| 2007-10-02 08:42:19 | CONSTRUCTION SERVICES DEPARTMENT |
| | 200 SECOND STREET, 3RD FLOOR, WEST PALM BEACH, |
| | FLORIDA33401 |
| | TEL:561-805-6713FAX: |
| | 561-805-6731 |
| | |
| | JAMES JOHNSTON, PERMIT NO 06111071 BUILDING |
| | PLAN EXAMINERII PROJECT HOMEWOOD |
| | SUITES HILTON |
| | E-MAIL:JJOHNSTON @WPB.ORG ADDRESS |
| | 2455 METROCENTREBOULEVARD DATE SEPTEMBER |
| | 27, 2007 |
| | |
| | STRUCTURALPLANREVIEW |
| | |
| | |
| | |
| | SOILREPORT |
| | THE SOILS AND BEARING CAPACITY LISTED IN THE REPORT |
| | FURNISHED BY MATEC APPEARED TO BE IN CONFLICT WITH THE |
| | FBC SECTION 1804 (SEE TABLE) SANDY SOILS. ANY |
| | INFORMATION PROVIDED REFERENCING THIS COMMENT WOULD BE |
| | APPRECIATED. PLEASE NOTE UPON SOIL PREPARATION AND |
| | COMPLETION A REPORT OF THE ACTUAL BEARING CAPACITY (IN |
| | SEVERAL AREAS) SHALL BE SUBMITTED FOR REVIEW PRIOR TO |
| | CONCRETE PLACEMENT IN THE FOUNDATION.THE MATEC REPORT |
| | STATES THE GUIDELINES FOR ACHIEVING THE BEARING |
| | CAPACITY AS A SUGGESTION.THE COMPLETION REPORT WILL |
| | ALLEVIATE ANY CONCERNS AND SUBSTANTIATE THAT THE |
| | CAPACITY HAS BEEN ACHIEVED. |
| | |
| | 14B FIRE SPRINKLER PLANS NOT INCLUDED WITH THIS |
| | RESUBMIT AS REQUESTED |
| | |
| | |
| | FLORIDA ADMINISTRATIVE CODE CHAPTER 61G15-23.001 SEALS |
| | ACCEPTABLE TO THE BOARD |
| | ARCHITECT AND ENGINEER SEALS ARE TO BE A MINIMUM OF 2? |
| | COMMENT-ARCHITECT SEAL IS NOT IN COMPLIANCE WITH THIS |
| | RULE |
| | |
| | ADDITIONAL PERMITS |
| | SEPARATE PERMITS SHALL BE REQUIRED FOR POOL, POOL |
| | BUILDING, FENCING, SIGNAGE |
| | |
| | STAIRWAY OCCUPANT DISCHARGE |
| | |
| | A-1 1008.1.8.1 HARDWARE. |
| | DOOR HANDLES, PULLS, LATCHES, LOCKS AND OTHER OPERATING |
| | DEVICES ON DOORS REQUIRED TO BE ACCESSIBLE BY CHAPTER |
| | 11 SHALL NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR |
| | TWISTING OF THE WRIST TO OPERATE. |
| | COMMENT-IDENTIFY HARDWARE FOR EACH DOOR ON DOOR |
| | SCHEDULE SHEET A603 |
| | IDENTIFY ALL STAIRWAY DOORS AT EACH FLOOR ON DOOR |
| | SCHEDULE AND APPROPRIATE EXIT ACCESS REQUIRED HARDWARE |
| | |
| | |
| | A-2 1008.1.8 DOOR OPERATIONS. |
| | EXCEPT AS SPECIFICALLY PERMITTED BY THIS SECTION EGRESS |
| | DOORS SHALL BE READILY OPERABLE FROM THE EGRESS SIDE |
| | WITHOUT THE USE OF A KEY OR SPECIAL KNOWLEDGE OR |
| | EFFORT. |
| | COMMENT-FOR YOUR INFORMATION |
| | |
| | A-3 1019.1.7 STAIRWAY FLOOR NUMBER SIGNS. |
| | A SIGN SHALL BE PROVIDED AT EACH FLOOR LANDING IN |
| | INTERIOR VERTICAL EXIT ENCLOSURES CONNECTING MORE THAN |
| | THREE STORIES DESIGNATING THE FLOOR LEVEL, THE TERMINUS |
| | OF THE TOP AND BOTTOM OF THE STAIR ENCLOSURE AND THE |
| | IDENTIFICATION OF THE STAIR. THE SIGNAGE SHALL ALSO |
| | STATE THE STORY OF, AND THE DIRECTION TO THE EXIT |
| | DISCHARGE AND THE AVAILABILITY OF ROOF ACCESS FROM THE |
| | STAIRWAY FOR THE FIRE DEPARTMENT. THE SIGN SHALL BE |
| | LOCATED 5 FEET (1524 MM) ABOVE THE FLOOR LANDING IN A |
| | POSITION WHICH IS READILY VISIBLE WHEN THE DOORS ARE IN |
| | THE OPEN AND CLOSED POSITIONS. |
| | PLEASE APPLY THIS CODE SECTION WHEN DESCRIBING HARDWARE |
| | FOR EMERGENCY DOORS ON DOOR SCHEDULE COMMENT-PLEASE |
| | DETAIL ONTHE PLAN SHEETS THAT ARE APPLICABLE |
| | |
| | ELEVATOR |
| | B-1 3002.4 ELEVATOR CAR TO ACCOMMODATE AMBULANCE |
| | STRETCHER. |
| | SHALL BE IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR |
| | EMERGENCY MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL |
| | SHALL NOT BE LESS THAN 3 INCHES (76 MM) HIGH AND SHALL |
| | BE PLACED INSIDE ON BOTH SIDES OF THE HOISTWAY DOOR |
| | FRAME. |
| | COMMENT-PLEASE SHOW DETAIL AND LOCATION ON PLANS. |
| | |
| | B-2 3003.2 FIRE-FIGHTERS? EMERGENCY OPERATION. |
| | ELEVATORS SHALL BE PROVIDED WITH PHASE I EMERGENCY |
| | RECALL OPERATION AND PHASE II EMERGENCY IN-CAR |
| | OPERATION IN ACCORDANCE WITH ASME A17.1. |
| | COMMENT -PLEASE NOTE ON PLANS |
| | |
| | C-1 ROOFINGSHEETA-106 |
| | STATE ON PLAN ?THIS ROOFING SYSTEM MUST BE INSTALLED BY |
| | A CARLISLE AUTHORIZED ROOFING APPLICATOR IN COMPLIANCE |
| | WITH SHOP DRAWINGSAPPROVED BY CARLISLE?AS PER |
| | SECTION 1.02?CARLISLE QUALITY ASSURANCE? |
| | |
| | C-2 S-309ROOF DECK |
| | AS SPECIFIED IN CARLISLE PRODUCT INFORMATION PART 1, |
| | 103 (B) MUST BE MINIMUM OF 22 GA. STEEL. PLEASE SPECIFY |
| | THIS ON DETAILS LOCATED ON SHEET S-309 |
| | |
| | |
| | D-1 UL ASSEMBLIES |
| | COMMENT -DETAIL ALL UL ASSEMBLIES ON PLAN SHEETS WHERE |
| | APPLICABLE FOR PLAN REVIEW ANDFIELD INSPECTOR?S USE. |
| | |
| | FBC 1807.1 WATERPROOFING - ELEVATOR PIT |
| | WALLS OR PORTIONS THEREOF THAT RETAIN EARTH AND ENCLOSE |
| | INTERIOR SPACES AND FLOORS BELOW GRADE SHALL BE |
| | WATERPROOFED AND DAMP PROOFED IN ACCORDANCE WITH THIS |
| | SECTION, WITH THE EXCEPTION OF THOSE SPACES CONTAINING |
| | GROUPS OTHER THAN RESIDENTIAL AND INSTITUTIONAL WHERE |
| | SUCH OMISSION IS NOT DETRIMENTAL TO THE BUILDING OR |
| | OCCUPANCY. |
| | COMMENT-THIS APPLIES TO THE ELEVATOR PIT. PLEASE NOTE |
| | ON PLANSHEETA-702 |