| 2008-05-09 09:33:16 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | ******FROM PREVIOUS REVIEW: 3RD REVIEW: |
| | |
| | ********FROM PREVIOUS REVIEWS: 4TH REVIEW: |
| | |
| | **********FROM PREVIOUS REVIEWS: 5TH REVIEW: |
| | |
| | A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS |
| | PERMIT. PLEASE SUBMIT THE FOLLOWING: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK,NATURAL. |
| | 4. OK |
| | 5. OK |
| | 6. OK |
| | 7. IOK |
| | 8. OK |
| | |
| | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED,BUT THE MANUF. SHEETS WILL BE |
| | REQUIRED TO VERIFY CFH & LISTING. PLEASE INDICATE IF |
| | THE GAS INFORMATION WILL BE SUBMITTED AT THE TIME OF |
| | GAS PERMIT APPLICATION. IF SO ALL GAS APPROVAL WILL BE |
| | WITHELD UNTIL THEN. |
| | ******RESPONSE NOTED, BUT ALL MANUF. SPECIFICATION |
| | SHEETS SHALL BE SUBMITTED PRIOR TO ISSUING THE GAS |
| | PERMIT. IT WAS INDICATED THAT THE SHEETS WOULD BE |
| | SUBMITTED AT THE MEETING HELD IN CITY HALL 7-19-07. |
| | ********RESPONSE NOTED, BUT THE POOL HEATERS DO NOT |
| | SHOW A LISTING AND THE BTU LOADS INDICATED DO NOT |
| | REFLECT THE BTU'S INDICATED ON THE RISER DIAGRAM. |
| | (INDICATE MODEL NUMBERS).--NO MANUF SHEETS WERE |
| | SUBMITTED FOR THE FIREPLACE NOR FOR THE BBQ GRILLS. |
| | **********NO RESPONSE NOT ADDRESSED. |
| | |
| | 10. N/A |
| | 11. N/A |
| | |
| | ***********NEW COMMENT********** |
| | |
| | 1B. OK |
| | |
| | **********NEW COMMENT |
| | |
| | 1C. OK |
| | 2C. OK |
| | |