| 2008-03-03 11:40:24 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | ******FROM PREVIOUS REVIEW: 3RD REVIEW: |
| | |
| | ********FROM PREVIOUS REVIEWS: 4TH REVIEW: |
| | |
| | A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS |
| | PERMIT. PLEASE SUBMIT THE FOLLOWING: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ****RESPONSE NOTED, BUT NOT ALL SECTIONS OF PIPES SHOW |
| | THE LENGTH.--ALSO THE ISOMETRIC RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN PRIOR TO AND AT THE TOP OF |
| | THE RISER TO THE APPLIANCE THAT INDICATES 150 CFH.-- |
| | PLEASE IDENTIFY ALL GAS APPLIANCES ON THE RISER |
| | DIAGRAM. (ONLY GAS GRILLS INDICATED).--SOLENOID |
| | VALVES IN THE CEILING ARE NOT REQUIRED. PLEASE DELETE. |
| | --UPSTREAM OF THE 4 WATER (200CFH) IS INDICATED AS |
| | 600CFH. THIS SHOULD BE 800CFH. |
| | ******RESPONSE NOTED, BUT THE LENGHT OF PIPE TO THE |
| | FIREPLACE IS NOT SHOWN.--IF THE SOLENOID VALVES ARE |
| | TO REMAIN, THEN A SHUT OFF VALVE SHALL BE INSTALLED |
| | WITH A UNION TO SERVICE THE SOLENOID VAVLES. THE VALVES |
| | AND UNION SHALL BE INSTALLED BELOW THE CEILING. |
| | ********RESPONSE NOTED FOR THE LENGHT OF PIPE TO THE |
| | FIREPLACE, BUT NO RESPONSE FOR THE SOLENOID VALVES. |
| | COMMENT NOT ADDRESSED. SECTION 409.4. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. ****RESPONSE |
| | NOTED, BUT SPECIFICATIONS HAVE NOT BEEN LOCATED, PLEASE |
| | INDICATE WHERE THE SPECIFICATIONS CAN BE FOUND, OR |
| | INDICATE THE INFORMATION AT THE GAS RISER DIAGRAM. |
| | ******RESPONSE NOTED, IS THE GAS LINE TO THE SAME |
| | MATERIAL? INDICATE SLEEVE SIZE AND MATERIAL & INDICATE |
| | WHERE THE SLEEVE WILL BE VENTED. SUBMIT A DETAIL FOR |
| | THE SLEEVE. |
| | ********RESPONSE NOTED, BUT PIPE SIZING IS INCORRECT IN |
| | MANY PIPE SECTIONS. 2" IS REQUIRED FOR 600 CFH, 1-1/2" |
| | IS REQUIRED FOR 300 CFH, 1-1/4" IS REQUIRED FOR 200 |
| | CFH, 2-1/2" IS REQUIRED FOR 800 CFH, 2" IS REQUIRED FOR |
| | 400 CFH, 1-1/4" IS REQUIRED FOR 150 CFH, 1" IS REQUIRED |
| | FOR 80 CFH.--ALSO 30 CFH IS INDICATED DOWNSTREAM OF |
| | THE SECOND BBQ GRILL.--ALL SHUTOFF VALVES SHALL BE |
| | THE SAME SIZE AS THE PIPE REQUIRED FOR EACH GAS |
| | APPLIANCE. |
| | |
| | 3. OK,NATURAL. |
| | 4. OK |
| | |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A-USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ****RESPONSE NOTED, BUT WILL NOT BE ABLE TO VERIFY |
| | UNTIL ALL CUT SECTIONS INDICATE THE LENGTH. (SEE |
| | COMMENT 31). |
| | ******RESPONSE NOTED, BUT THE TOTAL DEVELOPED LENGTH |
| | DOES NOT INCLUDE THE LENGHT OF PIPE TO THE FIREPLACE. |
| | ********RESPONSE NOTED, BUT THE NOTE BY THE METER |
| | INDICATES 235 FT, THE NOTE BELOW DETAIL #1 INDICATES |
| | 252FT, BUT ADDING UP THE CUT LENGTHS IN ADDS UP TO |
| | 255FT. PLEASE CORRELATE. |
| | |
| | 6. OK |
| | 7. IOK |
| | 8. OK |
| | |
| | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED,BUT THE MANUF. SHEETS WILL BE |
| | REQUIRED TO VERIFY CFH & LISTING. PLEASE INDICATE IF |
| | THE GAS INFORMATION WILL BE SUBMITTED AT THE TIME OF |
| | GAS PERMIT APPLICATION. IF SO ALL GAS APPROVAL WILL BE |
| | WITHELD UNTIL THEN. |
| | ******RESPONSE NOTED, BUT ALL MANUF. SPECIFICATION |
| | SHEETS SHALL BE SUBMITTED PRIOR TO ISSUING THE GAS |
| | PERMIT. IT WAS INDICATED THAT THE SHEETS WOULD BE |
| | SUBMITTED AT THE MEETING HELD IN CITY HALL 7-19-07. |
| | ********RESPONSE NOTED, BUT THE POOL HEATERS DO NOT |
| | SHOW A LISTING AND THE BTU LOADS INDICATED DO NOT |
| | REFLECT THE BTU'S INDICATED ON THE RISER DIAGRAM. |
| | (INDICATE MODEL NUMBERS).--NO MANUF SHEETS WERE |
| | SUBMITTED FOR THE FIREPLACE NOR FOR THE BBQ GRILLS. |
| | |
| | 10. N/A |
| | 11. N/A |
| | |
| | ***********NEW COMMENT********** |
| | |
| | 1B. OK |
| | |
| | **********NEW COMMENT |
| | |
| | 1C. SHT P511 UNDERGROUND PIPING SHALL COMPLY WITH |
| | SECTION 404.8. INDICATE METHOD. |
| | |
| | 2C. SHT P511 GAS PIPING SHALL COMPLY WITH SECTION 408.4 |
| | SEDIMENT TRAPS. PLEASE INDICATE ON PLANS. |
| | |