| 2008-02-22 13:22:56 | BUILDING PLAN REVIEW |
| | PERMIT: 06111071 |
| | ADD: 2455 METROCENTRE BLVD |
| | CONT: AUTOBUILDERS |
| | TEL: (561)310-7735 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | HOMEWOOD SUITES HOTEL/ HILTON |
| | FIVE STORY/ 114 UNITS |
| | |
| | JW-4TH REVIEW |
| | ACTION: DENIED |
| | |
| | 1)INFOMATIONAL, WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2-16B) COMPLIED. |
| | |
| | 16C) SHEET A-404, 3RD REQUEST, THE ELEVATOR SHAFT WALL |
| | DESIGNATION IS MISSING, THE TAG IS SHOWN ON THE PLANS |
| | BUT IS LEFT BLANK. (5) STORY BUILDINGS REQUIRE A 2HR |
| | RATED SHAFT, PLEASE SEE 707.4. |
| | |
| | 17-20) COMPLIED. |
| | |
| | 21) SHEET A-701 STAIRWAY THAT LEADS TO THE ROOF, THE |
| | DOOR EXITING TO THE ROOF DOES NOT INDICATE THE 1 1/2 HR |
| | FIRE RATING IN THE DOOR SCHEDULE, NOTE DOOR S6.2. |
| | SHAFTS 707.4 AND OPENING PROTECTIVES 715.3. THE |
| | DOORNORMALLY AT THE BOTTOM OF THE SHAFT DOES NOT |
| | REQUIRE FIRE RATINGS UNLESS THE EXTERIOR WALL REQUIRES |
| | RATINGS. THE DOOR AT THE TOP OF THE SHAFT IS STILL PART |
| | OF THE |
| | VERTICAL SHAFT ENCLOSURE, CREATING THE SAFE SMOKE AND |
| | FIRE FREE ZONE FOR VERTICAL EXIT ENCLOSURES. |
| | |
| | 22-29D) COMPLIED. |
| | |
| | 30) PRODUCT APPROVALS( PREVIOUS REVIEW, NOT NUMBERED) |
| | THE RESPONCE INDICATES THAT ALL THE WINDOWS AND DOORS |
| | ARE DESIGNED FOR THE INTERIOR WIND ZONE# 4. THIS |
| | STATEMENT IF TRUE WOULD NEED TO TAKE ALL OPENINGS AWAY |
| | FROM THE CORNERS OF THE BUILDING A MINIMUM OF 7'-6" SEE |
| | S-101. PLEASE REVIEW AND CORRECT EITHER THE |
| | ARCHITECTURAL AND STRUCTURAL SHEETS OR REVIEW THIS |
| | STATEMEENT AND CORRECT. |
| | |
| | S-101 IN REVIEWING THE PRODUCT APPROVAL DATA AND |
| | ASSOCIATED WIND ZONES PLEASE SEE HEADING# 1.11 THE |
| | DESIGN PRESSURES FOR SIGNS AND POLES, ARE DESIGNED TO |
| | THE WRONG STANDARD. |
| | THIS WAS THE STANDARD UNDER THE 2001 FBC, PLEASE |
| | CORRECT, SEE 1609.1.1. |
| | |
| | SHEET A-604 IN REVIEWING THE PRODUCT APPROVALS FOR THE |
| | WINDOWS AND DOORS THE TYPICAL GUEST ROOM WINDOW DETAIL |
| | INDICATES A SINGLE HUNG WINDOW, IN REVIEWING THE |
| | ELEVATIONS AND WINDOW |
| | DETAILS THIS SHEET THERE ARE NO SINGLE HUNG WINDOWS BUT |
| | THE COMMON GUEST ROOM WINDOW IS W1 A SLIDING WINDOW |
| | WITH INTEGRAL PTAC UNIT. MISSING PRODUCT APPROVAL FOR |
| | HORIZONTAL |
| | SLIDING WINDOW. |
| | |
| | SHEET A-604 WINDOW UNIT W-1 WITH PTAC UNIT INDICATES |
| | VARIOUS CUT SECTIONS ON SHEET A-605, ALL SECTIONS ARE |
| | MISSING, I BELIEVE THIS MAY OF BEEN DISCUSSED ON THE |
| | SPRINGHILL SUITES, HOW OR WHAT STRUCTURAL MEMBER WIL |
| | AJOIN THESE TWO MEMBERS. MULLIONS 1707.4.5.1 MULLIONS |
| | OCCURRING BETWEEN INDIVIDUAL WINDOW AND GLASS DOOR |
| | ASSEMBLIES. TESTING REPORTS ARE REQUIRED BY AN APPROVED |
| | TESTING LABORATORY OR BE ENGINEERED. |
| | 1707.4.5.2 MULLIONS SHALL BE DESIGNED TO TRANSFER THE |
| | DESIGN PRESSURE LOADS APPLIED BY THE WINDOW OR DOOR |
| | ASSEMBLIES TO THE ROUGH OPENING SUBTRATE. |
| | |
| | PRODUCT APPROVAL FL7941-R1 THE ASSOCIATED REPORT THAT |
| | WAS SUBMITTED UNDER THIS APPROVAL NUMBER IS ILLEGABLE, |
| | PLEASE PROVIDE CLEAR LEGIBLE COPIES. |
| | |
| | PRODUCT APPROVAL FL1601-R3 UNDER THIS PRODUCT APPROVAL |
| | THE ROOFING SYSTEM MUST BE INSTALLED BY A CARLISLE |
| | AUTHORIZED ROOFING CONTRACTOR WITH SHOP DRAWINGS |
| | APPROVED BY CARLISLE. |
| | TO DATE NO ADDITIONAL INFORMATION HAS BEEN SUBMITTED. |
| | THIS CAN BE PROVISOED AS A SEPERATE PERMIT WITH |
| | SEPERATE FEES AND ASSOCIATED ROOFING REVIEW. |
| | |
| | SECTIONS OF THE FRONT ENTRY ALSO INDICATE THE USE OF |
| | EITHER CONCERTE OR CLAY ROOF TILE, NO PRODUCT APPROVALS |
| | HAVE BEEN SUBMITTED, NOR METHOD OF ATTACHMENT. |
| | |
| | SHEET A-302 INDICATES THE USE OF A FIREPLACE AND DOUBLE |
| | WALL FLUE, PLEASE SUBMIT PRODUCT APPROVALS IN |
| | COMPLIANCE WITH 2801 AND FBC MECHANICAL CODE. |
| | |
| | SHEET S-306 INDICATES THE USE OF METAL FRAME INFILL, |
| | PLEASE SUBMIT PRODUCT APPROVALS FOR EFIS WALL SYSTEMS. |
| | RULE 9B-72 (31)(C). |
| | |
| | 30) COMPLIED. POOL TO BE UNDER SEPERATE PERMIT, |
| | |
| | 31) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY |
| | OF THE PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE INFORMATION. |
| | |
| | |
| | |
| | NEW COMMENTS: |
| | |
| | 32) NOTICE, SHEET A-301 HAS AN ROOFING ASSEMBLY UL P540 |
| | SEE NOTE (6C) THIS IS A TYPE I-B BUILDING NO |
| | COMBUSTIBLE ALLOWED SEE TABLE 601 FOOTNOTE (C) (2) FOR |
| | USE OF FIRE RETARDANT TREATED |
| | GIRDERS, TRUSSES AND ROOF DECKS. |
| | |
| | 33) PLEASE PROVIDE FIRE RATINGS FOR STRUCTURAL MEMBERS |
| | AS PER TABLE 601. |
| | |
| | 34) SHEET A-101B/ G003 THE LIFE SAFETY PLAN SEE UNITS |
| | 100 AND 101 REQUIRE 2 EXIT ACCESS DOORWAYS PLEASE SEE |
| | DOOR# 34. THIS DOOR IS NOT ON AN ACCESIBLE PATH OF |
| | TRAVEL, THERE IS ONLY A DOOR STOOP TO THE EXTERIOR, |
| | THEN SEE THE CIVIL PLANS C-2 THERE IS A YARD DRAIN (Y1) |
| | MAKING IT IMPOSSIBLE FOR A DISSABLED PERSON TO MAKE IT |
| | TO SAFETY.1014.2.1. 11-4.1.3(9). |
| | |
| | 35) SHEET C-2 AND A-101A SEE DOOR NUMBER 152, 152A AND |
| | DOOR NUMBER 154 NEED TO HAVE ACCESSIBLE CURB CUTS TO |
| | THE PARKING LOT, THEY ALL ARE PART OF THE MEANS OF |
| | EGRESS THAT WILL ALLOW A DISABLED PERSON TO HAVE EGRESS |
| | TO THE PUBLIC WAY IN CASE OF EMERGENCY. 11-4.1.3(9) |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |