Plan Review Notes
Plan Review Notes For Permit 06111071
Permit Number 06111071
Review Stop B
Sequence Number 5
Notes
Date Text
2008-02-22 13:22:56BUILDING PLAN REVIEW
 PERMIT: 06111071
 ADD: 2455 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 HOMEWOOD SUITES HOTEL/ HILTON
 FIVE STORY/ 114 UNITS
  
 JW-4TH REVIEW
 ACTION: DENIED
  
 1)INFOMATIONAL, WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2-16B) COMPLIED.
  
 16C) SHEET A-404, 3RD REQUEST, THE ELEVATOR SHAFT WALL
 DESIGNATION IS MISSING, THE TAG IS SHOWN ON THE PLANS
 BUT IS LEFT BLANK. (5) STORY BUILDINGS REQUIRE A 2HR
 RATED SHAFT, PLEASE SEE 707.4.
  
 17-20) COMPLIED.
  
 21) SHEET A-701 STAIRWAY THAT LEADS TO THE ROOF, THE
 DOOR EXITING TO THE ROOF DOES NOT INDICATE THE 1 1/2 HR
 FIRE RATING IN THE DOOR SCHEDULE, NOTE DOOR S6.2.
 SHAFTS 707.4 AND OPENING PROTECTIVES 715.3. THE
 DOORNORMALLY AT THE BOTTOM OF THE SHAFT DOES NOT
 REQUIRE FIRE RATINGS UNLESS THE EXTERIOR WALL REQUIRES
 RATINGS. THE DOOR AT THE TOP OF THE SHAFT IS STILL PART
 OF THE
 VERTICAL SHAFT ENCLOSURE, CREATING THE SAFE SMOKE AND
 FIRE FREE ZONE FOR VERTICAL EXIT ENCLOSURES.
  
 22-29D) COMPLIED.
  
 30) PRODUCT APPROVALS( PREVIOUS REVIEW, NOT NUMBERED)
 THE RESPONCE INDICATES THAT ALL THE WINDOWS AND DOORS
 ARE DESIGNED FOR THE INTERIOR WIND ZONE# 4. THIS
 STATEMENT IF TRUE WOULD NEED TO TAKE ALL OPENINGS AWAY
 FROM THE CORNERS OF THE BUILDING A MINIMUM OF 7'-6" SEE
 S-101. PLEASE REVIEW AND CORRECT EITHER THE
 ARCHITECTURAL AND STRUCTURAL SHEETS OR REVIEW THIS
 STATEMEENT AND CORRECT.
  
 S-101 IN REVIEWING THE PRODUCT APPROVAL DATA AND
 ASSOCIATED WIND ZONES PLEASE SEE HEADING# 1.11 THE
 DESIGN PRESSURES FOR SIGNS AND POLES, ARE DESIGNED TO
 THE WRONG STANDARD.
 THIS WAS THE STANDARD UNDER THE 2001 FBC, PLEASE
 CORRECT, SEE 1609.1.1.
  
 SHEET A-604 IN REVIEWING THE PRODUCT APPROVALS FOR THE
 WINDOWS AND DOORS THE TYPICAL GUEST ROOM WINDOW DETAIL
 INDICATES A SINGLE HUNG WINDOW, IN REVIEWING THE
 ELEVATIONS AND WINDOW
 DETAILS THIS SHEET THERE ARE NO SINGLE HUNG WINDOWS BUT
 THE COMMON GUEST ROOM WINDOW IS W1 A SLIDING WINDOW
 WITH INTEGRAL PTAC UNIT. MISSING PRODUCT APPROVAL FOR
 HORIZONTAL
 SLIDING WINDOW.
  
 SHEET A-604 WINDOW UNIT W-1 WITH PTAC UNIT INDICATES
 VARIOUS CUT SECTIONS ON SHEET A-605, ALL SECTIONS ARE
 MISSING, I BELIEVE THIS MAY OF BEEN DISCUSSED ON THE
 SPRINGHILL SUITES, HOW OR WHAT STRUCTURAL MEMBER WIL
 AJOIN THESE TWO MEMBERS. MULLIONS 1707.4.5.1 MULLIONS
 OCCURRING BETWEEN INDIVIDUAL WINDOW AND GLASS DOOR
 ASSEMBLIES. TESTING REPORTS ARE REQUIRED BY AN APPROVED
 TESTING LABORATORY OR BE ENGINEERED.
 1707.4.5.2 MULLIONS SHALL BE DESIGNED TO TRANSFER THE
 DESIGN PRESSURE LOADS APPLIED BY THE WINDOW OR DOOR
 ASSEMBLIES TO THE ROUGH OPENING SUBTRATE.
  
 PRODUCT APPROVAL FL7941-R1 THE ASSOCIATED REPORT THAT
 WAS SUBMITTED UNDER THIS APPROVAL NUMBER IS ILLEGABLE,
 PLEASE PROVIDE CLEAR LEGIBLE COPIES.
  
 PRODUCT APPROVAL FL1601-R3 UNDER THIS PRODUCT APPROVAL
 THE ROOFING SYSTEM MUST BE INSTALLED BY A CARLISLE
 AUTHORIZED ROOFING CONTRACTOR WITH SHOP DRAWINGS
 APPROVED BY CARLISLE.
 TO DATE NO ADDITIONAL INFORMATION HAS BEEN SUBMITTED.
 THIS CAN BE PROVISOED AS A SEPERATE PERMIT WITH
 SEPERATE FEES AND ASSOCIATED ROOFING REVIEW.
  
 SECTIONS OF THE FRONT ENTRY ALSO INDICATE THE USE OF
 EITHER CONCERTE OR CLAY ROOF TILE, NO PRODUCT APPROVALS
 HAVE BEEN SUBMITTED, NOR METHOD OF ATTACHMENT.
  
 SHEET A-302 INDICATES THE USE OF A FIREPLACE AND DOUBLE
 WALL FLUE, PLEASE SUBMIT PRODUCT APPROVALS IN
 COMPLIANCE WITH 2801 AND FBC MECHANICAL CODE.
  
 SHEET S-306 INDICATES THE USE OF METAL FRAME INFILL,
 PLEASE SUBMIT PRODUCT APPROVALS FOR EFIS WALL SYSTEMS.
 RULE 9B-72 (31)(C).
  
 30) COMPLIED. POOL TO BE UNDER SEPERATE PERMIT,
  
 31) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY
 OF THE PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE INFORMATION.
  
  
  
 NEW COMMENTS:
  
 32) NOTICE, SHEET A-301 HAS AN ROOFING ASSEMBLY UL P540
 SEE NOTE (6C) THIS IS A TYPE I-B BUILDING NO
 COMBUSTIBLE ALLOWED SEE TABLE 601 FOOTNOTE (C) (2) FOR
 USE OF FIRE RETARDANT TREATED
 GIRDERS, TRUSSES AND ROOF DECKS.
  
 33) PLEASE PROVIDE FIRE RATINGS FOR STRUCTURAL MEMBERS
 AS PER TABLE 601.
  
 34) SHEET A-101B/ G003 THE LIFE SAFETY PLAN SEE UNITS
 100 AND 101 REQUIRE 2 EXIT ACCESS DOORWAYS PLEASE SEE
 DOOR# 34. THIS DOOR IS NOT ON AN ACCESIBLE PATH OF
 TRAVEL, THERE IS ONLY A DOOR STOOP TO THE EXTERIOR,
 THEN SEE THE CIVIL PLANS C-2 THERE IS A YARD DRAIN (Y1)
 MAKING IT IMPOSSIBLE FOR A DISSABLED PERSON TO MAKE IT
 TO SAFETY.1014.2.1. 11-4.1.3(9).
  
 35) SHEET C-2 AND A-101A SEE DOOR NUMBER 152, 152A AND
 DOOR NUMBER 154 NEED TO HAVE ACCESSIBLE CURB CUTS TO
 THE PARKING LOT, THEY ALL ARE PART OF THE MEANS OF
 EGRESS THAT WILL ALLOW A DISABLED PERSON TO HAVE EGRESS
 TO THE PUBLIC WAY IN CASE OF EMERGENCY. 11-4.1.3(9)
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS