Plan Review Notes
Plan Review Notes For Permit 06111071
Permit Number 06111071
Review Stop G
Sequence Number 4
Notes
Date Text
2008-03-03 11:40:24DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEW: 3RD REVIEW:
  
 ********FROM PREVIOUS REVIEWS: 4TH REVIEW:
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS
 PERMIT. PLEASE SUBMIT THE FOLLOWING:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT NOT ALL SECTIONS OF PIPES SHOW
 THE LENGTH.--ALSO THE ISOMETRIC RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN PRIOR TO AND AT THE TOP OF
 THE RISER TO THE APPLIANCE THAT INDICATES 150 CFH.--
 PLEASE IDENTIFY ALL GAS APPLIANCES ON THE RISER
 DIAGRAM. (ONLY GAS GRILLS INDICATED).--SOLENOID
 VALVES IN THE CEILING ARE NOT REQUIRED. PLEASE DELETE.
 --UPSTREAM OF THE 4 WATER (200CFH) IS INDICATED AS
 600CFH. THIS SHOULD BE 800CFH.
 ******RESPONSE NOTED, BUT THE LENGHT OF PIPE TO THE
 FIREPLACE IS NOT SHOWN.--IF THE SOLENOID VALVES ARE
 TO REMAIN, THEN A SHUT OFF VALVE SHALL BE INSTALLED
 WITH A UNION TO SERVICE THE SOLENOID VAVLES. THE VALVES
 AND UNION SHALL BE INSTALLED BELOW THE CEILING.
 ********RESPONSE NOTED FOR THE LENGHT OF PIPE TO THE
 FIREPLACE, BUT NO RESPONSE FOR THE SOLENOID VALVES.
 COMMENT NOT ADDRESSED. SECTION 409.4.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. ****RESPONSE
 NOTED, BUT SPECIFICATIONS HAVE NOT BEEN LOCATED, PLEASE
 INDICATE WHERE THE SPECIFICATIONS CAN BE FOUND, OR
 INDICATE THE INFORMATION AT THE GAS RISER DIAGRAM.
 ******RESPONSE NOTED, IS THE GAS LINE TO THE SAME
 MATERIAL? INDICATE SLEEVE SIZE AND MATERIAL & INDICATE
 WHERE THE SLEEVE WILL BE VENTED. SUBMIT A DETAIL FOR
 THE SLEEVE.
 ********RESPONSE NOTED, BUT PIPE SIZING IS INCORRECT IN
 MANY PIPE SECTIONS. 2" IS REQUIRED FOR 600 CFH, 1-1/2"
 IS REQUIRED FOR 300 CFH, 1-1/4" IS REQUIRED FOR 200
 CFH, 2-1/2" IS REQUIRED FOR 800 CFH, 2" IS REQUIRED FOR
 400 CFH, 1-1/4" IS REQUIRED FOR 150 CFH, 1" IS REQUIRED
 FOR 80 CFH.--ALSO 30 CFH IS INDICATED DOWNSTREAM OF
 THE SECOND BBQ GRILL.--ALL SHUTOFF VALVES SHALL BE
 THE SAME SIZE AS THE PIPE REQUIRED FOR EACH GAS
 APPLIANCE.
  
 3. OK,NATURAL.
 4. OK
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A-USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT WILL NOT BE ABLE TO VERIFY
 UNTIL ALL CUT SECTIONS INDICATE THE LENGTH. (SEE
 COMMENT 31).
 ******RESPONSE NOTED, BUT THE TOTAL DEVELOPED LENGTH
 DOES NOT INCLUDE THE LENGHT OF PIPE TO THE FIREPLACE.
 ********RESPONSE NOTED, BUT THE NOTE BY THE METER
 INDICATES 235 FT, THE NOTE BELOW DETAIL #1 INDICATES
 252FT, BUT ADDING UP THE CUT LENGTHS IN ADDS UP TO
 255FT. PLEASE CORRELATE.
  
 6. OK
 7. IOK
 8. OK
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED,BUT THE MANUF. SHEETS WILL BE
 REQUIRED TO VERIFY CFH & LISTING. PLEASE INDICATE IF
 THE GAS INFORMATION WILL BE SUBMITTED AT THE TIME OF
 GAS PERMIT APPLICATION. IF SO ALL GAS APPROVAL WILL BE
 WITHELD UNTIL THEN.
 ******RESPONSE NOTED, BUT ALL MANUF. SPECIFICATION
 SHEETS SHALL BE SUBMITTED PRIOR TO ISSUING THE GAS
 PERMIT. IT WAS INDICATED THAT THE SHEETS WOULD BE
 SUBMITTED AT THE MEETING HELD IN CITY HALL 7-19-07.
 ********RESPONSE NOTED, BUT THE POOL HEATERS DO NOT
 SHOW A LISTING AND THE BTU LOADS INDICATED DO NOT
 REFLECT THE BTU'S INDICATED ON THE RISER DIAGRAM.
 (INDICATE MODEL NUMBERS).--NO MANUF SHEETS WERE
 SUBMITTED FOR THE FIREPLACE NOR FOR THE BBQ GRILLS.
  
 10. N/A
 11. N/A
  
 ***********NEW COMMENT**********
  
 1B. OK
  
 **********NEW COMMENT
  
 1C. SHT P511 UNDERGROUND PIPING SHALL COMPLY WITH
 SECTION 404.8. INDICATE METHOD.
  
 2C. SHT P511 GAS PIPING SHALL COMPLY WITH SECTION 408.4
 SEDIMENT TRAPS. PLEASE INDICATE ON PLANS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved