANT-1 SANT-4 TYPICAL OF DETALI 4 SHT P401) -- |
| | INDICATE ROOM NUMBER EACH RISER CAN BE LOCATED. |
| | ****RESPONSE NOTED, BUT SHEET P503 HAS NOT BEEN |
| | SUBMITTED. |
| | ******RESPONSE NOTED, BUT RESPONSE DOES NOT ADDRESS THE |
| | WATER RISERS, STORM RISERS, OR CONDENSATE RISERS. |
| | ********RESPONSE NOTED, BUT THERE ARE STILL RISER |
| | DESIGNATIONS MISSING ON THE FIRST FLOOR. |
| | **********RESPONSE NOTED, BUT THERE ARE TWO RISERS |
| | DESIGNATED AS CW-76 AND NO RISER CW-75 INDICATED ON THE |
| | FLOOR PLAN AND NO RISER HW/CW-86 SHOWN ON THE FLOOR |
| | PLAN. |
| | |
| | 35. OK |
| | 36. OK |
| | 37. OK |
| | |
| | *****NEW COMMENTS 3RD REVIEW***** |
| | |
| | |
| | 1B. OK |
| | |
| | 2B. SHT G-001 NOT ALL SHEETS SHOWN ON THE DRAWING INDEX |
| | HAVE BEEN SUBMITTED, AND SOME SHEETS ARE OUT OF ORDER. |
| | PLEASE CORRELATE THE SHEETS SUBMITTED WITH THE DRAWING |
| | INDEX. SECTION 106.1.1. |
| | ********RESPONSE NOTED, BUT ONE SET OF PLANS HAS TWO |
| | SHEETS P507 ONE SEAL DATED 12/18/07 AND THE OTHER |
| | SEALED 12/19/07. ALSO ONE SET IS MISSING SHTS P101C & |
| | P101D. PLEASE SUBMIT 3 SETS OF PLANS THAT HAVE ALL |
| | SHEETS PER DRAWING INDEX. |
| | **********RESPONSE NOTED, BUT THE SHEETS ARE STILL OUT |
| | OF ORDER AND THERE ARE STILL OLD SHEETS STILL IN THE |
| | SET. PLEASE HAVE THE SHEETS CORRELATE WITH THE DRAWING |
| | INDEX AND REMOVE ALL SHEETS THAT ARE NOT CURRENT. |
| | |
| | 3B. OK |
| | 4B. OK |
| | 5B. OK |
| | 6B. OK |
| | 7B. OK |
| | 8B. OK |
| | 9B. OK |
| | 10B. OK |
| | 11B. OK |
| | 12B. OK |
| | 13B. OK |
| | 14B. OK |
| | 15B. OK |
| | 16B. OK |
| | 17B. OK |
| | 18B. OK |
| | 19B. OK |
| | 20B. OK |
| | 21B. OK |
| | 22B. OK |
| | 23B. OK |
| | 24B. OK |
| | 25B. OK |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1C. OK |
| | 2C. OK |
| | |
| | 3C. SHT P101C FIRST FLOOR PLAN DOMESTIC WATER & GAS. |
| | MANY WATER RISERS SHOW NO WATER LINES CONNECTING TO THE |
| | WATER MAIN. SHOW ALL PIPING ON THE FLOOR PLAN.-- |
| | ACCESSIBLE STUDIO REFERS TO DETAIL 5, SHEET P401, BUT |
| | DETAIL 5 HAS NOT BEEN SUBMITTED.--THREE OTHER |
| | REFERENCES TO DETAIL 4, SHT P402, BUT THESE DETAILS ARE |
| | FOR SANITARY WASTE & VENT, NOT WATER INFORMATION. |
| | CLARIFY-- ACCESSIBLE STUDIO (125), SHOWER IS NOT |
| | SHOWN ON THE FLOOR PLAN.--RISER CW-92 IS NOT SHOWN |
| | ON THE FLOOR PLAN.--SHOW THE LOCATION OF RISERS 85, |
| | 86 & 87 ON THE FLOOR PLAN SO THE RISERS CAN BE TRACKED. |
| | --FLOOR PLAN REFERENCES RISER CW-94, BUT NO CW-94 WAS |
| | SUBMITTED,--3" HOT WATER MAIN LINE HAS BEEN |
| | MISLABELED AS 3" COLD WATER. SECTIONS 106.1.1 106.1.2 & |
| | 604. |
| | **********RESPONSE NOTED, BUT THERE IS STILL NO PIPING |
| | TO RISER CW-112 AND RISER 86 IS STILL NOT INDICATED ON |
| | THE FLOOR PLAN. |
| | |
| | 4C. SHT P101D FIRST FLOOR PLAN DOMESTIC WATER & GAS. |
| | SOME RISER DESIGNATIONS ARE NOT LEGIBLE.--SOME |
| | RISERS SHOW NO PIPING TO THE RISER--SHOWER NOT |
| | SHOWN ON THE FLOOR PLAN FOR THE ACCESSIBLE QUEEN (101). |
| | --RISER CW-104 NOT SUBMITTED.--BOTH HOT AND COLD |
| | WATER FOR CW-50 CONNECT TO THE HOT WATER MAIN. SECTIONS |
| | 106.1.1, 106.1.2 & 607.4. |
| | **********RESPONSE NOTED, BUT NOW RISER HW/CW-59 IS NOT |
| | INDICATED ON THE FLOOR PLAN. |
| | |
| | 5C. SHT P102 SECOND FLOOR PLUMBING. ACCESSIBLE STUDIO |
| | (225) IS INDICATED AS KING UNIT ON THE ARCHITECTURAL |
| | FLOOR PLAN. PLEASE CORRELATE.--RISER SAN-13 IS |
| | LABELED AS SAN-3. PLEASE CORRELATE.--NO RISERS |
| | INDICATED FOR THE SHOWER IN STUDIO 105 THRU 505.-- NO |
| | LAV SHOWN IN ACCESSIBLE QUEEN (201).--THE RISERS |
| | BEHIND WHERE THE LAV SHOULD BE IN THE ACCESSIBLE QUEEN |
| | ARE NOT SHOWN ON THE FIRST FLOOR, NOR ARE THEY SHOWN ON |
| | THE THIRD FLOOR. PLEASE CLARIFY. IDENTIFY RISERS.-- |
| | INFORMATION AT THE RIGHT SIDE OF THE KEY NOTES IS NOT |
| | LEGIBLE.SECTIONS 106.1.1, 106.1.2. **********RESPONSE |
| | NOTED, BUT THE ARCHITECTURAL SHEETS AND THE PLUMBING |
| | SHEETS STILL DO NOT CORRELATE FOR ROOM 225. |
| | |
| | 6C. OK |
| | 7C. OK |
| | 8C. OK |
| | 9C. OK |
| | 10C. OK |
| | |
| | 11C. SHT P501 SANITARY RISER DIAGRAMS PLUMBING. EVERY |
| | VENT STACK SHALL CONNECT TO THE BASE OF THE DRAINAGE |
| | STACK. SECTION 903.4. SEE STACKS 3, 6, 12, 17, 23 & 30. |
| | --ALL SINK AND LAV RISERS SHOW TRAPS UNDER THE SLABS |
| | FOR THESE FIXTURES. PLEASE CLAIRFY. SECTIONS 106.1.1 & |
| | 1002.1.--DETAIL 1 REFERENCES ACCESSIBLE STUDIO 2BD, |
| | 1ST THRU 5TH FLOOR ONLY, BUT THE ARCHITECURAL SHEETS |
| | INDICATE THAT THE 2ND FLOOR IS A STANDARD STUDIO AND |
| | THE 3RD THRU 5TH FLOORS ARE ACCESSIBLE KINGS. PLEASE |
| | CORRELATE.--SAN-1 DOES NOT REFLECT THE FLOOR PLAN. |
| | ALL FLOORS INDICATE ACCESSIBLE SHOWERS, BUT THE FIRST |
| | FLOOR SHOWS AN ACCESSIBLE SHOWER, THE SECOND FLOOR |
| | SHOWS A STANDARD TUB, AND THIRD FLOOR THRU FIFTH FLOOR |
| | SHOWS ACCESSIBLE TUB. PLEASE CORRELATE.--SAN-2, |
| | SAN-3 & SAN-4 DO NOT REFLECT THE FLOOR PLAN BECAUSE OF |
| | THE SAME CONDITION OF CHANGING FLOOR PLANS BUT THE |
| | RISER SHOWS THE SAME FOR EACH FLOOR. CORRELATE.-- |
| | SAN-22 DOES NOT REFLECT THE FLOOR PLAN.SECTION |
| | 106.1.1. |
| | **********RESPONSE NOTED, BUT THE VENT STACKS ARE SHOWN |
| | CONNECTING TO THE BRANCH LINE NOT THE SANITARY STACK. |
| | ALSO THE VENT CONNECTION IS A DRY HORIZONTAL VENT WHICH |
| | IS NOT ALLOWED PER SECTION 905.3. THIS CAN BE REMEDIED |
| | BY CONNECTING A FULL SIZE VENT TO THE SANITARY STACK |
| | ABOVE THE FIRST FLOOR FIXTURES AND CONNECTING THE LAV |
| | VENT FROM THE FIRST FLOOR TO THE VENT.--STACK 8 |
| | STILL SHOWS THE TRAPS BELOW THE SLAB, STACK 18 SHOWS |
| | THE 5TH FLOOR TRAP BELOW THE SLAB, AND STACK 2 IS |
| | MISSING THE WASTE LINE AND TRAP FOR THE 5TH FLOOR.-- |
| | THE ARCHITECTURAL SHEET STILL SHOWS A KING UNIT FOR |
| | UNIT 225. CORRELATE.--(NEW) RISERS 6, 12, 17, 23 & |
| | 30 SHOW THE SECOND FLOOR FIXTURES CONNECTING TO THE WET |
| | VENT OF THE FIRST FLOOR. THIS IS NOT APPROVED PER |
| | SECTIONS 908.3 & 909.1. CONNECT THE BRANCH LINE FOR THE |
| | 2ND FLOOR FIXTURES TO THE SANITARY STACK. |
| | |
| | 12C. SHT P502SANITARY RISER DIAGRAMS PLUMBING. EVERY |
| | VENT STACK SHALL CONNECT TO THE BASE OF THE DRAINAGE |
| | STACK. SECTION 903.4. SEE STACKS 37, 44, 46, 54 & 60. |
| | --ALL SINK AND LAV RISERS SHOW TRAPS UNDER THE SLABS |
| | FOR THESE FIXTURES. PLEASE CLAIRFY. SECTIONS 106.1.1 & |
| | 1002.1.--DETAIL ONE SHOWS THE SECOND SAN-31 RISER |
| | SUBMITTED. THE RISER 31 ON THE PREVIOUS SHEET SHOWS |
| | SINKS, THE RISER 31 ON THIS SHEET SHOWS TUBS. PLEASE |
| | CLARIFY.--SAN-36 RISER DOES NOT REFLECT THE FLOOR |
| | PLAN.--SAN-48 DOES NOT REFLECT THE FLOOR PLAN AS IT |
| | INDICATES A SHOWER ON THE FIRST FLOOR THAT IS NOT SHOWN |
| | ON THE FLOOR PLAN, THEN CHANGES INTO W/C'S & TUBS FROM |
| | THE 3RD FLOOR TO THE 5TH FLOOR.--SAN-46 DOES NOT |
| | REFLECT THE FLOOR PLAN AS IT DOES NOT SHOW THE W/C ON |
| | THE FIRST FLOOR, DOES NOT SHOW THE OFFSET BETWEEN THE |
| | 2ND AND 3RD FLOORS AND SHOWS LAVS ON THE 3RD THRU 5TH |
| | FLOORS.--SAN-48/SAN-46 SHOW NO VENT THRU ROOF. |
| | SECTIONS 106.1.1 & 903.3. |
| | **********RESPONSE NOTED, BUT THE VENT STACKS ARE SHOWN |
| | CONNECTING TO THE BRANCH LINE NOT THE SANITARY STACK. |
| | ALSO THE VENT CONNECTION IS A DRY HORIZONTAL VENT WHICH |
| | IS NOT ALLOWED PER SECTION 905.3. THIS CAN BE REMEDIED |
| | BY CONNECTING A FULL SIZE VENT TO THE SANITARY STACK |
| | ABOVE THE FIRST FLOOR FIXTURES AND CONNECTING THE LAV |
| | VENT FROM THE FIRST FLOOR TO THE VENT.--RISERS |
| | SAN-42, SAN-55 & SAN-62 STILL SHOW THE TRAPS UNDER THE |
| | SLAB AS WELL AS THE FIRST FLOOR ON SAN-47.--(NEW) |
| | THERE ARE TWO RISERS WITH THE DESIGNATION OF SAN-33 |
| | INDICATED ON SHTS P501 & P502, BUT NO SAN-34 SUBMITTED. |
| | PLEASE CLARIFY. SECTIONS 106.1.1 & 701.1 WITH TABLE |
| | 710.1(2).--(NEW) RISERS 37, 44, 48, 54 & 60 SHOW |
| | THE SECOND FLOOR FIXTURES CONNECTING TO THE WET VENT OF |
| | THE FIRST FLOOR. THIS IS NOT APPROVED PER SECTIONS |
| | 908.3 & 909.1. CONNECT THE BRANCH LINE FOR THE 2ND |
| | FLOOR FIXTURES TO THE SANITARY STACK. |
| | |
| | 13C. SHT P503 SANITARY RISER DIAGRAMS PLUMBING. EVERY |
| | VENT STACK SHALL CONNECT TO THE BASE OF THE DRAINAGE |
| | STACK. SECTION 903.4. SEE STACKS 66, 74, 77, 84, 91 & |
| | 87.--ALL SINK AND LAV RISERS SHOW TRAPS UNDER THE |
| | SLABS FOR THESE FIXTURES. PLEASE CLAIRFY. SECTIONS |
| | 106.1.1 & 1002.1.--RISER SAN-76 DOES NOT REFLECT |
| | THE FLOOR PLAN.--SAN-91 RISER DOES NOT REFLECT THE |
| | FLOOR PLAN.--SAN-90 RISER DIAGRAM DOES NOT REFLECT |
| | THE FLOOR PLAN.--SAN-89 RISER DOES NOT REFLECT THE |
| | FLOOR PLAN. SECTIONS 106.1.1 & 106.3.5.1.3. |
| | **********RESPONSE NOTED, BUT THE VENT STACKS ARE SHOWN |
| | CONNECTING TO THE BRANCH LINE NOT THE SANITARY STACK. |
| | ALSO THE VENT CONNECTION IS A DRY HORIZONTAL VENT WHICH |
| | IS NOT ALLOWED PER SECTION 905.3. THIS CAN BE REMEDIED |
| | BY CONNECTING A FULL SIZE VENT TO THE SANITARY STACK |
| | ABOVE THE FIRST FLOOR FIXTURES AND CONNECTING THE LAV |
| | VENT FROM THE FIRST FLOOR TO THE VENT.--SAN-79, |
| | SAN-81, SAN-82 STILL SHOW TRAPS BELOW THE SLAB. SOME |
| | 2ND THRU 5TH FLOOR.--(NEW) RISERS SAN-74, SAN-77, |
| | SAN-84 & SAN-87 SHOW THE SECOND FLOOR FIXTURES |
| | CONNECTING TO THE WET VENT OF THE FIRST FLOOR. THIS IS |
| | NOT APPROVED PER SECTIONS 908.3 & 909.1. CONNECT THE |
| | BRANCH LINE FOR THE 2ND FLOOR FIXTURES TO THE SANITARY |
| | STACK.--THERE ARE TWO SAN-89 RISERS SUBMITTED. |
| | PLEASE CLARIFY. |
| | |
| | 14C. SHT P504 HOT & COLD WATER RISER DIAGRAM PLUMBING. |
| | ALL RISERS DO NOT REFLECT THE FLOOR PLAN AS THEY SHOW |
| | PIPING UNDERGROUND TO EACH RISER BUT THE FLOOR PLAN |
| | SHOWS THE WATER IN THE CEILING FEEDING DOWN TO THE |
| | FIRST FLOOR AND UP TO THE 2ND, 3RD, 4TH & 5TH FLOORS. |
| | --CW-1/HW-1 DOES NOT REFLECT THE FLOOR PLAN AS IT |
| | SHOWS THE SUPPLY PIPING UNDERGROUND.--CW-4/HW-4 |
| | DOES NOT REFLECT THE FLOOR PLAN.--NO WATER RISER |
| | FOR THE SHOWER IN THE STUDIO UNITS 113 THRU 513. |
| | SECTIONS 106.1.1 & 106.3.5.1.3. |
| | **********RESPONSE NOTED, NEW RISER FOR THE SHOWERS IN |
| | STUDIO UNITS 113 THRU 513 IS INDICATED AS A "SINK" |
| | RISER. PLEASE CORRELATE.--NOW ALL RISERS HAVE SIX |
| | SETS OF SUPPLY STUBOUTS FOR 5 FLOORS OF FIXTURES. |
| | PLEASE CORRELATE. |
| | |
| | 15C. SHT P505 HOT & COLD WATER RISER DIAGRAM PLUMBING. |
| | ALL RISERS DO NOT REFLECT THE FLOOR PLAN AS THEY SHOW |
| | PIPING UNDERGROUND TO EACH RISER BUT THE FLOOR PLAN |
| | SHOWS THE WATER IN THE CEILING FEEDING DOWN TO THE |
| | FIRST FLOOR AND UP TO THE 2ND, 3RD, 4TH & 5TH FLOORS. |
| | --NO RISER FOR THE SHOWER IN DETAIL 2/505.-- |
| | CW-43/HW-43 RISER SHOWS THE SUPPLY PIPING UNDERGROUND. |
| | --CW-41/HW-41 RISER DOES NOT REFLECT THE FLOOR PLAN. |
| | --DETAIL 3/505 SHOWS TWO CW-43 RISERS. PLEASE |
| | CLARIFY.--DETAIL 4/505 DOES NOT SHOW A LAV RISER |
| | DIAGRAM.--CW-48/HW-48 RISER DOES NOT REFLECT THE |
| | FLOOR PLAN.--CW-45/HW-45 DOES NOT REFLECT THE FLOOR |
| | PLAN.--DETAIL 5/505 DOES NOT SHOW A WATER CLOSET |
| | RISER DIAGRAM.--CW-51/HW-51 RISER DOES NOT REFLECT |
| | THE FLOOR PLAN. SECTIONS 106.1.1 & 106.3.5.1.3. |
| | **********RESPONSE NOTED, BUT RISER 34 IS MISSING THE |
| | 5TH FLOOR SUPPLY AND RISER 37 HAS 6 SETS OF SUPPLY |
| | STUBOUTS FOR 5 FLOORS. PLEASE CORRELATE.--THE |
| | COMMENT ABOUT THE SHOWER DETAIL 2/505 HAS NOT BEEN |
| | ADDRESSED. |
| | |
| | 16C. OK |
| | |
| | 17C. SHT P507 HOT & COLD WATER RISER DIAGRAM PLUMBING. |
| | ALL RISERS DO NOT REFLECT THE FLOOR PLAN AS THEY SHOW |
| | PIPING UNDERGROUND TO EACH RISER BUT THE FLOOR PLAN |
| | SHOWS THE WATER IN THE CEILING FEEDING DOWN TO THE |
| | FIRST FLOOR AND UP TO THE 2ND, 3RD, 4TH & 5TH FLOORS. |
| | --DETAIL 3/507 RISERS CW-89/HW-89, CW-90/HW-90 & |
| | CW-91/HW-91 DO NOT REFLECT THE FLOOR PLANS.--DETAIL |
| | 4/507 RISER CW-92 DOES NOT REFLECT THE FLOOR PLAN, NO |
| | ICE MACHINE SHOWN ON THE FLOOR PLAN.--DETAIL 5/507 |
| | RISERS CW-95 THRU CW-101 AND CW-103 THRU CW-114 DO NOT |
| | REFLECT THE FLOOR PLAN. ICE MAKER SHOWN ON THE 1ST |
| | FLOOR FLOOR PLAN BUT NOT SHOWN ON THE RISER DIAGRAM. -- |
| | CW-93 & CW-103 DOES NOT REFLECT THE FLOOR PLAN AS THE |
| | FLOOR PLANS SHOWS ICE MAKERS, WHERE AS THE RISER DOES |
| | NOT INDICATE 1ST FLOOR ICE MAKERS. --ALL ICE MAKER |
| | RISERS SHALL SHOW A WATER HAMMER ARRESTOR AT EACH ICE |
| | MAKER.--THERE IS NO RISER CW-102 SUBMITTED,TWO |
| | RISERS CW-98 SUBMITTED AND TWO RISERS 103 SUBMITTED. |
| | PLEASE CLARIFY. SECTIONS 106.1.1, 106.1.2 & 604.9. |
| | **********RESPONSE NOTED, BUT THE COMMENT CONCERNING |
| | DETAIL 3/507 RISERS HAS NOT BEEN ADDRESSED. THERE ARE |
| | NO 1ST FLOOR FIXTURES & ON RISERS 85 & 87 THE 5TH FLOOR |
| | FIXTURES ARE MISSING.--COMMENT CONCERNING THE ICE |
| | MAKER LINES ON DETAIL 5/507 HAVE NOT BEEN ADDRESSED. |
| | (CW-94 ALSO).--RISERS CW-75 & CW-76 ARE NOT |
| | SUBMITTED.--CW-93 & CW-103 DO NOT REFLECT THE FLOOR |
| | PLAN AS THERE IS NO ICE MAKER ON THE 1ST FLOOR. |
| | |
| | 18C. SHT P508 RISER DIAGRAM OVERALL FIRST FLOOR |
| | SANITARY. FIXTURE P6 FOR EMPLOYEE BREAK ROOM SINK, |
| | PLEASE INDICATE WHERE IT CONNECTS TO THE BRANCH LINE. |
| | --BRANCH LINE FOR SAN-86 NOT SHOWN.--RISERS |
| | SAN-82 & SAN-83 ARE NOT REFLECTING THE CONNECTION ON |
| | THE FLOOR PLAN. --RISERS SAN-89, SAN-90 & SAN-91 ARE |
| | NOT SHOWN ON THE RISER DIAGRAM.--RISERS SAN-9, |
| | SAN-10 & SAN-11 ARE NOT SHOWN ON THE RISER DIAGRAM.-- |
| | PIPING TO SAN-13 RISER DOES NOT REFLECT THE FLOOR PLAN. |
| | --SOME RISER LOCATIONS ON THE RISER DIAGRAM DO NOT |
| | REFLECT THE FLOOR PLAN. (EXAMPLES 14, 15, 77, 78)-- |
| | SAN RISER TO WASH MACHINES DO NOT REFLECT THE FLOOR |
| | PLAN SHT P101A. (FOUR RISERS SHOWN).--SUBMIT A |
| | FLOOR PLAN WITH SANITARY AND WATERRISER DIAGRAMS FOR |
| | THE WASH MACHINES IN GUEST LAUNDRY ROOM 218. SHOW PIPE |
| | SIZE, TRAPS, CLEANOUTS, VENTING FOR THE SANITARY RISER, |
| | AND SHOW PIPE SIZE, VALVES, WATER HAMMER ARRESTORS ETC |
| | FOR THE WATER RISER DIAGRAM.--CLEANOUT MISSING |
| | UPSTREAM OF SAN-34 THAT IS SHOWN ON THE FLOOR PLAN.-- |
| | SEVEN RISERS ALL SHOW RISER NUMBER SAN-34. THIS DOES |
| | NOT REFLECT THE FLOOR PLAN.--SAN-57 RISER DOES NOT |
| | REFLECT THE FLOOR PLAN AS IT DOES NOT SHOW A DOUBLE |
| | COMBO CONNECTION.--TWO SAN-48 RISER SHOWN ON THE |
| | RISER DIAGRAM. THAT DOES NOT REFLECT THE FLOOR PLAN. -- |
| | FIRST FIXTURE, (FLOOR DRAIN), UPSTREAM OF TOILET ROOMS |
| | 28 & 29 IS NOT SHOWN ON THE FLOOR PLAN SHT P101B. ALSO |
| | FIXTURE SHOWS A HORIZONTAL DRY VENT WHICH IS |
| | PROHIBITED.--FIRST FIXTURE, (FLOOR DRAIN). IN THE |
| | KITCHEN SHALL BE A FLOOR SINK, OR HUB DRAIN IF INDIRECT |
| | WASTE.--HORIZONTAL DRY VENT IS PROHIBITED PRIOR TO |
| | CLEANOUT AT THE UPSTREAM END OF THE KITCHEN FIXTURES. |
| | --RISER DIAGRAM SHOWS A SAN-47 RISER. THIS IS NOT |
| | SHOWN ON ANY FLOOR PLAN, NOR WAS THERE A RISER SAN-47 |
| | SUBMITTED. PLEASE CLARIFY.--THE SANITARY RISER |
| | DIAGRAM DOES NOT REFLECT THE FLOOR PLANS IN MANY AREAS. |
| | PLEASE RECHECK AND CORRELATE. SECTIONS 106.1.1, |
| | 106.2.1, 106.3.5.1.3, 604, 604.9, PDI-WH 201, TABLES |
| | 604.5, 604.10.1, 709.1, 710.1(1), 710.1(2), 905.3 & |
| | 905.4. |
| | **********RESPONSE NOTED, BUT THERE ARE TWO SAN-87 |
| | RISERS SHOWN AND NO SAN-86 RISER.--SAN-75 NOT |
| | SHOWN.--SAN 34 & SAN-63 ARE INDICATED UPSTREAM OF |
| | SAN-33 & SAN-64 ON THE RISER DIAGRAM, BUT DOWNSTREAM OF |
| | SAN-33 & SAN-64 ON THE FLOOR PLAN.--NO RESPONSE TO |
| | THE WATER REQUIREMENT FOR THE WASH MACHINES IN THE |
| | GUEST LAUNDRY ROOM 218.--PLEASE CORRELATE. |
| | |
| | 19C. SHT P509 RISER DIAGRAM OVERALL FIRST FLOOR WATER. |
| | ALL WATER HAMMER ARRESTORS SHALL BE LOCATED IN AN |
| | "EFFECTIVE RANGE",NOT IN THE CEILING AS SHOWN.-- |
| | RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN IN MANY |
| | AREAS AND RISERS DO NOT REFLECT THE FLOOR PLAN IN MANY |
| | AREA WHERE THE RISERS CONNECT TO THE WATER MAIN. PLEASE |
| | RECHECK THE ENTIRE RISER DIAGRAM PRIOR TO RESUBMITTING |
| | AS FAR AS RISER LOCATIONS AND RISER CONNECTIONS TO |
| | WATER MAIN.--RISER INDICATED HW/CW TO RISER 60, BUT |
| | RISER 60 ONLY HAS COLD WATER. CORRELATE.--RISERS |
| | 45, 46, 48, 49, 50 & 51 NOT SHOWN ON THE RISER DIAGRAM |
| | BUT ON THE FLOOR PLAN.--RISER 44 DOES NOT REFLECT |
| | THE FLOOR PLAN. SECTIONS 106.1.1, 106.1.2, PDI-WH 201, |
| | TABLES 604.5, 604.10.1. PDI-WH 201 & MANUF. |
| | INSTALLATION INSTRUCTIONS. |
| | **********RESPONSE NOTED, BUT THE WATER HAMMER |
| | ARRESTORS ARE STILL SHOWN IN THE CEILING AT THE TOP OF |
| | THE DROP OR UP IN THE DROP, NOT NEAR THE FIXTURES IN AN |
| | "EFFECTIVE RANGE" AS REQUIRED. ALL WATER HAMMER |
| | ARRESTORS SHALL BE LOCATED WHERE REQUIRED. --WATER |
| | SUPPLY LINE TO THE DRINKING FOUNTAIN BY THE POOL SHOWER |
| | DOES NOT REFLECT THE FLOOR PLAN, NOR DOES THE WATER |
| | RISER DIAGRAM FOR THE KITCHEN.--THE 4" COLD WATER |
| | LINE SUPPLYING THE PUMP ON THE SECOND FLOOR IS NOT |
| | SHOWN ON THE FLOOR PLAN AND THE WATER SUPPLY LINE TO |
| | THE WALL HYDRANT SHOWN ON THE FLOOR PLAN NEAR WHERE THE |
| | 4" WATER MAIN ENTERS THE BUILDING IS NOT SHOWN ON THE |
| | RISER DIAGRAM.--RISERS 40, 41, 42 & 43 ARE NOT |
| | INDICATED ON THE RISER DIAGRAM.--RISERS HW/CW-49 & |
| | HW/CW-51 ARE NOT SHOWN ON THE RISER DIAGRAM.--THERE |
| | ARE TWO CW-103 RISERS SHOWN ON THE RISER DIAGRAM.-- |
| | CW RISERS 75 & 76 ARE NOT SHOWN ON THE RISER DIAGRAM. |
| | --PLEASE CORRELATE. |
| | |
| | 20C. OK |
| | |
| | 21C. SHT P602 PLUMBING DETAILS. DETAIL NUMBER 1 DOES |
| | NOT COMPLY WITHTHE UTILITY STANDARD FOR GREASE |
| | INTERCEPTORS. PLEASE SEE ATTACHED SHEET. DETAIL |
| | INDICATES PREFAB TANKS. PLEASE SUBMIT MANUF. |
| | SPECIFICATIONS FOR GREASE INTERCEPTOR. ARTICLE III |
| | SECTION 90-124(7)(E)(F).--DETAIL 4 SHOWS A DOUBLE |
| | CHECK BACKFLOW PREVENTOR FOR THE DOMESTIC WATER |
| | BACKFLOW PREVENTOR. THIS IS NOT APPROVED. THE PROPER |
| | BACKFLOW PREVENTOR FOR THE DOMESTIC IS AN RPZV BACKFLOW |
| | PREVENTOR. SECTION 608.13.2. |
| | **********RESPONSE NOTED, BUT NEW DETAIL IS NOT |
| | LEGIBLE. SECTION 106.1.1. |
| | |
| | **********NEW COMMENT********** |
| | |
| | 1D. SEE ATTACHED SHEET CONCERNING THE DESIGN |
| | PROFESSIONALS AND FS 553.80(2)(B). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | -PLEASE RESUBMIT ONE SET OF OLD SHEETS |
| | FOR COMPARISON. |
| | |
| | ********NO RESPONSE, NOT ADDRESSED |
| | |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |