Plan Review Notes
Plan Review Notes For Permit 06111071
Permit Number 06111071
Review Stop P
Sequence Number 4
Notes
Date Text
2008-03-01 17:41:10 
 DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2001 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS: 3RD REVIEW:
  
 ********FROM PREVIOUS REVIEWS: 4TH REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK (INFORMATIONAL ONLY)
  
 7. SHT AC104 POOL HOUSE PLAN. MENS TOILET ROOM REQUIRES
 A URINAL. PLEASE INDICATE ON PLANS. TABLE 424.1.6.1.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT NOW A TOILET STALL IS SHOWN
 IN THE TOILET ROOM. PER SECTION 11-4.17.3 EXCEPTION NEW
 CONTRUCTION AN ACCESSIBLE LAV IS REQUIRED IN THE STALL.
 (SEE THE EXCEPTION (1) TO SECTION 310.4 WHERE A STALL
 IS NOT REQUIRED).
 ********RESPONSE NOTED, BUT NEW STALL DOES NOT COMPLY
 WITH SECTION 11-4.17.3 EXCEPTION NEW CONSTRUCTION.
  
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
 15. OK
 16. OK
  
 17. SHT A-808 ELEVATION DETAIL 9. THE SINK SHALL BE
 ACCESSIBLE & SHALL COMPLY WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. PLEASE SHOW COMPLIANCE.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT COMPLIANCE NOT SHOWN FOR THE
 FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE
 D. 11-4.24.7 FAUCETS
 ********RESPONSE NOTED, BUT NO SINK DEPTH IS INDICATED,
 NO CLEAR FLOOR SPACE SHOWN ON THE FLOOR PLAN, NOR HAS
 THE FAUCET INFORMATION BEEN SUBMITTED.
  
 18. SHT A-809 ELEVATIONS 4 & 9. THE SINK SHALL COMPLY
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS. A FORWARD
 APPROACH CLEAR FLOOR SPACE IS REQUIRED AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE SINK. CABINET DOORS ARE
 NOT APPROVED IN THE CLEAR FLOORSPACE AND ARE NOT TO
 BE INSTALLED. SUBMIT A SIDE ELEVATION SHOWING THE
 GARBAGE DISPOSAL. INDICTE COMPLIANCE WITH FIGURE 11-31.
 THE GARBAGE DISPOSAL SHALL BE ADA APPROVED LOW PROFILE
 TYPE THAT DOES NOT ENTER THE REQUIRED CLEAR FLOOR SPACE
 OF THE SINK.SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT
 SHOWN AT THE SINK IN THE EMPLOYEE BREAKROOM, (126), AND
 IS SHOWN AS PARALLEL APPROACH ON DETAIL #2. ELEVATION
 #4 DOES NOT SHOW THE KNEE CLEARANCE REQUIRED BY SECTION
 11-4.24.3. ELEVATIONS #4 & #9 DO NOT SHOW THE SINK
 DEPTH REQUIRED BY SECTION 11-4.24.4. ELEVATION #4
 EXPOSED PIPES & SURFACES REQUIREMENT OF 11-4.24.6.
 ELEVATIONS #4 & #9 THE FAUCET REQUIREMENT OF
 11-4.24.7.
 ********RESPONSE NOTED, BUT NO SINK DETAIL SHOWN, NO
 CLEAR FLOOR SPACE SHOWN ON THE FLOOR PLAN.
  
 19. RESPONSE NOTED, NOT APPLICABLE
 20. OK.
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
 28. OK
 29. OK
 30. OK
 31. OK
 32. OK
 33. OK
  
 34. INDICATE A NUMBER DESIGNATION FOR EACH RISER
 INCLUDING ALL SANT., WATER, STORM, CONDENSATE. (EXAMPLE
 SANT-1, SANT-2, RWL-1, RWL-2, CON-1, CON-2, W-1, W-2
 ETC.). THIS WILL AID IN TRACKING ALL RISERS FROM THE
 UNDERGROUND PIPING THROUGH THE ROOF. SECTIONS
 106.3.5.1.3 & SECTION 106.1.1.--INDICATE WHICH
 RISER IS TYPICAL OF WHICH RISER ISOMETRIC DIAGRAM.
 (EXAMPLE SANT-1 SANT-4 TYPICAL OF DETALI 4 SHT P401) --
 INDICATE ROOM NUMBER EACH RISER CAN BE LOCATED.
 ****RESPONSE NOTED, BUT SHEET P503 HAS NOT BEEN
 SUBMITTED.
 ******RESPONSE NOTED, BUT RESPONSE DOES NOT ADDRESS THE
 WATER RISERS, STORM RISERS, OR CONDENSATE RISERS.
 ********RESPONSE NOTED, BUT THERE ARE STILL RISER
 DESIGNATIONS MISSING ON THE FIRST FLOOR.
  
 35. ROUTE PLANS TO THE DEPT. OF BUSINESS REGULATION,
 HOTEL & RESTURANT DIVISION FOR REVIEW PRIOR TO
 RESUBMITTING TO THE CITY FOR REVIEW. A MINIMUM OF TWO
 SETS OF PLANS, STAMPED BY DBPR AND TWO PAGE
 "WORKSHEETS" ATTACHED TO PLAN ARE REQUIRED. SECTION
 102.2.1.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE TWO PAGE SPECIFICATION
 WORKSHEETS FOR THE HOMEWOOD REVIEW ARE ATTACHED TO THE
 SPRINGHILL PLANS, AND THE WORKSHEETS FOR THE SPRINGHILL
 PLANS ARE ATTACHED TO THE HOMEWOOD PLANS. PLEASE INSERT
 THE CORRECT SPECIFICATION WORKSHEETS IN THE CORRECT
 PLANS.
 ********RESPONSE NOTED, BUT THE SPECIFICATION
 WORKSHEETS HAVE NOT BEEN FOUND THIS SUBMITTAL.
  
 36. OK
 37. OK
  
 *****NEW COMMENTS 3RD REVIEW*****
  
  
 1B. OK
  
 2B. SHT G-001 NOT ALL SHEETS SHOWN ON THE DRAWING INDEX
 HAVE BEEN SUBMITTED, AND SOME SHEETS ARE OUT OF ORDER.
 PLEASE CORRELATE THE SHEETS SUBMITTED WITH THE DRAWING
 INDEX. SECTION 106.1.1.
 ********RESPONSE NOTED, BUT ONE SET OF PLANS HAS TWO
 SHEETS P507 ONE SEAL DATED 12/18/07 AND THE OTHER
 SEALED 12/19/07. ALSO ONE SET IS MISSING SHTS P101C &
 P101D. PLEASE SUBMIT 3 SETS OF PLANS THAT HAVE ALL
 SHEETS PER DRAWING INDEX.
  
 3B. OK
 4B. OK
 5B. OK
 6B. OK
 7B. OK
  
 8B. SHT P101B THREE BRANCH CONNECTIONS ARE SHOWN
 CONNECTING AGAINST THE FLOW. THIS IS NOT APPROVED PER
 SECTION 706.3. PLEASE SHOW FITTING INSTALLATION SO THAT
 IS GUIDES THE SEWAGE AND WASTE IN THE DIRECTION OF
 FLOW.
 ********RESPONSE NOTED, BUT TWO BRANCH LINES ARE SHOWN
 CONNECTING AGAINST THE FLOW.
  
 9B. OK
 10B. OK
 11B. OK
 12B. OK
 13B. OK
 14B. OK
 15B. OK
 16B. OK
 17B. OK
 18B. OK
 19B. OK
 20B. OK
  
 21B. SHT P501 DETAIL/RISER #1 DOES NOT REFLECT THE
 FLOOR PLAN AT FIXTURES P6 & P8.--DETAIL /RISER #5
 DOES NOT REFLECT SHT P101A SAN #1 & INDICATES PASSING
 THRU THE 1ST FLOOR TWICE. PLEASE CLARIFY. SECTION
 106.1.1.--DETAIL/RISER 3 INDICATES GUEST
 LAUNDRY/MAINTENANCE. THIS IS NOT FOUND ON THE FLOOR
 PLAN. PLEASE CLARIFY.
 ********RESPONSE NOTED, BUT RISER DIAGRAM SAN-1 NOW
 SHOWS ACCESSIBLE SHOWER ON ALL FLOORS.
  
 22B. SHT P502 THE WATER RISER DIAGRAMS DO NOT REFLECT
 THE FLOOR PLANS. NOT ALL FLOOR PLANS ARE SHOWN. PLEASE
 SUBMIT RISERS TO REFLECT THE FLOOR PLAN AND SUBMIT A
 FLOOR PLAN FOR EACH UNIT TYPE. SECTION 106.3.5.1.3.
 ********RESPONSE NOTED, BUT THERE ARE STILL RISERS THAT
 DO NOT REFLECT THE FLOOR PLAN. SEE NEW COMMENTS.
  
 23B. OK
 24B. OK
 25B. OK
  
 **********NEW COMMENTS**********
  
 1C. SHT P101A FIRST FLOOR PLAN SANITARY WASTE & VENT
 PLAN. THERE IS NO PIPING TO SAN-1 RISER FROM THE
 BUILDING DRAIN.--THE FIRST FLOOR SHOWER TO SAN-1
 IS NOT INDICATED ON THE FLOOR PLAN.--THERE IS NO
 PIPING TO SAN-6 RISER FROM BUILDING DRAIN.--THERE
 IS NO PIPING TO SAN-11 RISER FROM THE BUILDING DRAIN.
 --THE SLOPE INDICATOR ON THE BUILDING DRAIN FROM
 SAN-16 RISER TO SAN-33 RISER IS OPPOSITE OF THE PIPING.
 --IDENTIFY THE RISER IN THE EXERCISE ROOM (118)AND
 THE RISER BY ELEVATOR #2.--FLOOR DRAINS ARE NOT
 APPROVED INDIRECT WASTE RECEPTORS. FLOOR SINKS OR HUB
 DRAIN ARE REQUIRED AND SHALL BE LOCATED SO THEY ARE NOT
 TRIPPING HAZARDS.--THE EMPLOYEE SINK ON THE FIRST
 FLOOR IS SHOWN CONNECTING IN THE CEILING OF THE FIRST
 FLOOR ON THE FLOOR PLAN NOT UNDERGROUND AS REQUIRED. --
 SHOW THE RISER DESIGNATIONS FOR SANITARY RISERS 85, 86,
 87 & 88 ON THE FLOOR PLAN SO THE RISERS CAN BE TRACKED
 FROM THE FIRST FLOOR UP.--SUBMIT SANITARY AND WATER
 RISER DIAGRAMS THAT REFLECT KEY NOTE NUMBER 11.
 SECTIONS 106.1.1, 106.3.5.1.3, 706.3, 802.3, 802.3.2,
 AND TABLES 710.1(1) & 710.1(2).
  
 2C. SHT P101B FIRST FLOOR PLAN SANITARY WASTE & VENT
 PLAN. THERE ARE FITTINGS THAT ARE INDICATED AS
 INSTALLED AGAINST THE FLOW.--THE SHOWER IS NOT
 SHOWN ON THE FLOOR PLAN IN THE ACCESSIBLE DOUBLE QUEEN
 UNIT (101) AS WELL AS A SANITARY RISER THAT DOES NOT
 INDICATE THE RISER NUMBER.--SECTIONS 106.1.1,
 706.3.
  
 3C. SHT P101C FIRST FLOOR PLAN DOMESTIC WATER & GAS.
 MANY WATER RISERS SHOW NO WATER LINES CONNECTING TO THE
 WATER MAIN. SHOW ALL PIPING ON THE FLOOR PLAN.--
 ACCESSIBLE STUDIO REFERS TO DETAIL 5, SHEET P401, BUT
 DETAIL 5 HAS NOT BEEN SUBMITTED.--THREE OTHER
 REFERENCES TO DETAIL 4, SHT P402, BUT THESE DETAILS ARE
 FOR SANITARY WASTE & VENT, NOT WATER INFORMATION.
 CLARIFY-- ACCESSIBLE STUDIO (125), SHOWER IS NOT
 SHOWN ON THE FLOOR PLAN.--RISER CW-92 IS NOT SHOWN
 ON THE FLOOR PLAN.--SHOW THE LOCATION OF RISERS 85,
 86 & 87 ON THE FLOOR PLAN SO THE RISERS CAN BE TRACKED.
 --FLOOR PLAN REFERENCES RISER CW-94, BUT NO CW-94 WAS
 SUBMITTED,--3" HOT WATER MAIN LINE HAS BEEN
 MISLABELED AS 3" COLD WATER. SECTIONS 106.1.1 106.1.2 &
 604.
  
 4C. SHT P101D FIRST FLOOR PLAN DOMESTIC WATER & GAS.
 SOME RISER DESIGNATIONS ARE NOT LEGIBLE.--SOME
 RISERS SHOW NO PIPING TO THE RISER--SHOWER NOT
 SHOWN ON THE FLOOR PLAN FOR THE ACCESSIBLE QUEEN (101).
 --RISER CW-104 NOT SUBMITTED.--BOTH HOT AND COLD
 WATER FOR CW-50 CONNECT TO THE HOT WATER MAIN. SECTIONS
 106.1.1, 106.1.2 & 607.4.
  
 5C. SHT P102 SECOND FLOOR PLUMBING. ACCESSIBLE STUDIO
 (225) IS INDICATED AS KING UNIT ON THE ARCHITECTURAL
 FLOOR PLAN. PLEASE CORRELATE.--RISER SAN-13 IS
 LABELED AS SAN-3. PLEASE CORRELATE.--NO RISERS
 INDICATED FOR THE SHOWER IN STUDIO 105 THRU 505.-- NO
 LAV SHOWN IN ACCESSIBLE QUEEN (201).--THE RISERS
 BEHIND WHERE THE LAV SHOULD BE IN THE ACCESSIBLE QUEEN
 ARE NOT SHOWN ON THE FIRST FLOOR, NOR ARE THEY SHOWN ON
 THE THIRD FLOOR. PLEASE CLARIFY. IDENTIFY RISERS.--
 INFORMATION AT THE RIGHT SIDE OF THE KEY NOTES IS NOT
 LEGIBLE.SECTIONS 106.1.1, 106.1.2.
  
 6C. SHT P103 THIRD TO FIFTH FLOOR PLUMBING. THE SHOWER
 IS NOT SHOWN ON THE FLOOR PLAN FOR SAN-1.--SANITARY
 RISER 71 IS NOT LEGIBLE.--NO LAV SHOWN ON THE FLOOR
 PLAN IN UNIT WITH SAN-46 & SAN-48. SECTIONS 106.1.1 &
 106.1.2.
  
 7C. SHT P104A ROOF PLAN PLUMBING. THE CALCULATIONS FOR
 ZONE 7 DO NOT COMPUTE. PLEASE RECHECK FIGURES. SECTION
 106.1.1 & TABLE 1106.3.
  
 8C. SHT P402 ACCESSIBLE STUDIO UNIT PLAN - WASTE &
 VENT. THE SHOWER IS NOT SHOWN ON THE FLOOR PLAN.
 SECTION 106.1.1.
  
 9C. SHT P403 PARTIAL PLAN KITCHEN - WASTE & VENT.
 IDENTIFY ROOM AND IDENTIFY WHAT DRAINS INTO THE FLOOR
 DRAIN. (KEY NOTE 10).--HORIZONTAL DRY VENT
 DOWNSTREAM OF THE CLEANOUT IS NOT APPROVED.--KEY
 NOTE 14 THE 2" HUB DRAIN IS NOT APPROVED FOR INDIRECT
 WASTE FOR THE DISHWASHER. A FLOOR SINK LARGE ENOUGH TO
 ACCEPT ALL THE PUMPING ACTION WITH A BASKET TO CATCH
 ANY OR ALL SOLIDS IS REQUIRED.--FLOOR DRAIN BY THE
 REF & FREEZER SHALL BE ACCESSIBLE AND NOT BE A TRIPPING
 HAZARD. EXPLAIN THE 1/2 GRATE. --PLUMBING KEY NOTES 3
 NOT FOUND. PLEASE CLAIFY. SECTIONS 106.1.1, 106.1.2,
 708.9. 802.3.2.
  
 10C. SHT P403 PARTIAL PLAN - WASTE & VENT. PIPING TO
 THE LAV IN THE WOMENS TOILET ROOM DOES NOT REFLECT THE
 RISER DIAGRAM. NO PIPING IS SHOWN TO THE LAV. SECTION
 106.1.1.
  
 11C. SHT P501 SANITARY RISER DIAGRAMS PLUMBING. EVERY
 VENT STACK SHALL CONNECT TO THE BASE OF THE DRAINAGE
 STACK. SECTION 903.4. SEE STACKS 3, 6, 12, 17, 23 & 30.
 --ALL SINK AND LAV RISERS SHOW TRAPS UNDER THE SLABS
 FOR THESE FIXTURES. PLEASE CLAIRFY. SECTIONS 106.1.1 &
 1002.1.--DETAIL 1 REFERENCES ACCESSIBLE STUDIO 2BD,
 1ST THRU 5TH FLOOR ONLY, BUT THE ARCHITECURAL SHEETS
 INDICATE THAT THE 2ND FLOOR IS A STANDARD STUDIO AND
 THE 3RD THRU 5TH FLOORS ARE ACCESSIBLE KINGS. PLEASE
 CORRELATE.--SAN-1 DOES NOT REFLECT THE FLOOR PLAN.
 ALL FLOORS INDICATE ACCESSIBLE SHOWERS, BUT THE FIRST
 FLOOR SHOWS AN ACCESSIBLE SHOWER, THE SECOND FLOOR
 SHOWS A STANDARD TUB, AND THIRD FLOOR THRU FIFTH FLOOR
 SHOWS ACCESSIBLE TUB. PLEASE CORRELATE.--SAN-2,
 SAN-3 & SAN-4 DO NOT REFLECT THE FLOOR PLAN BECAUSE OF
 THE SAME CONDITION OF CHANGING FLOOR PLANS BUT THE
 RISER SHOWS THE SAME FOR EACH FLOOR. CORRELATE.--
 SAN-22 DOES NOT REFLECT THE FLOOR PLAN.SECTION
 106.1.1.
  
 12C. SHT P502SANITARY RISER DIAGRAMS PLUMBING. EVERY
 VENT STACK SHALL CONNECT TO THE BASE OF THE DRAINAGE
 STACK. SECTION 903.4. SEE STACKS 37, 44, 46, 54 & 60.
 --ALL SINK AND LAV RISERS SHOW TRAPS UNDER THE SLABS
 FOR THESE FIXTURES. PLEASE CLAIRFY. SECTIONS 106.1.1 &
 1002.1.--DETAIL ONE SHOWS THE SECOND SAN-31 RISER
 SUBMITTED. THE RISER 31 ON THE PREVIOUS SHEET SHOWS
 SINKS, THE RISER 31 ON THIS SHEET SHOWS TUBS. PLEASE
 CLARIFY.--SAN-36 RISER DOES NOT REFLECT THE FLOOR
 PLAN.--SAN-48 DOES NOT REFLECT THE FLOOR PLAN AS IT
 INDICATES A SHOWER ON THE FIRST FLOOR THAT IS NOT SHOWN
 ON THE FLOOR PLAN, THEN CHANGES INTO W/C'S & TUBS FROM
 THE 3RD FLOOR TO THE 5TH FLOOR.--SAN-46 DOES NOT
 REFLECT THE FLOOR PLAN AS IT DOES NOT SHOW THE W/C ON
 THE FIRST FLOOR, DOES NOT SHOW THE OFFSET BETWEEN THE
 2ND AND 3RD FLOORS AND SHOWS LAVS ON THE 3RD THRU 5TH
 FLOORS.--SAN-48/SAN-46 SHOW NO VENT THRU ROOF.
 SECTIONS 106.1.1 & 903.3.
  
 13C. SHT P503 SANITARY RISER DIAGRAMS PLUMBING. EVERY
 VENT STACK SHALL CONNECT TO THE BASE OF THE DRAINAGE
 STACK. SECTION 903.4. SEE STACKS 66, 74, 77, 84, 91 &
 87.--ALL SINK AND LAV RISERS SHOW TRAPS UNDER THE
 SLABS FOR THESE FIXTURES. PLEASE CLAIRFY. SECTIONS
 106.1.1 & 1002.1.--RISER SAN-76 DOES NOT REFLECT
 THE FLOOR PLAN.--SAN-91 RISER DOES NOT REFLECT THE
 FLOOR PLAN.--SAN-90 RISER DIAGRAM DOES NOT REFLECT
 THE FLOOR PLAN.--SAN-89 RISER DOES NOT REFLECT THE
 FLOOR PLAN. SECTIONS 106.1.1 & 106.3.5.1.3.
  
 14C. SHT P504 HOT & COLD WATER RISER DIAGRAM PLUMBING.
 ALL RISERS DO NOT REFLECT THE FLOOR PLAN AS THEY SHOW
 PIPING UNDERGROUND TO EACH RISER BUT THE FLOOR PLAN
 SHOWS THE WATER IN THE CEILING FEEDING DOWN TO THE
 FIRST FLOOR AND UP TO THE 2ND, 3RD, 4TH & 5TH FLOORS.
 --CW-1/HW-1 DOES NOT REFLECT THE FLOOR PLAN AS IT
 SHOWS THE SUPPLY PIPING UNDERGROUND.--CW-4/HW-4
 DOES NOT REFLECT THE FLOOR PLAN.--NO WATER RISER
 FOR THE SHOWER IN THE STUDIO UNITS 113 THRU 513.
 SECTIONS 106.1.1 & 106.3.5.1.3.
  
 15C. SHT P505 HOT & COLD WATER RISER DIAGRAM PLUMBING.
 ALL RISERS DO NOT REFLECT THE FLOOR PLAN AS THEY SHOW
 PIPING UNDERGROUND TO EACH RISER BUT THE FLOOR PLAN
 SHOWS THE WATER IN THE CEILING FEEDING DOWN TO THE
 FIRST FLOOR AND UP TO THE 2ND, 3RD, 4TH & 5TH FLOORS.
 --NO RISER FOR THE SHOWER IN DETAIL 2/505.--
 CW-43/HW-43 RISER SHOWS THE SUPPLY PIPING UNDERGROUND.
 --CW-41/HW-41 RISER DOES NOT REFLECT THE FLOOR PLAN.
 --DETAIL 3/505 SHOWS TWO CW-43 RISERS. PLEASE
 CLARIFY.--DETAIL 4/505 DOES NOT SHOW A LAV RISER
 DIAGRAM.--CW-48/HW-48 RISER DOES NOT REFLECT THE
 FLOOR PLAN.--CW-45/HW-45 DOES NOT REFLECT THE FLOOR
 PLAN.--DETAIL 5/505 DOES NOT SHOW A WATER CLOSET
 RISER DIAGRAM.--CW-51/HW-51 RISER DOES NOT REFLECT
 THE FLOOR PLAN. SECTIONS 106.1.1 & 106.3.5.1.3.
  
 16C. SHT P506 HOT & COLD WATER RISER DIAGRAM PLUMBING.
 ALL RISERS DO NOT REFLECT THE FLOOR PLAN AS THEY SHOW
 PIPING UNDERGROUND TO EACH RISER BUT THE FLOOR PLAN
 SHOWS THE WATER IN THE CEILING FEEDING DOWN TO THE
 FIRST FLOOR AND UP TO THE 2ND, 3RD, 4TH & 5TH FLOORS.
 --DETAIL 1/506 CW-53/HW-53 SHOWS THE WATER SUPPLIES
 FOR THE SHOWER UNDER THE FIRST FLOOR SLAB.--DETAIL
 1/506 CW-56/HW-56 SHOWS NO SINK ON THE FIRST FLOOR.
 THIS DOES NOT REFLECT THE FLOOR PLAN.--DETAIL 2/506
 DOES NOT REFLECT THE FLOOR PLAN AS THERE IS NO RISER
 FOR THE SHOWERS IN UNITS 104 THRU 504.--DETAIL
 3/506 DOES NOT REFLECT THE FLOOR PLAN AS THERE IS NO
 RISER FOR THE TUBS IN UNITS 109 THRU 509. SECTIONS
 106.1.1 & 106.3.5.1.3.
  
 17C. SHT P507 HOT & COLD WATER RISER DIAGRAM PLUMBING.
 ALL RISERS DO NOT REFLECT THE FLOOR PLAN AS THEY SHOW
 PIPING UNDERGROUND TO EACH RISER BUT THE FLOOR PLAN
 SHOWS THE WATER IN THE CEILING FEEDING DOWN TO THE
 FIRST FLOOR AND UP TO THE 2ND, 3RD, 4TH & 5TH FLOORS.
 --DETAIL 3/507 RISERS CW-89/HW-89, CW-90/HW-90 &
 CW-91/HW-91 DO NOT REFLECT THE FLOOR PLANS.--DETAIL
 4/507 RISER CW-92 DOES NOT REFLECT THE FLOOR PLAN, NO
 ICE MACHINE SHOWN ON THE FLOOR PLAN.--DETAIL 5/507
 RISERS CW-95 THRU CW-101 AND CW-103 THRU CW-114 DO NOT
 REFLECT THE FLOOR PLAN. ICE MAKER SHOWN ON THE 1ST
 FLOOR FLOOR PLAN BUT NOT SHOWN ON THE RISER DIAGRAM. --
 CW-93 & CW-103 DOES NOT REFLECT THE FLOOR PLAN AS THE
 FLOOR PLANS SHOWS ICE MAKERS, WHERE AS THE RISER DOES
 NOT INDICATE 1ST FLOOR ICE MAKERS. --ALL ICE MAKER
 RISERS SHALL SHOW A WATER HAMMER ARRESTOR AT EACH ICE
 MAKER.--THERE IS NO RISER CW-102 SUBMITTED,TWO
 RISERS CW-98 SUBMITTED AND TWO RISERS 103 SUBMITTED.
 PLEASE CLARIFY. SECTIONS 106.1.1, 106.1.2 & 604.9.
  
 18C. SHT P508 RISER DIAGRAM OVERALL FIRST FLOOR
 SANITARY. FIXTURE P6 FOR EMPLOYEE BREAK ROOM SINK,
 PLEASE INDICATE WHERE IT CONNECTS TO THE BRANCH LINE.
 --BRANCH LINE FOR SAN-86 NOT SHOWN.--RISERS
 SAN-82 & SAN-83 ARE NOT REFLECTING THE CONNECTION ON
 THE FLOOR PLAN. --RISERS SAN-89, SAN-90 & SAN-91 ARE
 NOT SHOWN ON THE RISER DIAGRAM.--RISERS SAN-9,
 SAN-10 & SAN-11 ARE NOT SHOWN ON THE RISER DIAGRAM.--
 PIPING TO SAN-13 RISER DOES NOT REFLECT THE FLOOR PLAN.
 --SOME RISER LOCATIONS ON THE RISER DIAGRAM DO NOT
 REFLECT THE FLOOR PLAN. (EXAMPLES 14, 15, 77, 78)--
 SAN RISER TO WASH MACHINES DO NOT REFLECT THE FLOOR
 PLAN SHT P101A. (FOUR RISERS SHOWN).--SUBMIT A
 FLOOR PLAN WITH SANITARY AND WATERRISER DIAGRAMS FOR
 THE WASH MACHINES IN GUEST LAUNDRY ROOM 218. SHOW PIPE
 SIZE, TRAPS, CLEANOUTS, VENTING FOR THE SANITARY RISER,
 AND SHOW PIPE SIZE, VALVES, WATER HAMMER ARRESTORS ETC
 FOR THE WATER RISER DIAGRAM.--CLEANOUT MISSING
 UPSTREAM OF SAN-34 THAT IS SHOWN ON THE FLOOR PLAN.--
 SEVEN RISERS ALL SHOW RISER NUMBER SAN-34. THIS DOES
 NOT REFLECT THE FLOOR PLAN.--SAN-57 RISER DOES NOT
 REFLECT THE FLOOR PLAN AS IT DOES NOT SHOW A DOUBLE
 COMBO CONNECTION.--TWO SAN-48 RISER SHOWN ON THE
 RISER DIAGRAM. THAT DOES NOT REFLECT THE FLOOR PLAN. --
 FIRST FIXTURE, (FLOOR DRAIN), UPSTREAM OF TOILET ROOMS
 28 & 29 IS NOT SHOWN ON THE FLOOR PLAN SHT P101B. ALSO
 FIXTURE SHOWS A HORIZONTAL DRY VENT WHICH IS
 PROHIBITED.--FIRST FIXTURE, (FLOOR DRAIN). IN THE
 KITCHEN SHALL BE A FLOOR SINK, OR HUB DRAIN IF INDIRECT
 WASTE.--HORIZONTAL DRY VENT IS PROHIBITED PRIOR TO
 CLEANOUT AT THE UPSTREAM END OF THE KITCHEN FIXTURES.
 --RISER DIAGRAM SHOWS A SAN-47 RISER. THIS IS NOT
 SHOWN ON ANY FLOOR PLAN, NOR WAS THERE A RISER SAN-47
 SUBMITTED. PLEASE CLARIFY.--THE SANITARY RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLANS IN MANY AREAS.
 PLEASE RECHECK AND CORRELATE. SECTIONS 106.1.1,
 106.2.1, 106.3.5.1.3, 604, 604.9, PDI-WH 201, TABLES
 604.5, 604.10.1, 709.1, 710.1(1), 710.1(2), 905.3 &
 905.4.
  
 19C. SHT P509 RISER DIAGRAM OVERALL FIRST FLOOR WATER.
 ALL WATER HAMMER ARRESTORS SHALL BE LOCATED IN AN
 "EFFECTIVE RANGE",NOT IN THE CEILING AS SHOWN.--
 RISER DIAGRAM DOES NOT REFLECT THE FLOOR PLAN IN MANY
 AREAS AND RISERS DO NOT REFLECT THE FLOOR PLAN IN MANY
 AREA WHERE THE RISERS CONNECT TO THE WATER MAIN. PLEASE
 RECHECK THE ENTIRE RISER DIAGRAM PRIOR TO RESUBMITTING
 AS FAR AS RISER LOCATIONS AND RISER CONNECTIONS TO
 WATER MAIN.--RISER INDICATED HW/CW TO RISER 60, BUT
 RISER 60 ONLY HAS COLD WATER. CORRELATE.--RISERS
 45, 46, 48, 49, 50 & 51 NOT SHOWN ON THE RISER DIAGRAM
 BUT ON THE FLOOR PLAN.--RISER 44 DOES NOT REFLECT
 THE FLOOR PLAN. SECTIONS 106.1.1, 106.1.2, PDI-WH 201,
 TABLES 604.5, 604.10.1. PDI-WH 201 & MANUF.
 INSTALLATION INSTRUCTIONS.
  
 20C. SHT P510 STORM WATER RISER DIAGRAMS PLUMBING.
 PLEASE RECHECK TOTAL SQUARE FOOTAGE FOR RWL-7 AND PIPE
 SIZE DOWNSTREAM OF RWL-7.--CHECK THE PIPE SIZING
 DOWNSTREAM OF RD-1. SECTION 106.1.1 AND TABLE 1106.3.
  
 21C. SHT P602 PLUMBING DETAILS. DETAIL NUMBER 1 DOES
 NOT COMPLY WITHTHE UTILITY STANDARD FOR GREASE
 INTERCEPTORS. PLEASE SEE ATTACHED SHEET. DETAIL
 INDICATES PREFAB TANKS. PLEASE SUBMIT MANUF.
 SPECIFICATIONS FOR GREASE INTERCEPTOR. ARTICLE III
 SECTION 90-124(7)(E)(F).--DETAIL 4 SHOWS A DOUBLE
 CHECK BACKFLOW PREVENTOR FOR THE DOMESTIC WATER
 BACKFLOW PREVENTOR. THIS IS NOT APPROVED. THE PROPER
 BACKFLOW PREVENTOR FOR THE DOMESTIC IS AN RPZV BACKFLOW
 PREVENTOR. SECTION 608.13.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 -PLEASE RESUBMIT ONE SET OF OLD SHEETS
 FOR COMPARISON.
  
 ********NO RESPONSE, NOT ADDRESSED
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  