| Date |
Text |
| 2008-03-01 17:41:10 | |
| | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2001 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | ******FROM PREVIOUS REVIEWS: 3RD REVIEW: |
| | |
| | ********FROM PREVIOUS REVIEWS: 4TH REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | 6. OK (INFORMATIONAL ONLY) |
| | |
| | 7. SHT AC104 POOL HOUSE PLAN. MENS TOILET ROOM REQUIRES |
| | A URINAL. PLEASE INDICATE ON PLANS. TABLE 424.1.6.1. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT NOW A TOILET STALL IS SHOWN |
| | IN THE TOILET ROOM. PER SECTION 11-4.17.3 EXCEPTION NEW |
| | CONTRUCTION AN ACCESSIBLE LAV IS REQUIRED IN THE STALL. |
| | (SEE THE EXCEPTION (1) TO SECTION 310.4 WHERE A STALL |
| | IS NOT REQUIRED). |
| | ********RESPONSE NOTED, BUT NEW STALL DOES NOT COMPLY |
| | WITH SECTION 11-4.17.3 EXCEPTION NEW CONSTRUCTION. |
| | |
| | 8. OK |
| | 9. OK |
| | 10. OK |
| | 11. OK |
| | 12. OK |
| | 13. OK |
| | 14. OK |
| | 15. OK |
| | 16. OK |
| | |
| | 17. SHT A-808 ELEVATION DETAIL 9. THE SINK SHALL BE |
| | ACCESSIBLE & SHALL COMPLY WITH SECTION 11-4.24 AND ALL |
| | SUBSECTIONS. PLEASE SHOW COMPLIANCE. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT COMPLIANCE NOT SHOWN FOR THE |
| | FOLLOWING: |
| | A. 11-4.24.3 KNEE CLEARANCE |
| | B. 11-4.24.4 SINK DEPTH |
| | C. 11-4.24.5 CLEAR FLOOR SPACE |
| | D. 11-4.24.7 FAUCETS |
| | ********RESPONSE NOTED, BUT NO SINK DEPTH IS INDICATED, |
| | NO CLEAR FLOOR SPACE SHOWN ON THE FLOOR PLAN, NOR HAS |
| | THE FAUCET INFORMATION BEEN SUBMITTED. |
| | |
| | 18. SHT A-809 ELEVATIONS 4 & 9. THE SINK SHALL COMPLY |
| | WITH SECTION 11-4.24 AND ALL SUBSECTIONS. A FORWARD |
| | APPROACH CLEAR FLOOR SPACE IS REQUIRED AND SHALL EXTEND |
| | A MAXIMUM OF 19" UNDERNEATH THE SINK. CABINET DOORS ARE |
| | NOT APPROVED IN THE CLEAR FLOORSPACE AND ARE NOT TO |
| | BE INSTALLED. SUBMIT A SIDE ELEVATION SHOWING THE |
| | GARBAGE DISPOSAL. INDICTE COMPLIANCE WITH FIGURE 11-31. |
| | THE GARBAGE DISPOSAL SHALL BE ADA APPROVED LOW PROFILE |
| | TYPE THAT DOES NOT ENTER THE REQUIRED CLEAR FLOOR SPACE |
| | OF THE SINK.SECTION 106.1.1. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT |
| | SHOWN AT THE SINK IN THE EMPLOYEE BREAKROOM, (126), AND |
| | IS SHOWN AS PARALLEL APPROACH ON DETAIL #2. ELEVATION |
| | #4 DOES NOT SHOW THE KNEE CLEARANCE REQUIRED BY SECTION |
| | 11-4.24.3. ELEVATIONS #4 & #9 DO NOT SHOW THE SINK |
| | DEPTH REQUIRED BY SECTION 11-4.24.4. ELEVATION #4 |
| | EXPOSED PIPES & SURFACES REQUIREMENT OF 11-4.24.6. |
| | ELEVATIONS #4 & #9 THE FAUCET REQUIREMENT OF |
| | 11-4.24.7. |
| | ********RESPONSE NOTED, BUT NO SINK DETAIL SHOWN, NO |
| | CLEAR FLOOR SPACE SHOWN ON THE FLOOR PLAN. |
| | |
| | 19. RESPONSE NOTED, NOT APPLICABLE |
| | 20. OK. |
| | 21. OK |
| | 22. OK |
| | 23. OK |
| | 24. OK |
| | 25. OK |
| | 26. OK |
| | 27. OK |
| | 28. OK |
| | 29. OK |
| | 30. OK |
| | 31. OK |
| | 32. OK |
| | 33. OK |
| | |
| | 34. INDICATE A NUMBER DESIGNATION FOR EACH RISER |
| | INCLUDING ALL SANT., WATER, STORM, CONDENSATE. (EXAMPLE |
| | SANT-1, SANT-2, RWL-1, RWL-2, CON-1, CON-2, W-1, W-2 |
| | ETC.). THIS WILL AID IN TRACKING ALL RISERS FROM THE |
| | UNDERGROUND PIPING THROUGH THE ROOF. SECTIONS |
| | 106.3.5.1.3 & SECTION 106.1.1.--INDICATE WHICH |
| | RISER IS TYPICAL OF WHICH RISER ISOMETRIC DIAGRAM. |
| | (EXAMPLE SANT-1 SANT-4 TYPICAL OF DETALI 4 SHT P401) -- |
| | INDICATE ROOM NUMBER EACH RISER CAN BE LOCATED. |
| | ****RESPONSE NOTED, BUT SHEET P503 HAS NOT BEEN |
| | SUBMITTED. |
| | ******RESPONSE NOTED, BUT RESPONSE DOES NOT ADDRESS THE |
| | WATER RISERS, STORM RISERS, OR CONDENSATE RISERS. |
| | ********RESPONSE NOTED, BUT THERE ARE STILL RISER |
| | DESIGNATIONS MISSING ON THE FIRST FLOOR. |
| | |
| | 35. ROUTE PLANS TO THE DEPT. OF BUSINESS REGULATION, |
| | HOTEL & RESTURANT DIVISION FOR REVIEW PRIOR TO |
| | RESUBMITTING TO THE CITY FOR REVIEW. A MINIMUM OF TWO |
| | SETS OF PLANS, STAMPED BY DBPR AND TWO PAGE |
| | "WORKSHEETS" ATTACHED TO PLAN ARE REQUIRED. SECTION |
| | 102.2.1. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE TWO PAGE SPECIFICATION |
| | WORKSHEETS FOR THE HOMEWOOD REVIEW ARE ATTACHED TO THE |
| | SPRINGHILL PLANS, AND THE WORKSHEETS FOR THE SPRINGHILL |
| | PLANS ARE ATTACHED TO THE HOMEWOOD PLANS. PLEASE INSERT |
| | THE CORRECT SPECIFICATION WORKSHEETS IN THE CORRECT |
| | PLANS. |
| | ********RESPONSE NOTED, BUT THE SPECIFICATION |
| | WORKSHEETS HAVE NOT BEEN FOUND THIS SUBMITTAL. |
| | |
| | 36. OK |
| | 37. OK |
| | |
| | *****NEW COMMENTS 3RD REVIEW***** |
| | |
| | |
| | 1B. OK |
| | |
| | 2B. SHT G-001 NOT ALL SHEETS SHOWN ON THE DRAWING INDEX |
| | HAVE BEEN SUBMITTED, AND SOME SHEETS ARE OUT OF ORDER. |
| | PLEASE CORRELATE THE SHEETS SUBMITTED WITH THE DRAWING |
| | INDEX. SECTION 106.1.1. |
| | ********RESPONSE NOTED, BUT ONE SET OF PLANS HAS TWO |
| | SHEETS P507 ONE SEAL DATED 12/18/07 AND THE OTHER |
| | SEALED 12/19/07. ALSO ONE SET IS MISSING SHTS P101C & |
| | P101D. PLEASE SUBMIT 3 SETS OF PLANS THAT HAVE ALL |
| | SHEETS PER DRAWING INDEX. |
| | |
| | 3B. OK |
| | 4B. OK |
| | 5B. OK |
| | 6B. OK |
| | 7B. OK |
| | |
| | 8B. SHT P101B THREE BRANCH CONNECTIONS ARE SHOWN |
| | CONNECTING AGAINST THE FLOW. THIS IS NOT APPROVED PER |
| | SECTION 706.3. PLEASE SHOW FITTING INSTALLATION SO THAT |
| | IS GUIDES THE SEWAGE AND WASTE IN THE DIRECTION OF |
| | FLOW. |
| | ********RESPONSE NOTED, BUT TWO BRANCH LINES ARE SHOWN |
| | CONNECTING AGAINST THE FLOW. |
| | |
| | 9B. OK |
| | 10B. OK |
| | 11B. OK |
| | 12B. OK |
| | 13B. OK |
| | 14B. OK |
| | 15B. OK |
| | 16B. OK |
| | 17B. OK |
| | 18B. OK |
| | 19B. OK |
| | 20B. OK |
| | |
| | 21B. SHT P501 DETAIL/RISER #1 DOES NOT REFLECT THE |
| | FLOOR PLAN AT FIXTURES P6 & P8.--DETAIL /RISER #5 |
| | DOES NOT REFLECT SHT P101A SAN #1 & INDICATES PASSING |
| | THRU THE 1ST FLOOR TWICE. PLEASE CLARIFY. SECTION |
| | 106.1.1.--DETAIL/RISER 3 INDICATES GUEST |
| | LAUNDRY/MAINTENANCE. THIS IS NOT FOUND ON THE FLOOR |
| | PLAN. PLEASE CLARIFY. |
| | ********RESPONSE NOTED, BUT RISER DIAGRAM SAN-1 NOW |
| | SHOWS ACCESSIBLE SHOWER ON ALL FLOORS. |
| | |
| | 22B. SHT P502 THE WATER RISER DIAGRAMS DO NOT REFLECT |
| | THE FLOOR PLANS. NOT ALL FLOOR PLANS ARE SHOWN. PLEASE |
| | SUBMIT RISERS TO REFLECT THE FLOOR PLAN AND SUBMIT A |
| | FLOOR PLAN FOR EACH UNIT TYPE. SECTION 106.3.5.1.3. |
| | ********RESPONSE NOTED, BUT THERE ARE STILL RISERS THAT |
| | DO NOT REFLECT THE FLOOR PLAN. SEE NEW COMMENTS. |
| | |
| | 23B. OK |
| | 24B. OK |
| | 25B. OK |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1C. SHT P101A FIRST FLOOR PLAN SANITARY WASTE & VENT |
| | PLAN. THERE IS NO PIPING TO SAN-1 RISER FROM THE |
| | BUILDING DRAIN.--THE FIRST FLOOR SHOWER TO SAN-1 |
| | IS NOT INDICATED ON THE FLOOR PLAN.--THERE IS NO |
| | PIPING TO SAN-6 RISER FROM BUILDING DRAIN.--THERE |
| | IS NO PIPING TO SAN-11 RISER FROM THE BUILDING DRAIN. |
| | --THE SLOPE INDICATOR ON THE BUILDING DRAIN FROM |
| | SAN-16 RISER TO SAN-33 RISER IS OPPOSITE OF THE PIPING. |
| | --IDENTIFY THE RISER IN THE EXERCISE ROOM (118)AND |
| | THE RISER BY ELEVATOR #2.--FLOOR DRAINS ARE NOT |
| | APPROVED INDIRECT WASTE RECEPTORS. FLOOR SINKS OR HUB |
| | DRAIN ARE REQUIRED AND SHALL BE LOCATED SO THEY ARE NOT |
| | TRIPPING HAZARDS.--THE EMPLOYEE SINK ON THE FIRST |
| | FLOOR IS SHOWN CONNECTING IN THE CEILING OF THE FIRST |
| | FLOOR ON THE FLOOR PLAN NOT UNDERGROUND AS REQUIRED. -- |
| | SHOW THE RISER DESIGNATIONS FOR SANITARY RISERS 85, 86, |
| | 87 & 88 ON THE FLOOR PLAN SO THE RISERS CAN BE TRACKED |
| | FROM THE FIRST FLOOR UP.--SUBMIT SANITARY AND WATER |
| | RISER DIAGRAMS THAT REFLECT KEY NOTE NUMBER 11. |
| | SECTIONS 106.1.1, 106.3.5.1.3, 706.3, 802.3, 802.3.2, |
| | AND TABLES 710.1(1) & 710.1(2). |
| | |
| | 2C. SHT P101B FIRST FLOOR PLAN SANITARY WASTE & VENT |
| | PLAN. THERE ARE FITTINGS THAT ARE INDICATED AS |
| | INSTALLED AGAINST THE FLOW.--THE SHOWER IS NOT |
| | SHOWN ON THE FLOOR PLAN IN THE ACCESSIBLE DOUBLE QUEEN |
| | UNIT (101) AS WELL AS A SANITARY RISER THAT DOES NOT |
| | INDICATE THE RISER NUMBER.--SECTIONS 106.1.1, |
| | 706.3. |
| | |
| | 3C. SHT P101C FIRST FLOOR PLAN DOMESTIC WATER & GAS. |
| | MANY WATER RISERS SHOW NO WATER LINES CONNECTING TO THE |
| | WATER MAIN. SHOW ALL PIPING ON THE FLOOR PLAN.-- |
| | ACCESSIBLE STUDIO REFERS TO DETAIL 5, SHEET P401, BUT |
| | DETAIL 5 HAS NOT BEEN SUBMITTED.--THREE OTHER |
| | REFERENCES TO DETAIL 4, SHT P402, BUT THESE DETAILS ARE |
| | FOR SANITARY WASTE & VENT, NOT WATER INFORMATION. |
| | CLARIFY-- ACCESSIBLE STUDIO (125), SHOWER IS NOT |
| | SHOWN ON THE FLOOR PLAN.--RISER CW-92 IS NOT SHOWN |
| | ON THE FLOOR PLAN.--SHOW THE LOCATION OF RISERS 85, |
| | 86 & 87 ON THE FLOOR PLAN SO THE RISERS CAN BE TRACKED. |
| | --FLOOR PLAN REFERENCES RISER CW-94, BUT NO CW-94 WAS |
| | SUBMITTED,--3" HOT WATER MAIN LINE HAS BEEN |
| | MISLABELED AS 3" COLD WATER. SECTIONS 106.1.1 106.1.2 & |
| | 604. |
| | |
| | 4C. SHT P101D FIRST FLOOR PLAN DOMESTIC WATER & GAS. |
| | SOME RISER DESIGNATIONS ARE NOT LEGIBLE.--SOME |
| | RISERS SHOW NO PIPING TO THE RISER--SHOWER NOT |
| | SHOWN ON THE FLOOR PLAN FOR THE ACCESSIBLE QUEEN (101). |
| | --RISER CW-104 NOT SUBMITTED.--BOTH HOT AND COLD |
| | WATER FOR CW-50 CONNECT TO THE HOT WATER MAIN. SECTIONS |
| | 106.1.1, 106.1.2 & 607.4. |
| | |
| | 5C. SHT P102 SECOND FLOOR PLUMBING. ACCESSIBLE STUDIO |
| | (225) IS INDICATED AS KING UNIT ON THE ARCHITECTURAL |
| | FLOOR PLAN. PLEASE CORRELATE.--RISER SAN-13 IS |
| | LABELED AS SAN-3. PLEASE CORRELATE.--NO RISERS |
| | INDICATED FOR THE SHOWER IN STUDIO 105 THRU 505.-- NO |
| | LAV SHOWN IN ACCESSIBLE QUEEN (201).--THE RISERS |
| | BEHIND WHERE THE LAV SHOULD BE IN THE ACCESSIBLE QUEEN |
| | ARE NOT SHOWN ON THE FIRST FLOOR, NOR ARE THEY SHOWN ON |
| | THE THIRD FLOOR. PLEASE CLARIFY. IDENTIFY RISERS.-- |
| | INFORMATION AT THE RIGHT SIDE OF THE KEY NOTES IS NOT |
| | LEGIBLE.SECTIONS 106.1.1, 106.1.2. |
| | |
| | 6C. SHT P103 THIRD TO FIFTH FLOOR PLUMBING. THE SHOWER |
| | IS NOT SHOWN ON THE FLOOR PLAN FOR SAN-1.--SANITARY |
| | RISER 71 IS NOT LEGIBLE.--NO LAV SHOWN ON THE FLOOR |
| | PLAN IN UNIT WITH SAN-46 & SAN-48. SECTIONS 106.1.1 & |
| | 106.1.2. |
| | |
| | 7C. SHT P104A ROOF PLAN PLUMBING. THE CALCULATIONS FOR |
| | ZONE 7 DO NOT COMPUTE. PLEASE RECHECK FIGURES. SECTION |
| | 106.1.1 & TABLE 1106.3. |
| | |
| | 8C. SHT P402 ACCESSIBLE STUDIO UNIT PLAN - WASTE & |
| | VENT. THE SHOWER IS NOT SHOWN ON THE FLOOR PLAN. |
| | SECTION 106.1.1. |
| | |
| | 9C. SHT P403 PARTIAL PLAN KITCHEN - WASTE & VENT. |
| | IDENTIFY ROOM AND IDENTIFY WHAT DRAINS INTO THE FLOOR |
| | DRAIN. (KEY NOTE 10).--HORIZONTAL DRY VENT |
| | DOWNSTREAM OF THE CLEANOUT IS NOT APPROVED.--KEY |
| | NOTE 14 THE 2" HUB DRAIN IS NOT APPROVED FOR INDIRECT |
| | WASTE FOR THE DISHWASHER. A FLOOR SINK LARGE ENOUGH TO |
| | ACCEPT ALL THE PUMPING ACTION WITH A BASKET TO CATCH |
| | ANY OR ALL SOLIDS IS REQUIRED.--FLOOR DRAIN BY THE |
| | REF & FREEZER SHALL BE ACCESSIBLE AND NOT BE A TRIPPING |
| | HAZARD. EXPLAIN THE 1/2 GRATE. --PLUMBING KEY NOTES 3 |
| | NOT FOUND. PLEASE CLAIFY. SECTIONS 106.1.1, 106.1.2, |
| | 708.9. 802.3.2. |
| | |
| | 10C. SHT P403 PARTIAL PLAN - WASTE & VENT. PIPING TO |
| | THE LAV IN THE WOMENS TOILET ROOM DOES NOT REFLECT THE |
| | RISER DIAGRAM. NO PIPING IS SHOWN TO THE LAV. SECTION |
| | 106.1.1. |
| | |
| | 11C. SHT P501 SANITARY RISER DIAGRAMS PLUMBING. EVERY |
| | VENT STACK SHALL CONNECT TO THE BASE OF THE DRAINAGE |
| | STACK. SECTION 903.4. SEE STACKS 3, 6, 12, 17, 23 & 30. |
| | --ALL SINK AND LAV RISERS SHOW TRAPS UNDER THE SLABS |
| | FOR THESE FIXTURES. PLEASE CLAIRFY. SECTIONS 106.1.1 & |
| | 1002.1.--DETAIL 1 REFERENCES ACCESSIBLE STUDIO 2BD, |
| | 1ST THRU 5TH FLOOR ONLY, BUT THE ARCHITECURAL SHEETS |
| | INDICATE THAT THE 2ND FLOOR IS A STANDARD STUDIO AND |
| | THE 3RD THRU 5TH FLOORS ARE ACCESSIBLE KINGS. PLEASE |
| | CORRELATE.--SAN-1 DOES NOT REFLECT THE FLOOR PLAN. |
| | ALL FLOORS INDICATE ACCESSIBLE SHOWERS, BUT THE FIRST |
| | FLOOR SHOWS AN ACCESSIBLE SHOWER, THE SECOND FLOOR |
| | SHOWS A STANDARD TUB, AND THIRD FLOOR THRU FIFTH FLOOR |
| | SHOWS ACCESSIBLE TUB. PLEASE CORRELATE.--SAN-2, |
| | SAN-3 & SAN-4 DO NOT REFLECT THE FLOOR PLAN BECAUSE OF |
| | THE SAME CONDITION OF CHANGING FLOOR PLANS BUT THE |
| | RISER SHOWS THE SAME FOR EACH FLOOR. CORRELATE.-- |
| | SAN-22 DOES NOT REFLECT THE FLOOR PLAN.SECTION |
| | 106.1.1. |
| | |
| | 12C. SHT P502SANITARY RISER DIAGRAMS PLUMBING. EVERY |
| | VENT STACK SHALL CONNECT TO THE BASE OF THE DRAINAGE |
| | STACK. SECTION 903.4. SEE STACKS 37, 44, 46, 54 & 60. |
| | --ALL SINK AND LAV RISERS SHOW TRAPS UNDER THE SLABS |
| | FOR THESE FIXTURES. PLEASE CLAIRFY. SECTIONS 106.1.1 & |
| | 1002.1.--DETAIL ONE SHOWS THE SECOND SAN-31 RISER |
| | SUBMITTED. THE RISER 31 ON THE PREVIOUS SHEET SHOWS |
| | SINKS, THE RISER 31 ON THIS SHEET SHOWS TUBS. PLEASE |
| | CLARIFY.--SAN-36 RISER DOES NOT REFLECT THE FLOOR |
| | PLAN.--SAN-48 DOES NOT REFLECT THE FLOOR PLAN AS IT |
| | INDICATES A SHOWER ON THE FIRST FLOOR THAT IS NOT SHOWN |
| | ON THE FLOOR PLAN, THEN CHANGES INTO W/C'S & TUBS FROM |
| | THE 3RD FLOOR TO THE 5TH FLOOR.--SAN-46 DOES NOT |
| | REFLECT THE FLOOR PLAN AS IT DOES NOT SHOW THE W/C ON |
| | THE FIRST FLOOR, DOES NOT SHOW THE OFFSET BETWEEN THE |
| | 2ND AND 3RD FLOORS AND SHOWS LAVS ON THE 3RD THRU 5TH |
| | FLOORS.--SAN-48/SAN-46 SHOW NO VENT THRU ROOF. |
| | SECTIONS 106.1.1 & 903.3. |
| | |
| | 13C. SHT P503 SANITARY RISER DIAGRAMS PLUMBING. EVERY |
| | VENT STACK SHALL CONNECT TO THE BASE OF THE DRAINAGE |
| | STACK. SECTION 903.4. SEE STACKS 66, 74, 77, 84, 91 & |
| | 87.--ALL SINK AND LAV RISERS SHOW TRAPS UNDER THE |
| | SLABS FOR THESE FIXTURES. PLEASE CLAIRFY. SECTIONS |
| | 106.1.1 & 1002.1.--RISER SAN-76 DOES NOT REFLECT |
| | THE FLOOR PLAN.--SAN-91 RISER DOES NOT REFLECT THE |
| | FLOOR PLAN.--SAN-90 RISER DIAGRAM DOES NOT REFLECT |
| | THE FLOOR PLAN.--SAN-89 RISER DOES NOT REFLECT THE |
| | FLOOR PLAN. SECTIONS 106.1.1 & 106.3.5.1.3. |
| | |
| | 14C. SHT P504 HOT & COLD WATER RISER DIAGRAM PLUMBING. |
| | ALL RISERS DO NOT REFLECT THE FLOOR PLAN AS THEY SHOW |
| | PIPING UNDERGROUND TO EACH RISER BUT THE FLOOR PLAN |
| | SHOWS THE WATER IN THE CEILING FEEDING DOWN TO THE |
| | FIRST FLOOR AND UP TO THE 2ND, 3RD, 4TH & 5TH FLOORS. |
| | --CW-1/HW-1 DOES NOT REFLECT THE FLOOR PLAN AS IT |
| | SHOWS THE SUPPLY PIPING UNDERGROUND.--CW-4/HW-4 |
| | DOES NOT REFLECT THE FLOOR PLAN.--NO WATER RISER |
| | FOR THE SHOWER IN THE STUDIO UNITS 113 THRU 513. |
| | SECTIONS 106.1.1 & 106.3.5.1.3. |
| | |
| | 15C. SHT P505 HOT & COLD WATER RISER DIAGRAM PLUMBING. |
| | ALL RISERS DO NOT REFLECT THE FLOOR PLAN AS THEY SHOW |
| | PIPING UNDERGROUND TO EACH RISER BUT THE FLOOR PLAN |
| | SHOWS THE WATER IN THE CEILING FEEDING DOWN TO THE |
| | FIRST FLOOR AND UP TO THE 2ND, 3RD, 4TH & 5TH FLOORS. |
| | --NO RISER FOR THE SHOWER IN DETAIL 2/505.-- |
| | CW-43/HW-43 RISER SHOWS THE SUPPLY PIPING UNDERGROUND. |
| | --CW-41/HW-41 RISER DOES NOT REFLECT THE FLOOR PLAN. |
| | --DETAIL 3/505 SHOWS TWO CW-43 RISERS. PLEASE |
| | CLARIFY.--DETAIL 4/505 DOES NOT SHOW A LAV RISER |
| | DIAGRAM.--CW-48/HW-48 RISER DOES NOT REFLECT THE |
| | FLOOR PLAN.--CW-45/HW-45 DOES NOT REFLECT THE FLOOR |
| | PLAN.--DETAIL 5/505 DOES NOT SHOW A WATER CLOSET |
| | RISER DIAGRAM.--CW-51/HW-51 RISER DOES NOT REFLECT |
| | THE FLOOR PLAN. SECTIONS 106.1.1 & 106.3.5.1.3. |
| | |
| | 16C. SHT P506 HOT & COLD WATER RISER DIAGRAM PLUMBING. |
| | ALL RISERS DO NOT REFLECT THE FLOOR PLAN AS THEY SHOW |
| | PIPING UNDERGROUND TO EACH RISER BUT THE FLOOR PLAN |
| | SHOWS THE WATER IN THE CEILING FEEDING DOWN TO THE |
| | FIRST FLOOR AND UP TO THE 2ND, 3RD, 4TH & 5TH FLOORS. |
| | --DETAIL 1/506 CW-53/HW-53 SHOWS THE WATER SUPPLIES |
| | FOR THE SHOWER UNDER THE FIRST FLOOR SLAB.--DETAIL |
| | 1/506 CW-56/HW-56 SHOWS NO SINK ON THE FIRST FLOOR. |
| | THIS DOES NOT REFLECT THE FLOOR PLAN.--DETAIL 2/506 |
| | DOES NOT REFLECT THE FLOOR PLAN AS THERE IS NO RISER |
| | FOR THE SHOWERS IN UNITS 104 THRU 504.--DETAIL |
| | 3/506 DOES NOT REFLECT THE FLOOR PLAN AS THERE IS NO |
| | RISER FOR THE TUBS IN UNITS 109 THRU 509. SECTIONS |
| | 106.1.1 & 106.3.5.1.3. |
| | |
| | 17C. SHT P507 HOT & COLD WATER RISER DIAGRAM PLUMBING. |
| | ALL RISERS DO NOT REFLECT THE FLOOR PLAN AS THEY SHOW |
| | PIPING UNDERGROUND TO EACH RISER BUT THE FLOOR PLAN |
| | SHOWS THE WATER IN THE CEILING FEEDING DOWN TO THE |
| | FIRST FLOOR AND UP TO THE 2ND, 3RD, 4TH & 5TH FLOORS. |
| | --DETAIL 3/507 RISERS CW-89/HW-89, CW-90/HW-90 & |
| | CW-91/HW-91 DO NOT REFLECT THE FLOOR PLANS.--DETAIL |
| | 4/507 RISER CW-92 DOES NOT REFLECT THE FLOOR PLAN, NO |
| | ICE MACHINE SHOWN ON THE FLOOR PLAN.--DETAIL 5/507 |
| | RISERS CW-95 THRU CW-101 AND CW-103 THRU CW-114 DO NOT |
| | REFLECT THE FLOOR PLAN. ICE MAKER SHOWN ON THE 1ST |
| | FLOOR FLOOR PLAN BUT NOT SHOWN ON THE RISER DIAGRAM. -- |
| | CW-93 & CW-103 DOES NOT REFLECT THE FLOOR PLAN AS THE |
| | FLOOR PLANS SHOWS ICE MAKERS, WHERE AS THE RISER DOES |
| | NOT INDICATE 1ST FLOOR ICE MAKERS. --ALL ICE MAKER |
| | RISERS SHALL SHOW A WATER HAMMER ARRESTOR AT EACH ICE |
| | MAKER.--THERE IS NO RISER CW-102 SUBMITTED,TWO |
| | RISERS CW-98 SUBMITTED AND TWO RISERS 103 SUBMITTED. |
| | PLEASE CLARIFY. SECTIONS 106.1.1, 106.1.2 & 604.9. |
| | |
| | 18C. SHT P508 RISER DIAGRAM OVERALL FIRST FLOOR |
| | SANITARY. FIXTURE P6 FOR EMPLOYEE BREAK ROOM SINK, |
| | PLEASE INDICATE WHERE IT CONNECTS TO THE BRANCH LINE. |
| | --BRANCH LINE FOR SAN-86 NOT SHOWN.--RISERS |
| | SAN-82 & SAN-83 ARE NOT REFLECTING THE CONNECTION ON |
| | THE FLOOR PLAN. --RISERS SAN-89, SAN-90 & SAN-91 ARE |
| | NOT SHOWN ON THE RISER DIAGRAM.--RISERS SAN-9, |
| | SAN-10 & SAN-11 ARE NOT SHOWN ON THE RISER DIAGRAM.-- |
| | PIPING TO SAN-13 RISER DOES NOT REFLECT THE FLOOR PLAN. |
| | --SOME RISER LOCATIONS ON THE RISER DIAGRAM DO NOT |
| | REFLECT THE FLOOR PLAN. (EXAMPLES 14, 15, 77, 78)-- |
| | SAN RISER TO WASH MACHINES DO NOT REFLECT THE FLOOR |
| | PLAN SHT P101A. (FOUR RISERS SHOWN).--SUBMIT A |
| | FLOOR PLAN WITH SANITARY AND WATERRISER DIAGRAMS FOR |
| | THE WASH MACHINES IN GUEST LAUNDRY ROOM 218. SHOW PIPE |
| | SIZE, TRAPS, CLEANOUTS, VENTING FOR THE SANITARY RISER, |
| | AND SHOW PIPE SIZE, VALVES, WATER HAMMER ARRESTORS ETC |
| | FOR THE WATER RISER DIAGRAM.--CLEANOUT MISSING |
| | UPSTREAM OF SAN-34 THAT IS SHOWN ON THE FLOOR PLAN.-- |
| | SEVEN RISERS ALL SHOW RISER NUMBER SAN-34. THIS DOES |
| | NOT REFLECT THE FLOOR PLAN.--SAN-57 RISER DOES NOT |
| | REFLECT THE FLOOR PLAN AS IT DOES NOT SHOW A DOUBLE |
| | COMBO CONNECTION.--TWO SAN-48 RISER SHOWN ON THE |
| | RISER DIAGRAM. THAT DOES NOT REFLECT THE FLOOR PLAN. -- |
| | FIRST FIXTURE, (FLOOR DRAIN), UPSTREAM OF TOILET ROOMS |
| | 28 & 29 IS NOT SHOWN ON THE FLOOR PLAN SHT P101B. ALSO |
| | FIXTURE SHOWS A HORIZONTAL DRY VENT WHICH IS |
| | PROHIBITED.--FIRST FIXTURE, (FLOOR DRAIN). IN THE |
| | KITCHEN SHALL BE A FLOOR SINK, OR HUB DRAIN IF INDIRECT |
| | WASTE.--HORIZONTAL DRY VENT IS PROHIBITED PRIOR TO |
| | CLEANOUT AT THE UPSTREAM END OF THE KITCHEN FIXTURES. |
| | --RISER DIAGRAM SHOWS A SAN-47 RISER. THIS IS NOT |
| | SHOWN ON ANY FLOOR PLAN, NOR WAS THERE A RISER SAN-47 |
| | SUBMITTED. PLEASE CLARIFY.--THE SANITARY RISER |
| | DIAGRAM DOES NOT REFLECT THE FLOOR PLANS IN MANY AREAS. |
| | PLEASE RECHECK AND CORRELATE. SECTIONS 106.1.1, |
| | 106.2.1, 106.3.5.1.3, 604, 604.9, PDI-WH 201, TABLES |
| | 604.5, 604.10.1, 709.1, 710.1(1), 710.1(2), 905.3 & |
| | 905.4. |
| | |
| | 19C. SHT P509 RISER DIAGRAM OVERALL FIRST FLOOR WATER. |
| | ALL WATER HAMMER ARRESTORS SHALL BE LOCATED IN AN |
| | "EFFECTIVE RANGE",NOT IN THE CEILING AS SHOWN.-- |
| | RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN IN MANY |
| | AREAS AND RISERS DO NOT REFLECT THE FLOOR PLAN IN MANY |
| | AREA WHERE THE RISERS CONNECT TO THE WATER MAIN. PLEASE |
| | RECHECK THE ENTIRE RISER DIAGRAM PRIOR TO RESUBMITTING |
| | AS FAR AS RISER LOCATIONS AND RISER CONNECTIONS TO |
| | WATER MAIN.--RISER INDICATED HW/CW TO RISER 60, BUT |
| | RISER 60 ONLY HAS COLD WATER. CORRELATE.--RISERS |
| | 45, 46, 48, 49, 50 & 51 NOT SHOWN ON THE RISER DIAGRAM |
| | BUT ON THE FLOOR PLAN.--RISER 44 DOES NOT REFLECT |
| | THE FLOOR PLAN. SECTIONS 106.1.1, 106.1.2, PDI-WH 201, |
| | TABLES 604.5, 604.10.1. PDI-WH 201 & MANUF. |
| | INSTALLATION INSTRUCTIONS. |
| | |
| | 20C. SHT P510 STORM WATER RISER DIAGRAMS PLUMBING. |
| | PLEASE RECHECK TOTAL SQUARE FOOTAGE FOR RWL-7 AND PIPE |
| | SIZE DOWNSTREAM OF RWL-7.--CHECK THE PIPE SIZING |
| | DOWNSTREAM OF RD-1. SECTION 106.1.1 AND TABLE 1106.3. |
| | |
| | 21C. SHT P602 PLUMBING DETAILS. DETAIL NUMBER 1 DOES |
| | NOT COMPLY WITHTHE UTILITY STANDARD FOR GREASE |
| | INTERCEPTORS. PLEASE SEE ATTACHED SHEET. DETAIL |
| | INDICATES PREFAB TANKS. PLEASE SUBMIT MANUF. |
| | SPECIFICATIONS FOR GREASE INTERCEPTOR. ARTICLE III |
| | SECTION 90-124(7)(E)(F).--DETAIL 4 SHOWS A DOUBLE |
| | CHECK BACKFLOW PREVENTOR FOR THE DOMESTIC WATER |
| | BACKFLOW PREVENTOR. THIS IS NOT APPROVED. THE PROPER |
| | BACKFLOW PREVENTOR FOR THE DOMESTIC IS AN RPZV BACKFLOW |
| | PREVENTOR. SECTION 608.13.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | -PLEASE RESUBMIT ONE SET OF OLD SHEETS |
| | FOR COMPARISON. |
| | |
| | ********NO RESPONSE, NOT ADDRESSED |
| | |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |