Plan Review Notes
Plan Review Notes For Permit 06111071
Permit Number 06111071
Review Stop P
Sequence Number 3
Notes
Date Text
2007-11-19 18:56:55 
 DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2001 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS: 3RD REVIEW:
  
 1. OK
  
 2. SHTS G-000 THRU G-003 THE FIRM LICENSE NUMBER AND
 THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT ARE
 REQUIRED ON EACH SHEET. FAC 61G1-16.004(2)(6) & FS
 481.219, 481.2055.-THE EMBOSSED SEAL SHALL IMPRESS
 ALL INFORMATION REQUIRED BY FAC G1G1-16.002 & FS
 481.2055. NOT ALL INFORMATION REQUIRED IS IMPRESSED ON
 EACH SHEET. PLEASE MAKE SURE THE REQUIRED INFORMATION
 IS IN THE TITLE BLOCK AND RESEAL THE PLANS MAKING SURE
 ALL INFORMATION IS IMPRESSED & LEGIBLE WHEN SEALING THE
 PLANS.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE TITLE BLOCK STILL
 INDICATES PFVS ARCHITECTS. ALL REFERENCE TO THE
 ARCHITECTURAL COMPANY SHALL BE DELETED FROM THE TITLE
 BLOCK OR A FIRM LICENSE NUMBER, (CERTIFICATE OF
 AUTHORIZATION), WILL BE REQUIRED.--ALSO THE SEAL
 BEING USED IS NOT APPROVED. PER FAC 61G1-16.002 THE
 SEAL SHALL BE APPROX. 2" IN DIAMETER. FS 481.2055.
  
 3. ALL ARCHITECTURAL SHEETS THE TITLE BLOCK SHALL
 INDICATE THE FIRM LICENSE NUMBER,AND THE PRINTED NAME
 OF THE PERSON SEALING THE DOCUMENT. FAC
 61G1-16.004(2)(6) & FS 481.219, 481.2055.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT PVFS ARCHITECTS IS STILL
 INDICATED IN THE TITLE BLOCK OF EACH SHEET. ALL
 REFERENCE TO THE ARCHITECTURAL COMPANY SHALL BE DELETED
 FROM THE TITLE BLOCK OR A FIRM LICENSE NUMBER,
 (CERTIFICATE OF AUTHORIZATION), WILL BE REQUIRED.--
 ALSO THE SEAL BEING USED IS NOT APPROVED. PER FAC
 61G1-16.002 THE SEAL SHALL BE APPROX. 2" IN DIAMETER.
 FS 481.2055.
  
 4.SHTS SP-1, LP-1, LP-2 & LP-3. THE ADDRESS OF THE
 LANDSCAPE ARCHITECT DOES NOT REFLECT THE ADDRESS
 INDICATED ON THE DBPR WEBSITE. (SEE ATTACHED SHEET FROM
 THE STATE WEBSITE). PLEASE SHOW CORRECT ADDRESS IN THE
 TITLE BLOCK OR UPDATE THE ADDRESS WITH THE STATE DBPR
 WEBSITE. FAC 61G1-16.004(1) & FS 481.2055. ****RESPONSE
 NOTED, BUT NOT ALL INFORMATION REQUIRED FOR THE SEAL
 HAS BEEN IMPRESSED ON EACH SHEET. NOT ALL INFORMATION
 IS LEGIBLE.
 ******RESPONSE NOTED. THE SHEETS HAVE BEEN DELETED BUT
 ARE STILL SHOWN IN THE INDEX OF DRAWINGS ON SHT G-001.
 PLEASE CORRELATE THE DRAWING INDEX WITH THE SHEETS
 SUBMITTED.
  
 5. ALL STRUCTURAL SHEETS. THE ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON
 EACH SHEET. IF PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME & LICENSE NUMBER, AS WELL AS, THE NAME,
 ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS ON EACH SHEET. FAC 61G15-23.002(2)
 & FS 471.025. THE BUSINESS NUMBER, (CERTIFICATE OF
 AUTHORIZATION), FOR PFVS ARCHITECTURE IS REQUIRED IN
 THE TITLE BLOCK AS WELL. FAC 61G1-16.004(2) & FS
 481.219, 481.2055.
 ****NO RESPONSE. THE CA NUMBER'S FOR THE STRUCTURAL
 ENGINEER AND PFVS ARCHITECTS ARE STILL REQUIRED AND NOT
 INDICATED IN THE TITLE BLOCKS. (EACH SHEET).
 ******RESPONSE NOTED, BUT PFVS ARCHITECTS IS STILL
 INDICATED IN THE TITLE BLOCK OF EACH SHEET. ALL
 REFERENCE TO THE ARCHITECTURAL COMPANY SHALL BE DELETED
 FROM THE TITLE BLOCK OR A FIRM LICENSE NUMBER,
 (CERTIFICATE OF AUTHORIZATION), WILL BE REQUIRED.
  
 6. OK (INFORMATIONAL ONLY)
  
 7. SHT AC104 POOL HOUSE PLAN. MENS TOILET ROOM REQUIRES
 A URINAL. PLEASE INDICATE ON PLANS. TABLE 424.1.6.1.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT NOW A TOILET STALL IS SHOWN
 IN THE TOILET ROOM. PER SECTION 11-4.17.3 EXCEPTION NEW
 CONTRUCTION AN ACCESSIBLE LAV IS REQUIRED IN THE STALL.
 (SEE THE EXCEPTION (1) TO SECTION 310.4 WHERE A STALL
 IS NOT REQUIRED).
  
 8. SHTS G-000 GUESTROOM MATRIX DOES NOT REFLECT THE
 FLOOR PLANS ON SHTS A-101 THRU A-105. THE MATRIX
 INDICATES A STUDIO AND A TWO BEDROOM ONLY TO BE
 ACCESSIBLE, BUT THE FLOOR PLAN ALSO SHOWS AN ACCESSIBLE
 DOUBLE QUEEN. ALSO THE 5TH FLOOR ON THE MATRIX
 INDICATES AN ACCESSIBLE KING, BUT NO ACCESSIBLE UNIT IS
 INDICATED ON THE FLOOR PLAN. PLEASE CORRELATE THE
 INFORMATION BETWEEN THE MATRIX AND THE FLOOR PLANS.
 SECTIONS 106.1.1 AND 11-9.1.2.
 ****RESPONSE WAS TO CHANGE MATRIX TO SHT G-002, BUT THE
 5TH FLOOR ON THE MATRIX INDICATES AN ACCESSIBLE KING,
 BUT NO ACCESSIBLE UNIT IS INDICATED ON THE FLOOR PLAN.
 ******RESPONSE NOTED, BUT 2ND FLOOR ACCESSIBLE STUDIO
 WAS NOT FOUND. 2ND FLOOR SHOWS ACCESSIBLE DOUBLE QUEEN
 NOT ON THE MATRIX. 3RD FLOOR ACCESSIBLE KING DOES NOT
 SHOW THE CLEAR FLOOR SPACE, TURNING ARE ETC. 5TH FLOOR
 ACCESSIBLE KING NOT FOUND. PLEASE CORRELATE THE MATRIX
 WITH ACCESSIBLE UNITS ON EACH FLOOR.
  
 9. PER SECTION 11-9.1.3, FIVE UNITS ARE REQUIRED TO BE
 COMPLIANT FOR THE HEARING IMPAIRED. ONLY 4 UNITS, (200,
 202, 300 & 319), ARE INDICATED AS BEING COMPLIANT.
 PLEASE CLARIFY.
 ****NO RESPONSE, BUT NOW UNITS 300 & 319 HAVE BEEN
 DELETED AND ONLY 3 UNITS ARE SHOWN AS UNIT 219 HAS BEEN
 ADDED. INDICATE WHICH UNITS ARE DESIGNATED FOR THE
 HEARING IMPAIRED ON THE MATRIX AS WELL AS ON THE FLOOR
 PLANS.
 ******RESPONSE THAT UNITS 200, 202, 209, 104 & 106 ARE
 HEARING IMPAIRED COMPLIANT IS INCORRECT. THE SYMBOL FOR
 HEARING IMPAIRED IS ONLY SHOWN ON ROOMS 200, 202 & 219,
 (NOT 209). NOTHING IS SHOWN FOR UNITS 104 & 106. PLEASE
 CORRELATE THE INFORMATION ON THE MATRIX WITH WHAT IS
 SUBMITTED ON THE FLOOR PLAN.
  
 10. SHT A-106 SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE AREA TO BE DRAINED FOR
 EACH ROOF DRAIN, AND INDICATE 1/2 THE AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED TO THAT AREA.
 ALSO INDICATE ALL AREAS FROM ROOF AREAS THAT DRAIN ONTO
 THE ROOF FROM ABOVE. SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES. INDICATE TOTAL AREA BEING
 DRAINED BY EACH DRAIN.-ALSO SEE SHT A-503. DETAIL 1
 INDICATES A ROOF DRAIN, AN EMERGENCY OVERFLOW DRAIN AND
 AND AN OVERFLOW SCUPPER. PLEASE CLARIFY.IF THE
 OVERFLOW DRAIN AND THE OVERFLOW SCUPPER ARE BOTH
 INSTALLED, PLEASE SUBMIT A DETAIL FOR THE OVERFLOW
 SCUPPER SHOWING THE HEIGHT & WIDTH, AS WELL AS, THE
 MEASUREMENT FROM THE ROOF TO THE FLOW LINE OF THE
 OVERFLOW SCUPPER PER SECTION 1503.4.2 AND TABLE 1106.7.
 THIS IS REQUIRED FOR ALL 3 FLAT ROOF AREAS.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE CALCULATIONS WERE NOT
 SUBMITTED. IS THE AREA FOR EACH ROOF DRAIN EXACTLY THE
 SAME? ARE THE VERTICAL WALLS & PARAPETS THE SAME FOR
 EACH AREA? PLEASE SUBMIT THE CALCULATIONS FOR EACH AREA
 SHOWING THE INFORMATION REQUESTED.
  
 11. SHT A-402 EMPLOYEE BREAK ROOM SINK SHALL COMPLY
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS. INDICATE ON
 FLOOR PLAN AND SINK ELEVATION.
 ****NO RESPONSE. PLEASE SHOW THE FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 ******RESPONSE NOTED, BUT KNEE CLEARANCE IS NOT SHOWN.
 B. 11-4.24.4 SINK DEPTH
 ******RESPONSE NOTED, BUT SINK DEPTH IS NOT SHOWN.C.
 11-4.24.5 CLEAR FLOOR SPACE
 ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT
 SHOWN.
 D. 11-4.24.7 FAUCETS
 ******RESPONSE NOTED, BUT THE FAUCET TYPE IS NOT
 INDICATED.
  
 12. SHT A-402 EMPLOYEE TOILET ROOM SHALL COMPLY WITH
 SECTIONS 11-4.16, 11-4.19, 11-4.22 & ALL SUBSECTIONS.
 PLEASE INDICATE ON ELEVATIONS.
 ****NO RESPONSE NOTED. PLEASE SHOW THE FOLLOWING: __FOR
 W/C'S:
 A. 11-4.16.2 OK
 B. 11-4.24.3 HEIGHT
 ******RESPONSE NOTED, BUT THE HEIGHT IS SHOWN AS 1'2".
 1'7" TO 1'9" REQUIRED.
 C. 11-4.24.5 FLUSH CONTROLS
 ******RESPONSE NOTED, BUT THE FLUSH CONTROL REQUIREMENT
 HAS NOT BEEN ADDRESSED.
 __FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 ******RESPONSE NOTED, BUT THE HEIGHT & CLEARANCE IS NOT
 SHOWN.
 B. 11-4.19.3 OK
 C. 11-4.19.5 FAUCETS
 ******RESPONSE NOTED, BUT THE FAUCET TYPE IS NOT
 INDICATED.
  
 13. SHT A-406 DETAILS 1, 2, 3 & 4. SHOW THE CLEAR FLOOR
 SPACE FOR ALL ACCESSIBLE FIXTURES PER SECTIONS
 11-4.16.2, 11-4.19.3, 11-4.20.2, 11-4.21.2 &
 11-4.24.5.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT
 SHOWN FOR THE LAV IN DETAIL #4, NOT SHOWN FOR THE TUB,
 AND NOT SHOWN FOR THE SINK IN DETAIL #2.
  
 14. SHT A-408 SHOW THE CLEAR FLOOR SPACE FOR ALL
 ACCESSIBLE FIXTURES PER SECTIONS 11-4.15.5, 11-4.16.2,
 11-4.18.3 & 11-4.19.3, & 11-4.22..3.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT
 SHOWN FOR ANY FIXTURE.
  
 15. SHT A-605 THE FINISH SCHEDULE FOR ROOMS 28 & 29
 SHOW PAINT OR V.W.C. FOR THE WALLS. SECTION 1210.2
 CALLS FOR "SMOOTH, HARD, NONABSORBENT" SURFACES. PAINT
 AND V.W.C. DO NOT COMPLY WITH THE "HARD" REQUIREMENT.
 PLEASE COMPLY.
 ****RESPONSE ON PLANS INDICATE CT WAINSCOTT TO 4'0"
 AFF, BUT DOES NOT INDICATE WHICH WALLS. (N, S, E, W).
 ******RESPONSE NOTED, BUT ONLY ONE WALL INDICATES "CT"
 IN EACH OF THE MEN'S AND WOMEN'S TOILET ROOMS. THE
 REMARKS STILL DO NOT INDICATE WHICH WALLS HAVE CT
 WAINSCOTT TO 4'0" AFF. PLEASE CLARIFY.
  
 16. SHT A-804 APPLICABLE ELEVATIONS 1 THRU 11,A-805
 APPLICABLE ELEVATIONS 1- THRU 9, SHALL COMPLY WITH
 SECTIONS 11-4.16, 11-4.18, 11-4.19, 11-4.20, 11-4.21 &
 11-4.22 AND ALL SUBSECTIONS. PLEASE INDICATE ON
 ELEVATIONS. ALSO SHOW ALL LAVS TO BE MIN. 15" OFF THE
 WALL TO THE CENTERLINE OF THE FIXTURE WHERE THE
 FIXTURES ARE ADJACENT TO THE WALLS. FIGURE 11-32.
 ****NO RESPONSE NOTED. SHOW THE FOLLOWING:
 __FOR W/C'S:
 A. 11-4.16.2 OK
 B. 11-4.16.3 HEIGHT
 ******RESPONSE NOTED, BUT THE HEIGHT IS NOT SHOWN.C.
 11-4.16.5 FLUSH CONTROLS
 ******RESPONSE NOTED, BUT THE FLUSH CONTROLS HAVE NOT
 BEEN ADDRESSED.
 __FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 ******RESPONSE NOTED, BUT THE HEIGHT AND CLEARANCES ARE
 NOT SHOWN.
 B. 11-4.19.3 CLEAR FLOOR SPACE
 ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT
 SHOWN.
 C. 11-4.19.5 FAUCETS
 ******RESPONSE NOTED, BUT THE FAUCET TYPE IS NOT
 INDICATED.
 __FOR TUBS:
 A. 11-4.20.2 CLEAR FLOOR SPACE
 ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT
 INDICATED.
 B. 11-4.20.3 SEAT
 ******RESPONSE NOTED, BUT THE SEAT HAS NOT BEEN
 ADDRESSED.
 __FOR SHOWERS:
 A. 11-4.21.3 SEAT (FOLDING TYPE)
 ******RESPONSE NOTED, BUT THE SEAT HAS NOT BEEN
 ADDRESSED.
  
 17. SHT A-808 ELEVATION DETAIL 9. THE SINK SHALL BE
 ACCESSIBLE & SHALL COMPLY WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. PLEASE SHOW COMPLIANCE.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT COMPLIANCE NOT SHOWN FOR THE
 FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE
 D. 11-4.24.7 FAUCETS
  
 18. SHT A-809 ELEVATIONS 4 & 9. THE SINK SHALL COMPLY
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS. A FORWARD
 APPROACH CLEAR FLOOR SPACE IS REQUIRED AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE SINK. CABINET DOORS ARE
 NOT APPROVED IN THE CLEAR FLOORSPACE AND ARE NOT TO
 BE INSTALLED. SUBMIT A SIDE ELEVATION SHOWING THE
 GARBAGE DISPOSAL. INDICTE COMPLIANCE WITH FIGURE 11-31.
 THE GARBAGE DISPOSAL SHALL BE ADA APPROVED LOW PROFILE
 TYPE THAT DOES NOT ENTER THE REQUIRED CLEAR FLOOR SPACE
 OF THE SINK.SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT
 SHOWN AT THE SINK IN THE EMPLOYEE BREAKROOM, (126), AND
 IS SHOWN AS PARALLEL APPROACH ON DETAIL #2. ELEVATION
 #4 DOES NOT SHOW THE KNEE CLEARANCE REQUIRED BY SECTION
 11-4.24.3. ELEVATIONS #4 & #9 DO NOT SHOW THE SINK
 DEPTH REQUIRED BY SECTION 11-4.24.4. ELEVATION #4
 EXPOSED PIPES & SURFACES REQUIREMENT OF 11-4.24.6.
 ELEVATIONS #4 & #9 THE FAUCET REQUIREMENT OF 11-4.24.7
  
 19. RESPONSE NOTED, NOT APPLICABLE
 20. OK.
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
 26. OK
  
 27. SUBMIT A PLAN LAYOUT OF ALL PLUMBING SANITARY
 DRAINAGE, WASTE & VENT. INDICATE THE FIXTURE MARK
 DESIGNATION TO CORRELATE WITH THE PLUMBING SCHEDULE
 SHOWN ON SHT P601 AND REFLECT THE SANITARY RISER
 DIAGRAMS. THIS SHALL BE SUBMITTED FOR EACH UNIT TYPE.
 SHTS P401 & P402 DO NOT SHOW THE SANITARY PIPING IN THE
 UNIT, ONLY THE RISER LOCATIONS. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT SHEET P503 WAS NOT SUBMITTED.
 ******RESPONSE NOTED, BUT NO PIPING, TRAPS, PIPE SIZE,
 VENT ISOMETRIC RISER DIAGRAM HAS BEEN SUBMITTED FOR THE
 LAUNDRY TRENCH DRAIN.--NO SANITARY ISOMETRIC FOR
 THE LAUNDRY, EMPLOYEE TOILET, BREAKROOM SINK AND
 RELATED STACKS TO UNITS TO REFLECT THE PIPING ON SHT
 P101A.--DETAIL #3 SHT P402 DOES NOT REFLECT
 SANITARY #2 & #3 RISER DIAGRAM AT FIXTURES P-1 & P-8.
 --NO SANITARY RISERS #4 & #5 INDICATED ON SHT P503.
 --NO SANITARY RISER DIAGRAM SHOWING 40DFU'S WITH BACK
 TO BACK WATER CLOSETS AS SHOWN ON SHT P503.
  
 28. SHT P501 DETAIL 1 DOES NOT REFLECT THE FLOOR PLAN.
 KING UNIT SHOW A KIT SINK, (P6), A LAV (P3), A TUB
 (P8), AND A W/C (P1), BUT DETAIL SHOWS A P6, ANOTHER
 P6, A P1 THEN A P8. PLEASE CORRELATE THE RISER AND THE
 FLOOR PLAN. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT UNTILL A PLUMBING PLAN PIPING
 LAYOUT IS SUBMITTED THAT REFLECTS THE RISER DIAGRAM,
 THE RISER DIAGRAM CAN NOT BE VERIFYED OR APPROVED. (SEE
 COMMENT 27). IT STILL SEEMS LIKE THE TUB, (P8), IS
 BEFORE THE W/C, (P1), ON THE FLOOR PLAN, BUT IS SHOWN
 OPPOSITE ON THE RISER DIAGRAM.
 ******RESPONSE NOTED, BUT THE RISER STILL SHOWS P-6,
 P-3, P-1 THEN P-8. THE KING ON SHT P402 SHOWS THE TUB,
 (P-8), DOWNSTREAM OF THE W/C, (P-1). THE RISER DIAGRAM
 SHALL REFLECT THE FLOOR PLAN.
  
 29. SHT P501 DETAIL 2 DOES NOT REFLECT THE FLOOR PLAN,
 (SHT P401) . THE TYPICAL STUDIO UNIT SHOWS A KIT SINK,
 (P6), A LAV (P3), A SHOWER (INDICATED AS 7A, NO 7A
 SHOWN ON THE FIXTURE SCHEDULE), AND A W/C (P1), BUT
 DETAIL SHOWS A P6, ANOTHER P6, A P1 THEN A P7A. PLEASE
 CORRELATE THE RISER,THE FLOOR PLAN, AND THE FIXTURE
 SCHEDULE. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE STUDIO FLOOR PLAN IS
 DIFFERENT FROM THE STUDIO ACC FLOOR PLAN. THE RISER CAN
 NOT BE TYPICAL FOR BOTH. SEPARATE RISER DIAGRAMS ARE
 REQUIRED FOR THE DIFFERENT FLOOR PLANS. ******RESPONSE
 NOTED, BUT SEPARATE RISER DIAGRAMS ARE REQUIRED FOR
 DIFFERENT FLOOR PLANS. RISER DIAGRAMS CAN ONLY BE
 TYPICAL IF THE FLOOR PLANS ARE TYPICAL.-- NEW SHT
 P501 DETAIL #3 EMERGENCY SHOWER/EYE WASH IS NOT FOUND
 ON EACH FLOOR. PLEASE CLARIFY.
  
 30. OK
  
 31. SUBMIT A SANITARY HORIZONTAL BUILDING DRAIN
 ISOMETRIC RISER DIAGRAM THAT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES, RISER LOCATIONS, TRAPS AND DFU'S
 AS THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3.
 -SHOW ALL THE FIRST FLOOR FIXTURES NOT CONNECTED TO A
 VERTICAL RISER ON THE HORIZONTAL RISER DIAGRAM. (SEE
 BREAK ROOM, FOOD PREP, LAUNDRY ROOM, TOILET ROOMS, PUMP
 ROOM ETC.).
 ****RESPONSE NOTED, BUT SHEET P503 HAS NOT BEEN
 SUBMITTED.
 ******RESPONSE NOTED, BUT THE EMPLOYEE BREAKROOM, FOOD
 PREP, POOL TOILET ROOMS, POOL EQUIPMENT ROOM ETC DO NOT
 HAVE ISOMETRIC RISER DIAGRAMS THAT REFLECT THE FLOOR
 PLAN SUBMITTED.
  
 32. SUBMIT A HORIZONTAL BUILDING WATER ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS, (REQUIRED BY SECTION 604.9 FOR ICE MAKERS,
 WASH MACHINES, AND DISHWASHERS).
 ****RESPONSE NOTED, BUT A HORIZONTAL WATER ISOMETRIC
 HAS HOT BEEN SUBMITTED. ONLY VERTICAL RISERS ARE
 SUBMITTED.
 ******RESPONSE NOTED, BUT THE VERTICAL DROPS AND
 VERTICAL RISER SECTIONS WERE NOT INCLUDED. SHOW A
 COMPLETE RISER DIAGRAM.--THE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN IN THE MEN'S POOL BATH & AT THE
 STUDIO UNITS ON THE WEST SIDE OF THE CORRIDOR. (NO HOT
 WATER TO UNITS).--EXPLAIN THE COLD WATER OUTSIDE
 THE BUILDING BY THE EMPLOYEE BREAK ROOM. PLEASE
 INDICATE WHERE THE LINE TERMINATES AND WHAT FIXTURE IT
 CONNECTS TO.
  
 33. SUBMIT A HORIZONTAL BUILDING CONDENSATE ISOMETRIC
 RISER DIAGRAM AND VERTICAL RISER DIAGRAMS. SHOW ALL
 PIPE SIZES AND INDICATE THE TERMINATION POINT.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. SUBMIT
 HORIZONTAL AND VERTICAL RISERS AS REQUESTED. IF
 CONNECTING TO THE STORM LINE, A RELIEF VENT SHALL BE
 INSTALLED IN THE CONDENSATE LINE/LINES AS THEY EXIT THE
 BUILDING.
 ******RESPONSE NOTED, COMMENT NOT ADDRESSED. NO
 CONDENSATE RISERS WERE FOUND ON SHT P-501 AS INDICATED
 IN RESPONSE. THE CONDENSATE CAN NOT DRAIN WHERE IT WILL
 CAUSE A HAZARD OR A NUISANCE. PLEASE EXPLAIN "TO GRADE"
 IS THIS IN A PLANTED AREA, SIDEWALK, PARKING LOT OR
 WHAT?
  
 34. INDICATE A NUMBER DESIGNATION FOR EACH RISER
 INCLUDING ALL SANT., WATER, STORM, CONDENSATE. (EXAMPLE
 SANT-1, SANT-2, RWL-1, RWL-2, CON-1, CON-2, W-1, W-2
 ETC.). THIS WILL AID IN TRACKING ALL RISERS FROM THE
 UNDERGROUND PIPING THROUGH THE ROOF. SECTIONS
 106.3.5.1.3 & SECTION 106.1.1.--INDICATE WHICH
 RISER IS TYPICAL OF WHICH RISER ISOMETRIC DIAGRAM.
 (EXAMPLE SANT-1 SANT-4 TYPICAL OF DETALI 4 SHT P401) --
 INDICATE ROOM NUMBER EACH RISER CAN BE LOCATED.
 ****RESPONSE NOTED, BUT SHEET P503 HAS NOT BEEN
 SUBMITTED.
 ******RESPONSE NOTED, BUT RESPONSE DOES NOT ADDRESS THE
 WATER RISERS, STORM RISERS, OR CONDENSATE RISERS.
  
 35. ROUTE PLANS TO THE DEPT. OF BUSINESS REGULATION,
 HOTEL & RESTURANT DIVISION FOR REVIEW PRIOR TO
 RESUBMITTING TO THE CITY FOR REVIEW. A MINIMUM OF TWO
 SETS OF PLANS, STAMPED BY DBPR AND TWO PAGE
 "WORKSHEETS" ATTACHED TO PLAN ARE REQUIRED. SECTION
 102.2.1.
 ****NO RESPONSE, NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE TWO PAGE SPECIFICATION
 WORKSHEETS FOR THE HOMEWOOD REVIEW ARE ATTACHED TO THE
 SPRINGHILL PLANS, AND THE WORKSHEETS FOR THE SPRINGHILL
 PLANS ARE ATTACHED TO THE HOMEWOOD PLANS. PLEASE INSERT
 THE CORRECT SPECIFICATION WORKSHEETS IN THE CORRECT
 PLANS.
  
 36. SHT A-101, A FOOD PREP AREA IS INDICATED. A GREASE
 INTERCEPTOR MAY BE REQUIRED. A MINIMUM 750 GAL.
 INTERCEPTOR IS REQUIRED. PLEASE CONTACT LMASSON,
 ENVIRONMENTAL COMPLIANCE MANAGER FOR SIZING OF THE
 GREASE INTERCEPTOR. CONTACT HER BY PHONE (561)
 822-2271, FAX (561) 822-2279, OR E-MAIL
 [email protected].
 ****RESPONSE NOTED, BUT NO APPROVAL FROM ENVIRONMENTAL
 COMPLIANCE HAS BEEN NOTED. I WILL PROCEED WITH AN
 INQUIRY AT THIS END.
 ******RESPONSE NOTED, BUT I AM STILL WAITING FOR THE
 APPROVAL FROM ENVIRONMENTAL COMPLIANCE.
  
 37. OK
  
 *****NEW COMMENTS 3RD REVIEW*****
  
  
 1B. PLANS SHALL BE SUBMITTED IN COMPLETE SETS. LOOSE
 SHEETS ARE NOT ACCEPTABLE. SECTION 106.1. PLEASE SUBMIT
 PLANS IN COMPLETE SETS.
  
 2B. SHT G-001 NOT ALL SHEETS SHOWN ON THE DRAWING INDEX
 HAVE BEEN SUBMITTED, AND SOME SHEETS ARE OUT OF ORDER.
 PLEASE CORRELATE THE SHEETS SUBMITTED WITH THE DRAWING
 INDEX. SECTION 106.1.1.
  
 3B. SHT AC-103 A URINAL IS REQUIRED IN THE MEN'S POOL
 TOILET ROOM. TABLE 424.1.6.1. PLEASE SHOW REQUIRED
 URINAL.
  
 4B. SHT P101A THE SANITARY BUILDING DRAIN DOES NOT
 REFLECT THE UNIT FLOOR PLAN, NOR DOES IT REFLECT THE
 SANITARY RISER DIAGRAM. PLEASE CORRELATE. SECTION
 106.1.1. THE UNITS SHOW THE PIPING TO THE OPPOSITE END
 OF THE TUBS & SHOWERS.--CONNECTIONS TO THE SANITARY
 BUILDING DRAIN FROM THE ELEVATOR SUMPS IS NOT APPROVED.
 SECTION 301.6. PLEASE DELETE FROM RISER AND FLOOR PLAN.
 --IDENTIFY ALL RISERS.--KEY NOTES #3 STATES "NOT
 USED", BUT KEY NOTE #3 IS SHOWN ON THE FLOOR PLAN ABOUT
 6 TIMES. PLEASE CLARIFY.
  
 5B. SHT P101A THE SANITARY BRANCH CONNECTIONS FROM THE
 FLOOR DRAINS IN THE POOL EQUIPMENT ROOM ARE SHOWN
 CONNECTING AGAINST THE FLOW. THIS IS NOT APPROVED PER
 SECTION 706.3. PLEASE SHOW FITTING INSTALLATION SO THAT
 IS GUIDES THE SEWAGE AND WASTE IN THE DIRECTION OF
 FLOW.
  
 6B. SUBMIT THE ISOMETRIC RISER DIAGRAMS FOR THE
 SANITARY AND WATER FOR THE POOL TOILET ROOMS, & FLOOR
 DRAINS IN THE EQUIPMENT ROOM, STORAGE ROOM. SECTION
 106.3.5.1.3(3)(4)(6)(10)(13).
  
 7B. SUBMIT A UNIT PLAN FOR THE ACCESSIBLE STUDIO. (THIS
 IS DIFFERENT FROM THE STANDARD STUDIO). A RISER DIAGRAM
 TO REFLECT THE FLOOR PLAN IS REQUIRED. SECTION
 106.3.5.1.3(4)(13).
  
 8B. SHT P101B THREE BRANCH CONNECTIONS ARE SHOWN
 CONNECTING AGAINST THE FLOW. THIS IS NOT APPROVED PER
 SECTION 706.3. PLEASE SHOW FITTING INSTALLATION SO THAT
 IS GUIDES THE SEWAGE AND WASTE IN THE DIRECTION OF
 FLOW.
  
 9B. SHT P101B THE SANITARY DRAIN PIPING DOES NOT
 REFLECT THE UNIT PIPING. (TUBS & SHOWERS SHOW SANT.
 PIPING TO OPPOSITE END OF THE FIXTURES).--THE
 ELEVATOR SUMP PUMPS SHALL NOT CONNECT TO THE SANITARY
 BUILDING DRAIN. SECTION 301.6.--2-WAY CLEANOUTS ARE
 REQUIRED AT THE ENTRANCE AND EXITING PIPING OF THE
 GREASE INTERCEPTOR AND NEAR THE JUNCTION OF THE KITCHEN
 DRAIN & SEWER. SECTION 708.3.5 & UTILITY STANDARD FOR
 GREASE INTERCEPTORS.
  
 10B. SHT P101C PIPING IS NOT SHOWN TO STUDIOS WEST OF
 THE CORRIDOR.--KEY NOTES #2 STILL INDICATES 7" WC
 INLET PRESSURE. 11" TO 14", (1/2PSI) REQUIRED TO
 REFLECT CHANGES IN THE NATURAL GAS SYSTEM.-- INDICATE
 WHERE THE COLD WATER SUPPLY OUTSIDE THE EMPLOYEE BREAK
 ROOM TERMINATES OR WHAT FIXTURE IT SUPPLIES. SECTION
 106.1.1.
  
 11B. SHT P101D NO HOT & COLD PIPING IS INDICATED FOR
 THE STUDIOS. PLEASE SHOW PIPING. SECTION 106.3.5.1.3
  
 12B. SUBMIT A STORM ISOMETRIC RISER DIAGRAM FOR THE
 HORIZONTAL BUILDING STORM DRAIN. SHOW ALL VERTICAL
 RISERS FROM THE BUILDING DRAIN TO THE ROOF DRAINS. SHOW
 ALL PIPE SIZE, OFFSETS, CLEANOUTS REQUIRED BY SECTION
 1101.8 AND INDICATE SQUARE FOOTAGE AS IT ACCUMULATES IN
 THE SYSTEM. SECTION 106.3.5.1.3 (7)(13).
  
 13B. SHTS P104 & P104A SHOWS 2-1/2" FDV. PLEASE CLARIFY
 WHAT SYSTEM THIS PIPING IS FOR. SECTION 106.1.1.
  
 14B. SHT P401 SOME INFORMATION AT THE BOTTOM OF THE
 SHEET IS NOT LEGIBLE AND NO DETAIL NUMBERS ARE
 INDICATED. PLEASE CLARIFY. SECTION 106.1.1.--KEY
 NOTES #3 STATES "NOT USED", BUT #3 IS SHOWN ON THE
 FLOOR PLAN.--KEY NOTES #6 STATES "NOT USED", BUT
 #6 IS SHOWN ON THE FLOOR PLAN.--KEY NOTES #11 IS
 SHOWN ON THE FLOOR PLAN, BUT NOT INDICATED ON THE KEY
 NOTES INDEX. PLEASE CLARIFY. SECTION 106.1.1.
  
 15B. SHT P401 SUBMIT ISOMETRIC RISER DIAGRAMS FOR EACH
 UNIT. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9 ETC TO REFLECT THE
 FLOOR PLAN. SECTION 106.3.5.1.3(3)(10)(13).
  
 16B. SHT P402 SUBMIT ISOMETRIC RISER DIAGRAMS FOR EACH
 UNIT. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9 ETC TO REFLECT THE
 FLOOR PLAN. SECTION 106.3.5.1.3(3)(10)(13).
  
 17B. SHT P402 KEY NOTES #6 STATES "NOT USED", BUT IS
 INDICATED IN DETAILS #1 & #3. CLARIFY.--DETAIL#4
 SHOWS KEY NOTES #5 AT THE WATER CLOSET AND IS INDICATED
 AS HOT & COLD. CLARIFY.--DETAIL #1 KEY NOTE #2
 STATES "NOT USED", BUT IS INDICATED AT SHOWER WITH KEY
 NOTE #6. PLEASE CLARIFY. SECTION 106.1.1.
  
 18B. SHT P403 INFORMATION AT THE BOTTOM OF THE SHEET IS
 NOT LEGIBLE. PLEASE CLARIFY. SECTION 106.1.1.--KEY
 NOTES #14 DISHWASHER SHALL DISCHARGE TO A FLOOR SINK,
 NOT A FLOOR DRAIN & SHALL DRAIN TO THE SANITARY SYSTEM,
 NOT THE GREASE SYSTEM. SECTION 802.3 AND ARTICLE III
 SECTION 90-124(7)(B).--KEY NOTES #15 DRIP LEG NOT
 SHOWN.--DETAIL #4 FLOOR DRAIN TO BE ACCESSIBLE.
 SECTION 708.9.
  
 19B. SHT P403 SUBMIT ISOMETRIC RISER DIAGRAMS FOR THE
 SANITARY AND WATER FOR THE KITCHEN PIPING AND FOR THE
 MEN'S AND WOMEN'S TOILET ROOMS. SECTION 106.3.5.1.3
 (3)(4)(6)(10)(13).
  
 20B. SHT P404 KEY NOTES 5, 8, 11, & 13 WERE NOT FOUND
 IN DETAIL #1. PLEASE CLARIFY.--KEY NOTE #3 DRIP
 LEG SHALL BE INSTALLED IN THEVERTICAL POSITION. SHOWN
 AS HORIZONTAL.SECTIONS 106.1.1 & 408.2.
  
 21B. SHT P501 DETAIL/RISER #1 DOES NOT REFLECT THE
 FLOOR PLAN AT FIXTURES P6 & P8.--DETAIL /RISER #5
 DOES NOT REFLECT SHT P101A SAN #1 & INDICATES PASSING
 THRU THE 1ST FLOOR TWICE. PLEASE CLARIFY. SECTION
 106.1.1.--DETAIL/RISER 3 INDICATES GUEST
 LAUNDRY/MAINTENANCE. THIS IS NOT FOUND ON THE FLOOR
 PLAN. PLEASE CLARIFY.
  
 22B. SHT P502 THE WATER RISER DIAGRAMS DO NOT REFLECT
 THE FLOOR PLANS. NOT ALL FLOOR PLANS ARE SHOWN. PLEASE
 SUBMIT RISERS TO REFLECT THE FLOOR PLAN AND SUBMIT A
 FLOOR PLAN FOR EACH UNIT TYPE. SECTION 106.3.5.1.3.
  
 23B. SHT P503 THE SANITARY RISER ISOMETRIC DOES NOT
 REFLECT THE FLOOR PLAN.--THE GREASE INTERCEPTOR &
 PIPING TO THE KITCHEN IS NOT SHOWN.--THE TOILET
 ROOM ARE NOT SHOWN.--ONLY ONE FLOOR DRAIN IS SHOWN
 ON THE FLOOR PLAN, BUT TWO ARE SHOWN ON THE RISER.--
 3" FLOOR DRAIN REQUIRES A VENT.--NO RISER DETAIL #6
 WAS FOUND.--BOTH ELEVATOR SUMP PUMPS SHALL NOT
 CONNECT TO THE SANITARY BUILDING DRAIN.--THE BRANCH
 LINES TO THE STUDIO UNITS DO NOT REFLECT THE FLOOR
 PLAN. SECTIONS 106.1.1, 106.3.5.1.3, 901.2.1, 301.6.
  
 24B. SHT P503 THE BUILDING DRAIN LINE SHOWS TWO
 BUILDING DRAINS FROM THE BUILDING ON THE RISER DIAGRAM,
 BUT ONLY ONE ON THE FLOOR PLAN.--THERE ARE EXTRA
 BRANCH LINES, ONE FOR 40DFU'S THAT THERE IS NO RISER TO
 REFLECT BACK TO BACK WATER CLOSETS.--SOME BRANCH
 CONNECTIONS TO THE BUILDING DRAIN DO NOT REFLECT THE
 FLOOR PLAN.--RISER DOES NOT REFLECT THE FLOOR PLAN
 BY THE LAUNDRY/EMPLOYEE BREAK ROOM. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 25B. SHT P504 LABELED WASTE & VENT RISER DIAGRAMS.--
 WATER MAIN ISOMETRIC RISER DIAGRAM DOES NOT SHOW THE
 DROPS TO THE FIXTURES, OR THE RISERS TO THE UPPER
 LEVELS.--DOES NOT REFLECT THE FLOOR PLAN AT THE
 MENS POOL TOILET ROOM & AT THE STUDIO UNITS WEST OF THE
 CORRIDOR. PLEASE INDICATE WHERE THE COLD WATER LINE
 TERMINATES SHOWN OUTSIDE THE BUILDING BY THE EMPLOYEE
 BREAK ROOM AREA. PLEASE CLAIRFY. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 -PLEASE RESUBMIT ONE SET OF OLD SHEETS
 FOR COMPARISON.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  