2007-10-02 08:42:19CONSTRUCTION SERVICES DEPARTMENT
 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH,
 FLORIDA33401
 TEL:561-805-6713FAX:
 561-805-6731
  
 JAMES JOHNSTON, PERMIT NO 06111071 BUILDING
 PLAN EXAMINERII PROJECT HOMEWOOD
 SUITES HILTON
 E-MAIL:JJOHNSTON @WPB.ORG ADDRESS
 2455 METROCENTREBOULEVARD DATE SEPTEMBER
 27, 2007
  
 STRUCTURALPLANREVIEW
  
  
  
 SOILREPORT
 THE SOILS AND BEARING CAPACITY LISTED IN THE REPORT
 FURNISHED BY MATEC APPEARED TO BE IN CONFLICT WITH THE
 FBC SECTION 1804 (SEE TABLE) SANDY SOILS. ANY
 INFORMATION PROVIDED REFERENCING THIS COMMENT WOULD BE
 APPRECIATED. PLEASE NOTE UPON SOIL PREPARATION AND
 COMPLETION A REPORT OF THE ACTUAL BEARING CAPACITY (IN
 SEVERAL AREAS) SHALL BE SUBMITTED FOR REVIEW PRIOR TO
 CONCRETE PLACEMENT IN THE FOUNDATION.THE MATEC REPORT
 STATES THE GUIDELINES FOR ACHIEVING THE BEARING
 CAPACITY AS A SUGGESTION.THE COMPLETION REPORT WILL
 ALLEVIATE ANY CONCERNS AND SUBSTANTIATE THAT THE
 CAPACITY HAS BEEN ACHIEVED.
  
 14B FIRE SPRINKLER PLANS NOT INCLUDED WITH THIS
 RESUBMIT AS REQUESTED
  
  
 FLORIDA ADMINISTRATIVE CODE CHAPTER 61G15-23.001 SEALS
 ACCEPTABLE TO THE BOARD
 ARCHITECT AND ENGINEER SEALS ARE TO BE A MINIMUM OF 2?
 COMMENT-ARCHITECT SEAL IS NOT IN COMPLIANCE WITH THIS
 RULE
  
 ADDITIONAL PERMITS
 SEPARATE PERMITS SHALL BE REQUIRED FOR POOL, POOL
 BUILDING, FENCING, SIGNAGE
  
 STAIRWAY OCCUPANT DISCHARGE
  
 A-1 1008.1.8.1 HARDWARE.
 DOOR HANDLES, PULLS, LATCHES, LOCKS AND OTHER OPERATING
 DEVICES ON DOORS REQUIRED TO BE ACCESSIBLE BY CHAPTER
 11 SHALL NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR
 TWISTING OF THE WRIST TO OPERATE.
 COMMENT-IDENTIFY HARDWARE FOR EACH DOOR ON DOOR
 SCHEDULE SHEET A603
 IDENTIFY ALL STAIRWAY DOORS AT EACH FLOOR ON DOOR
 SCHEDULE AND APPROPRIATE EXIT ACCESS REQUIRED HARDWARE
  
  
 A-2 1008.1.8 DOOR OPERATIONS.
 EXCEPT AS SPECIFICALLY PERMITTED BY THIS SECTION EGRESS
 DOORS SHALL BE READILY OPERABLE FROM THE EGRESS SIDE
 WITHOUT THE USE OF A KEY OR SPECIAL KNOWLEDGE OR
 EFFORT.
 COMMENT-FOR YOUR INFORMATION
  
 A-3 1019.1.7 STAIRWAY FLOOR NUMBER SIGNS.
 A SIGN SHALL BE PROVIDED AT EACH FLOOR LANDING IN
 INTERIOR VERTICAL EXIT ENCLOSURES CONNECTING MORE THAN
 THREE STORIES DESIGNATING THE FLOOR LEVEL, THE TERMINUS
 OF THE TOP AND BOTTOM OF THE STAIR ENCLOSURE AND THE
 IDENTIFICATION OF THE STAIR. THE SIGNAGE SHALL ALSO
 STATE THE STORY OF, AND THE DIRECTION TO THE EXIT
 DISCHARGE AND THE AVAILABILITY OF ROOF ACCESS FROM THE
 STAIRWAY FOR THE FIRE DEPARTMENT. THE SIGN SHALL BE
 LOCATED 5 FEET (1524 MM) ABOVE THE FLOOR LANDING IN A
 POSITION WHICH IS READILY VISIBLE WHEN THE DOORS ARE IN
 THE OPEN AND CLOSED POSITIONS.
 PLEASE APPLY THIS CODE SECTION WHEN DESCRIBING HARDWARE
 FOR EMERGENCY DOORS ON DOOR SCHEDULE COMMENT-PLEASE
 DETAIL ONTHE PLAN SHEETS THAT ARE APPLICABLE
  
 ELEVATOR
 B-1 3002.4 ELEVATOR CAR TO ACCOMMODATE AMBULANCE
 STRETCHER.
 SHALL BE IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR
 EMERGENCY MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL
 SHALL NOT BE LESS THAN 3 INCHES (76 MM) HIGH AND SHALL
 BE PLACED INSIDE ON BOTH SIDES OF THE HOISTWAY DOOR
 FRAME.
 COMMENT-PLEASE SHOW DETAIL AND LOCATION ON PLANS.
  
 B-2 3003.2 FIRE-FIGHTERS? EMERGENCY OPERATION.
 ELEVATORS SHALL BE PROVIDED WITH PHASE I EMERGENCY
 RECALL OPERATION AND PHASE II EMERGENCY IN-CAR
 OPERATION IN ACCORDANCE WITH ASME A17.1.
 COMMENT -PLEASE NOTE ON PLANS
  
 C-1 ROOFINGSHEETA-106
 STATE ON PLAN ?THIS ROOFING SYSTEM MUST BE INSTALLED BY
 A CARLISLE AUTHORIZED ROOFING APPLICATOR IN COMPLIANCE
 WITH SHOP DRAWINGSAPPROVED BY CARLISLE?AS PER
 SECTION 1.02?CARLISLE QUALITY ASSURANCE?
  
 C-2 S-309ROOF DECK
 AS SPECIFIED IN CARLISLE PRODUCT INFORMATION PART 1,
 103 (B) MUST BE MINIMUM OF 22 GA. STEEL. PLEASE SPECIFY
 THIS ON DETAILS LOCATED ON SHEET S-309
  
  
 D-1 UL ASSEMBLIES
 COMMENT -DETAIL ALL UL ASSEMBLIES ON PLAN SHEETS WHERE
 APPLICABLE FOR PLAN REVIEW ANDFIELD INSPECTOR?S USE.
  
 FBC 1807.1 WATERPROOFING - ELEVATOR PIT
 WALLS OR PORTIONS THEREOF THAT RETAIN EARTH AND ENCLOSE
 INTERIOR SPACES AND FLOORS BELOW GRADE SHALL BE
 WATERPROOFED AND DAMP PROOFED IN ACCORDANCE WITH THIS
 SECTION, WITH THE EXCEPTION OF THOSE SPACES CONTAINING
 GROUPS OTHER THAN RESIDENTIAL AND INSTITUTIONAL WHERE
 SUCH OMISSION IS NOT DETRIMENTAL TO THE BUILDING OR
 OCCUPANCY.
 COMMENT-THIS APPLIES TO THE ELEVATOR PIT. PLEASE NOTE
 ON PLANSHEETA-702