| 2007-11-19 18:56:55 | |
| | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2001 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | ******FROM PREVIOUS REVIEWS: 3RD REVIEW: |
| | |
| | 1. OK |
| | |
| | 2. SHTS G-000 THRU G-003 THE FIRM LICENSE NUMBER AND |
| | THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT ARE |
| | REQUIRED ON EACH SHEET. FAC 61G1-16.004(2)(6) & FS |
| | 481.219, 481.2055.-THE EMBOSSED SEAL SHALL IMPRESS |
| | ALL INFORMATION REQUIRED BY FAC G1G1-16.002 & FS |
| | 481.2055. NOT ALL INFORMATION REQUIRED IS IMPRESSED ON |
| | EACH SHEET. PLEASE MAKE SURE THE REQUIRED INFORMATION |
| | IS IN THE TITLE BLOCK AND RESEAL THE PLANS MAKING SURE |
| | ALL INFORMATION IS IMPRESSED & LEGIBLE WHEN SEALING THE |
| | PLANS. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE TITLE BLOCK STILL |
| | INDICATES PFVS ARCHITECTS. ALL REFERENCE TO THE |
| | ARCHITECTURAL COMPANY SHALL BE DELETED FROM THE TITLE |
| | BLOCK OR A FIRM LICENSE NUMBER, (CERTIFICATE OF |
| | AUTHORIZATION), WILL BE REQUIRED.--ALSO THE SEAL |
| | BEING USED IS NOT APPROVED. PER FAC 61G1-16.002 THE |
| | SEAL SHALL BE APPROX. 2" IN DIAMETER. FS 481.2055. |
| | |
| | 3. ALL ARCHITECTURAL SHEETS THE TITLE BLOCK SHALL |
| | INDICATE THE FIRM LICENSE NUMBER,AND THE PRINTED NAME |
| | OF THE PERSON SEALING THE DOCUMENT. FAC |
| | 61G1-16.004(2)(6) & FS 481.219, 481.2055. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT PVFS ARCHITECTS IS STILL |
| | INDICATED IN THE TITLE BLOCK OF EACH SHEET. ALL |
| | REFERENCE TO THE ARCHITECTURAL COMPANY SHALL BE DELETED |
| | FROM THE TITLE BLOCK OR A FIRM LICENSE NUMBER, |
| | (CERTIFICATE OF AUTHORIZATION), WILL BE REQUIRED.-- |
| | ALSO THE SEAL BEING USED IS NOT APPROVED. PER FAC |
| | 61G1-16.002 THE SEAL SHALL BE APPROX. 2" IN DIAMETER. |
| | FS 481.2055. |
| | |
| | 4.SHTS SP-1, LP-1, LP-2 & LP-3. THE ADDRESS OF THE |
| | LANDSCAPE ARCHITECT DOES NOT REFLECT THE ADDRESS |
| | INDICATED ON THE DBPR WEBSITE. (SEE ATTACHED SHEET FROM |
| | THE STATE WEBSITE). PLEASE SHOW CORRECT ADDRESS IN THE |
| | TITLE BLOCK OR UPDATE THE ADDRESS WITH THE STATE DBPR |
| | WEBSITE. FAC 61G1-16.004(1) & FS 481.2055. ****RESPONSE |
| | NOTED, BUT NOT ALL INFORMATION REQUIRED FOR THE SEAL |
| | HAS BEEN IMPRESSED ON EACH SHEET. NOT ALL INFORMATION |
| | IS LEGIBLE. |
| | ******RESPONSE NOTED. THE SHEETS HAVE BEEN DELETED BUT |
| | ARE STILL SHOWN IN THE INDEX OF DRAWINGS ON SHT G-001. |
| | PLEASE CORRELATE THE DRAWING INDEX WITH THE SHEETS |
| | SUBMITTED. |
| | |
| | 5. ALL STRUCTURAL SHEETS. THE ENGINEERS SHALL LEGIBLY |
| | INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON |
| | EACH SHEET. IF PRACTICING THROUGH A DULY AUTHORIZED |
| | ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME & LICENSE NUMBER, AS WELL AS, THE NAME, |
| | ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE |
| | ENGINEERING BUSINESS ON EACH SHEET. FAC 61G15-23.002(2) |
| | & FS 471.025. THE BUSINESS NUMBER, (CERTIFICATE OF |
| | AUTHORIZATION), FOR PFVS ARCHITECTURE IS REQUIRED IN |
| | THE TITLE BLOCK AS WELL. FAC 61G1-16.004(2) & FS |
| | 481.219, 481.2055. |
| | ****NO RESPONSE. THE CA NUMBER'S FOR THE STRUCTURAL |
| | ENGINEER AND PFVS ARCHITECTS ARE STILL REQUIRED AND NOT |
| | INDICATED IN THE TITLE BLOCKS. (EACH SHEET). |
| | ******RESPONSE NOTED, BUT PFVS ARCHITECTS IS STILL |
| | INDICATED IN THE TITLE BLOCK OF EACH SHEET. ALL |
| | REFERENCE TO THE ARCHITECTURAL COMPANY SHALL BE DELETED |
| | FROM THE TITLE BLOCK OR A FIRM LICENSE NUMBER, |
| | (CERTIFICATE OF AUTHORIZATION), WILL BE REQUIRED. |
| | |
| | 6. OK (INFORMATIONAL ONLY) |
| | |
| | 7. SHT AC104 POOL HOUSE PLAN. MENS TOILET ROOM REQUIRES |
| | A URINAL. PLEASE INDICATE ON PLANS. TABLE 424.1.6.1. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT NOW A TOILET STALL IS SHOWN |
| | IN THE TOILET ROOM. PER SECTION 11-4.17.3 EXCEPTION NEW |
| | CONTRUCTION AN ACCESSIBLE LAV IS REQUIRED IN THE STALL. |
| | (SEE THE EXCEPTION (1) TO SECTION 310.4 WHERE A STALL |
| | IS NOT REQUIRED). |
| | |
| | 8. SHTS G-000 GUESTROOM MATRIX DOES NOT REFLECT THE |
| | FLOOR PLANS ON SHTS A-101 THRU A-105. THE MATRIX |
| | INDICATES A STUDIO AND A TWO BEDROOM ONLY TO BE |
| | ACCESSIBLE, BUT THE FLOOR PLAN ALSO SHOWS AN ACCESSIBLE |
| | DOUBLE QUEEN. ALSO THE 5TH FLOOR ON THE MATRIX |
| | INDICATES AN ACCESSIBLE KING, BUT NO ACCESSIBLE UNIT IS |
| | INDICATED ON THE FLOOR PLAN. PLEASE CORRELATE THE |
| | INFORMATION BETWEEN THE MATRIX AND THE FLOOR PLANS. |
| | SECTIONS 106.1.1 AND 11-9.1.2. |
| | ****RESPONSE WAS TO CHANGE MATRIX TO SHT G-002, BUT THE |
| | 5TH FLOOR ON THE MATRIX INDICATES AN ACCESSIBLE KING, |
| | BUT NO ACCESSIBLE UNIT IS INDICATED ON THE FLOOR PLAN. |
| | ******RESPONSE NOTED, BUT 2ND FLOOR ACCESSIBLE STUDIO |
| | WAS NOT FOUND. 2ND FLOOR SHOWS ACCESSIBLE DOUBLE QUEEN |
| | NOT ON THE MATRIX. 3RD FLOOR ACCESSIBLE KING DOES NOT |
| | SHOW THE CLEAR FLOOR SPACE, TURNING ARE ETC. 5TH FLOOR |
| | ACCESSIBLE KING NOT FOUND. PLEASE CORRELATE THE MATRIX |
| | WITH ACCESSIBLE UNITS ON EACH FLOOR. |
| | |
| | 9. PER SECTION 11-9.1.3, FIVE UNITS ARE REQUIRED TO BE |
| | COMPLIANT FOR THE HEARING IMPAIRED. ONLY 4 UNITS, (200, |
| | 202, 300 & 319), ARE INDICATED AS BEING COMPLIANT. |
| | PLEASE CLARIFY. |
| | ****NO RESPONSE, BUT NOW UNITS 300 & 319 HAVE BEEN |
| | DELETED AND ONLY 3 UNITS ARE SHOWN AS UNIT 219 HAS BEEN |
| | ADDED. INDICATE WHICH UNITS ARE DESIGNATED FOR THE |
| | HEARING IMPAIRED ON THE MATRIX AS WELL AS ON THE FLOOR |
| | PLANS. |
| | ******RESPONSE THAT UNITS 200, 202, 209, 104 & 106 ARE |
| | HEARING IMPAIRED COMPLIANT IS INCORRECT. THE SYMBOL FOR |
| | HEARING IMPAIRED IS ONLY SHOWN ON ROOMS 200, 202 & 219, |
| | (NOT 209). NOTHING IS SHOWN FOR UNITS 104 & 106. PLEASE |
| | CORRELATE THE INFORMATION ON THE MATRIX WITH WHAT IS |
| | SUBMITTED ON THE FLOOR PLAN. |
| | |
| | 10. SHT A-106 SUBMIT CALCULATIONS FOR THE PRIMARY AND |
| | SECONDARY ROOF DRAINS. SHOW THE AREA TO BE DRAINED FOR |
| | EACH ROOF DRAIN, AND INDICATE 1/2 THE AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS ADDED TO THAT AREA. |
| | ALSO INDICATE ALL AREAS FROM ROOF AREAS THAT DRAIN ONTO |
| | THE ROOF FROM ABOVE. SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS AND TABLES. INDICATE TOTAL AREA BEING |
| | DRAINED BY EACH DRAIN.-ALSO SEE SHT A-503. DETAIL 1 |
| | INDICATES A ROOF DRAIN, AN EMERGENCY OVERFLOW DRAIN AND |
| | AND AN OVERFLOW SCUPPER. PLEASE CLARIFY.IF THE |
| | OVERFLOW DRAIN AND THE OVERFLOW SCUPPER ARE BOTH |
| | INSTALLED, PLEASE SUBMIT A DETAIL FOR THE OVERFLOW |
| | SCUPPER SHOWING THE HEIGHT & WIDTH, AS WELL AS, THE |
| | MEASUREMENT FROM THE ROOF TO THE FLOW LINE OF THE |
| | OVERFLOW SCUPPER PER SECTION 1503.4.2 AND TABLE 1106.7. |
| | THIS IS REQUIRED FOR ALL 3 FLAT ROOF AREAS. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE CALCULATIONS WERE NOT |
| | SUBMITTED. IS THE AREA FOR EACH ROOF DRAIN EXACTLY THE |
| | SAME? ARE THE VERTICAL WALLS & PARAPETS THE SAME FOR |
| | EACH AREA? PLEASE SUBMIT THE CALCULATIONS FOR EACH AREA |
| | SHOWING THE INFORMATION REQUESTED. |
| | |
| | 11. SHT A-402 EMPLOYEE BREAK ROOM SINK SHALL COMPLY |
| | WITH SECTION 11-4.24 AND ALL SUBSECTIONS. INDICATE ON |
| | FLOOR PLAN AND SINK ELEVATION. |
| | ****NO RESPONSE. PLEASE SHOW THE FOLLOWING: |
| | A. 11-4.24.3 KNEE CLEARANCE |
| | ******RESPONSE NOTED, BUT KNEE CLEARANCE IS NOT SHOWN. |
| | B. 11-4.24.4 SINK DEPTH |
| | ******RESPONSE NOTED, BUT SINK DEPTH IS NOT SHOWN.C. |
| | 11-4.24.5 CLEAR FLOOR SPACE |
| | ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT |
| | SHOWN. |
| | D. 11-4.24.7 FAUCETS |
| | ******RESPONSE NOTED, BUT THE FAUCET TYPE IS NOT |
| | INDICATED. |
| | |
| | 12. SHT A-402 EMPLOYEE TOILET ROOM SHALL COMPLY WITH |
| | SECTIONS 11-4.16, 11-4.19, 11-4.22 & ALL SUBSECTIONS. |
| | PLEASE INDICATE ON ELEVATIONS. |
| | ****NO RESPONSE NOTED. PLEASE SHOW THE FOLLOWING: __FOR |
| | W/C'S: |
| | A. 11-4.16.2 OK |
| | B. 11-4.24.3 HEIGHT |
| | ******RESPONSE NOTED, BUT THE HEIGHT IS SHOWN AS 1'2". |
| | 1'7" TO 1'9" REQUIRED. |
| | C. 11-4.24.5 FLUSH CONTROLS |
| | ******RESPONSE NOTED, BUT THE FLUSH CONTROL REQUIREMENT |
| | HAS NOT BEEN ADDRESSED. |
| | __FOR LAVS: |
| | A. 11-4.19.2 HEIGHT & CLEARANCES |
| | ******RESPONSE NOTED, BUT THE HEIGHT & CLEARANCE IS NOT |
| | SHOWN. |
| | B. 11-4.19.3 OK |
| | C. 11-4.19.5 FAUCETS |
| | ******RESPONSE NOTED, BUT THE FAUCET TYPE IS NOT |
| | INDICATED. |
| | |
| | 13. SHT A-406 DETAILS 1, 2, 3 & 4. SHOW THE CLEAR FLOOR |
| | SPACE FOR ALL ACCESSIBLE FIXTURES PER SECTIONS |
| | 11-4.16.2, 11-4.19.3, 11-4.20.2, 11-4.21.2 & |
| | 11-4.24.5. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT |
| | SHOWN FOR THE LAV IN DETAIL #4, NOT SHOWN FOR THE TUB, |
| | AND NOT SHOWN FOR THE SINK IN DETAIL #2. |
| | |
| | 14. SHT A-408 SHOW THE CLEAR FLOOR SPACE FOR ALL |
| | ACCESSIBLE FIXTURES PER SECTIONS 11-4.15.5, 11-4.16.2, |
| | 11-4.18.3 & 11-4.19.3, & 11-4.22..3. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT |
| | SHOWN FOR ANY FIXTURE. |
| | |
| | 15. SHT A-605 THE FINISH SCHEDULE FOR ROOMS 28 & 29 |
| | SHOW PAINT OR V.W.C. FOR THE WALLS. SECTION 1210.2 |
| | CALLS FOR "SMOOTH, HARD, NONABSORBENT" SURFACES. PAINT |
| | AND V.W.C. DO NOT COMPLY WITH THE "HARD" REQUIREMENT. |
| | PLEASE COMPLY. |
| | ****RESPONSE ON PLANS INDICATE CT WAINSCOTT TO 4'0" |
| | AFF, BUT DOES NOT INDICATE WHICH WALLS. (N, S, E, W). |
| | ******RESPONSE NOTED, BUT ONLY ONE WALL INDICATES "CT" |
| | IN EACH OF THE MEN'S AND WOMEN'S TOILET ROOMS. THE |
| | REMARKS STILL DO NOT INDICATE WHICH WALLS HAVE CT |
| | WAINSCOTT TO 4'0" AFF. PLEASE CLARIFY. |
| | |
| | 16. SHT A-804 APPLICABLE ELEVATIONS 1 THRU 11,A-805 |
| | APPLICABLE ELEVATIONS 1- THRU 9, SHALL COMPLY WITH |
| | SECTIONS 11-4.16, 11-4.18, 11-4.19, 11-4.20, 11-4.21 & |
| | 11-4.22 AND ALL SUBSECTIONS. PLEASE INDICATE ON |
| | ELEVATIONS. ALSO SHOW ALL LAVS TO BE MIN. 15" OFF THE |
| | WALL TO THE CENTERLINE OF THE FIXTURE WHERE THE |
| | FIXTURES ARE ADJACENT TO THE WALLS. FIGURE 11-32. |
| | ****NO RESPONSE NOTED. SHOW THE FOLLOWING: |
| | __FOR W/C'S: |
| | A. 11-4.16.2 OK |
| | B. 11-4.16.3 HEIGHT |
| | ******RESPONSE NOTED, BUT THE HEIGHT IS NOT SHOWN.C. |
| | 11-4.16.5 FLUSH CONTROLS |
| | ******RESPONSE NOTED, BUT THE FLUSH CONTROLS HAVE NOT |
| | BEEN ADDRESSED. |
| | __FOR LAVS: |
| | A. 11-4.19.2 HEIGHT & CLEARANCES |
| | ******RESPONSE NOTED, BUT THE HEIGHT AND CLEARANCES ARE |
| | NOT SHOWN. |
| | B. 11-4.19.3 CLEAR FLOOR SPACE |
| | ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT |
| | SHOWN. |
| | C. 11-4.19.5 FAUCETS |
| | ******RESPONSE NOTED, BUT THE FAUCET TYPE IS NOT |
| | INDICATED. |
| | __FOR TUBS: |
| | A. 11-4.20.2 CLEAR FLOOR SPACE |
| | ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT |
| | INDICATED. |
| | B. 11-4.20.3 SEAT |
| | ******RESPONSE NOTED, BUT THE SEAT HAS NOT BEEN |
| | ADDRESSED. |
| | __FOR SHOWERS: |
| | A. 11-4.21.3 SEAT (FOLDING TYPE) |
| | ******RESPONSE NOTED, BUT THE SEAT HAS NOT BEEN |
| | ADDRESSED. |
| | |
| | 17. SHT A-808 ELEVATION DETAIL 9. THE SINK SHALL BE |
| | ACCESSIBLE & SHALL COMPLY WITH SECTION 11-4.24 AND ALL |
| | SUBSECTIONS. PLEASE SHOW COMPLIANCE. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT COMPLIANCE NOT SHOWN FOR THE |
| | FOLLOWING: |
| | A. 11-4.24.3 KNEE CLEARANCE |
| | B. 11-4.24.4 SINK DEPTH |
| | C. 11-4.24.5 CLEAR FLOOR SPACE |
| | D. 11-4.24.7 FAUCETS |
| | |
| | 18. SHT A-809 ELEVATIONS 4 & 9. THE SINK SHALL COMPLY |
| | WITH SECTION 11-4.24 AND ALL SUBSECTIONS. A FORWARD |
| | APPROACH CLEAR FLOOR SPACE IS REQUIRED AND SHALL EXTEND |
| | A MAXIMUM OF 19" UNDERNEATH THE SINK. CABINET DOORS ARE |
| | NOT APPROVED IN THE CLEAR FLOORSPACE AND ARE NOT TO |
| | BE INSTALLED. SUBMIT A SIDE ELEVATION SHOWING THE |
| | GARBAGE DISPOSAL. INDICTE COMPLIANCE WITH FIGURE 11-31. |
| | THE GARBAGE DISPOSAL SHALL BE ADA APPROVED LOW PROFILE |
| | TYPE THAT DOES NOT ENTER THE REQUIRED CLEAR FLOOR SPACE |
| | OF THE SINK.SECTION 106.1.1. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE IS NOT |
| | SHOWN AT THE SINK IN THE EMPLOYEE BREAKROOM, (126), AND |
| | IS SHOWN AS PARALLEL APPROACH ON DETAIL #2. ELEVATION |
| | #4 DOES NOT SHOW THE KNEE CLEARANCE REQUIRED BY SECTION |
| | 11-4.24.3. ELEVATIONS #4 & #9 DO NOT SHOW THE SINK |
| | DEPTH REQUIRED BY SECTION 11-4.24.4. ELEVATION #4 |
| | EXPOSED PIPES & SURFACES REQUIREMENT OF 11-4.24.6. |
| | ELEVATIONS #4 & #9 THE FAUCET REQUIREMENT OF 11-4.24.7 |
| | |
| | 19. RESPONSE NOTED, NOT APPLICABLE |
| | 20. OK. |
| | 21. OK |
| | 22. OK |
| | 23. OK |
| | 24. OK |
| | 25. OK |
| | 26. OK |
| | |
| | 27. SUBMIT A PLAN LAYOUT OF ALL PLUMBING SANITARY |
| | DRAINAGE, WASTE & VENT. INDICATE THE FIXTURE MARK |
| | DESIGNATION TO CORRELATE WITH THE PLUMBING SCHEDULE |
| | SHOWN ON SHT P601 AND REFLECT THE SANITARY RISER |
| | DIAGRAMS. THIS SHALL BE SUBMITTED FOR EACH UNIT TYPE. |
| | SHTS P401 & P402 DO NOT SHOW THE SANITARY PIPING IN THE |
| | UNIT, ONLY THE RISER LOCATIONS. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT SHEET P503 WAS NOT SUBMITTED. |
| | ******RESPONSE NOTED, BUT NO PIPING, TRAPS, PIPE SIZE, |
| | VENT ISOMETRIC RISER DIAGRAM HAS BEEN SUBMITTED FOR THE |
| | LAUNDRY TRENCH DRAIN.--NO SANITARY ISOMETRIC FOR |
| | THE LAUNDRY, EMPLOYEE TOILET, BREAKROOM SINK AND |
| | RELATED STACKS TO UNITS TO REFLECT THE PIPING ON SHT |
| | P101A.--DETAIL #3 SHT P402 DOES NOT REFLECT |
| | SANITARY #2 & #3 RISER DIAGRAM AT FIXTURES P-1 & P-8. |
| | --NO SANITARY RISERS #4 & #5 INDICATED ON SHT P503. |
| | --NO SANITARY RISER DIAGRAM SHOWING 40DFU'S WITH BACK |
| | TO BACK WATER CLOSETS AS SHOWN ON SHT P503. |
| | |
| | 28. SHT P501 DETAIL 1 DOES NOT REFLECT THE FLOOR PLAN. |
| | KING UNIT SHOW A KIT SINK, (P6), A LAV (P3), A TUB |
| | (P8), AND A W/C (P1), BUT DETAIL SHOWS A P6, ANOTHER |
| | P6, A P1 THEN A P8. PLEASE CORRELATE THE RISER AND THE |
| | FLOOR PLAN. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT UNTILL A PLUMBING PLAN PIPING |
| | LAYOUT IS SUBMITTED THAT REFLECTS THE RISER DIAGRAM, |
| | THE RISER DIAGRAM CAN NOT BE VERIFYED OR APPROVED. (SEE |
| | COMMENT 27). IT STILL SEEMS LIKE THE TUB, (P8), IS |
| | BEFORE THE W/C, (P1), ON THE FLOOR PLAN, BUT IS SHOWN |
| | OPPOSITE ON THE RISER DIAGRAM. |
| | ******RESPONSE NOTED, BUT THE RISER STILL SHOWS P-6, |
| | P-3, P-1 THEN P-8. THE KING ON SHT P402 SHOWS THE TUB, |
| | (P-8), DOWNSTREAM OF THE W/C, (P-1). THE RISER DIAGRAM |
| | SHALL REFLECT THE FLOOR PLAN. |
| | |
| | 29. SHT P501 DETAIL 2 DOES NOT REFLECT THE FLOOR PLAN, |
| | (SHT P401) . THE TYPICAL STUDIO UNIT SHOWS A KIT SINK, |
| | (P6), A LAV (P3), A SHOWER (INDICATED AS 7A, NO 7A |
| | SHOWN ON THE FIXTURE SCHEDULE), AND A W/C (P1), BUT |
| | DETAIL SHOWS A P6, ANOTHER P6, A P1 THEN A P7A. PLEASE |
| | CORRELATE THE RISER,THE FLOOR PLAN, AND THE FIXTURE |
| | SCHEDULE. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THE STUDIO FLOOR PLAN IS |
| | DIFFERENT FROM THE STUDIO ACC FLOOR PLAN. THE RISER CAN |
| | NOT BE TYPICAL FOR BOTH. SEPARATE RISER DIAGRAMS ARE |
| | REQUIRED FOR THE DIFFERENT FLOOR PLANS. ******RESPONSE |
| | NOTED, BUT SEPARATE RISER DIAGRAMS ARE REQUIRED FOR |
| | DIFFERENT FLOOR PLANS. RISER DIAGRAMS CAN ONLY BE |
| | TYPICAL IF THE FLOOR PLANS ARE TYPICAL.-- NEW SHT |
| | P501 DETAIL #3 EMERGENCY SHOWER/EYE WASH IS NOT FOUND |
| | ON EACH FLOOR. PLEASE CLARIFY. |
| | |
| | 30. OK |
| | |
| | 31. SUBMIT A SANITARY HORIZONTAL BUILDING DRAIN |
| | ISOMETRIC RISER DIAGRAM THAT REFLECT THE FLOOR PLAN. |
| | SHOW ALL PIPE SIZES, RISER LOCATIONS, TRAPS AND DFU'S |
| | AS THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3. |
| | -SHOW ALL THE FIRST FLOOR FIXTURES NOT CONNECTED TO A |
| | VERTICAL RISER ON THE HORIZONTAL RISER DIAGRAM. (SEE |
| | BREAK ROOM, FOOD PREP, LAUNDRY ROOM, TOILET ROOMS, PUMP |
| | ROOM ETC.). |
| | ****RESPONSE NOTED, BUT SHEET P503 HAS NOT BEEN |
| | SUBMITTED. |
| | ******RESPONSE NOTED, BUT THE EMPLOYEE BREAKROOM, FOOD |
| | PREP, POOL TOILET ROOMS, POOL EQUIPMENT ROOM ETC DO NOT |
| | HAVE ISOMETRIC RISER DIAGRAMS THAT REFLECT THE FLOOR |
| | PLAN SUBMITTED. |
| | |
| | 32. SUBMIT A HORIZONTAL BUILDING WATER ISOMETRIC RISER |
| | DIAGRAM. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER |
| | ARRESTORS, (REQUIRED BY SECTION 604.9 FOR ICE MAKERS, |
| | WASH MACHINES, AND DISHWASHERS). |
| | ****RESPONSE NOTED, BUT A HORIZONTAL WATER ISOMETRIC |
| | HAS HOT BEEN SUBMITTED. ONLY VERTICAL RISERS ARE |
| | SUBMITTED. |
| | ******RESPONSE NOTED, BUT THE VERTICAL DROPS AND |
| | VERTICAL RISER SECTIONS WERE NOT INCLUDED. SHOW A |
| | COMPLETE RISER DIAGRAM.--THE RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN IN THE MEN'S POOL BATH & AT THE |
| | STUDIO UNITS ON THE WEST SIDE OF THE CORRIDOR. (NO HOT |
| | WATER TO UNITS).--EXPLAIN THE COLD WATER OUTSIDE |
| | THE BUILDING BY THE EMPLOYEE BREAK ROOM. PLEASE |
| | INDICATE WHERE THE LINE TERMINATES AND WHAT FIXTURE IT |
| | CONNECTS TO. |
| | |
| | 33. SUBMIT A HORIZONTAL BUILDING CONDENSATE ISOMETRIC |
| | RISER DIAGRAM AND VERTICAL RISER DIAGRAMS. SHOW ALL |
| | PIPE SIZES AND INDICATE THE TERMINATION POINT. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. SUBMIT |
| | HORIZONTAL AND VERTICAL RISERS AS REQUESTED. IF |
| | CONNECTING TO THE STORM LINE, A RELIEF VENT SHALL BE |
| | INSTALLED IN THE CONDENSATE LINE/LINES AS THEY EXIT THE |
| | BUILDING. |
| | ******RESPONSE NOTED, COMMENT NOT ADDRESSED. NO |
| | CONDENSATE RISERS WERE FOUND ON SHT P-501 AS INDICATED |
| | IN RESPONSE. THE CONDENSATE CAN NOT DRAIN WHERE IT WILL |
| | CAUSE A HAZARD OR A NUISANCE. PLEASE EXPLAIN "TO GRADE" |
| | IS THIS IN A PLANTED AREA, SIDEWALK, PARKING LOT OR |
| | WHAT? |
| | |
| | 34. INDICATE A NUMBER DESIGNATION FOR EACH RISER |
| | INCLUDING ALL SANT., WATER, STORM, CONDENSATE. (EXAMPLE |
| | SANT-1, SANT-2, RWL-1, RWL-2, CON-1, CON-2, W-1, W-2 |
| | ETC.). THIS WILL AID IN TRACKING ALL RISERS FROM THE |
| | UNDERGROUND PIPING THROUGH THE ROOF. SECTIONS |
| | 106.3.5.1.3 & SECTION 106.1.1.--INDICATE WHICH |
| | RISER IS TYPICAL OF WHICH RISER ISOMETRIC DIAGRAM. |
| | (EXAMPLE SANT-1 SANT-4 TYPICAL OF DETALI 4 SHT P401) -- |
| | INDICATE ROOM NUMBER EACH RISER CAN BE LOCATED. |
| | ****RESPONSE NOTED, BUT SHEET P503 HAS NOT BEEN |
| | SUBMITTED. |
| | ******RESPONSE NOTED, BUT RESPONSE DOES NOT ADDRESS THE |
| | WATER RISERS, STORM RISERS, OR CONDENSATE RISERS. |
| | |
| | 35. ROUTE PLANS TO THE DEPT. OF BUSINESS REGULATION, |
| | HOTEL & RESTURANT DIVISION FOR REVIEW PRIOR TO |
| | RESUBMITTING TO THE CITY FOR REVIEW. A MINIMUM OF TWO |
| | SETS OF PLANS, STAMPED BY DBPR AND TWO PAGE |
| | "WORKSHEETS" ATTACHED TO PLAN ARE REQUIRED. SECTION |
| | 102.2.1. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | ******RESPONSE NOTED, BUT THE TWO PAGE SPECIFICATION |
| | WORKSHEETS FOR THE HOMEWOOD REVIEW ARE ATTACHED TO THE |
| | SPRINGHILL PLANS, AND THE WORKSHEETS FOR THE SPRINGHILL |
| | PLANS ARE ATTACHED TO THE HOMEWOOD PLANS. PLEASE INSERT |
| | THE CORRECT SPECIFICATION WORKSHEETS IN THE CORRECT |
| | PLANS. |
| | |
| | 36. SHT A-101, A FOOD PREP AREA IS INDICATED. A GREASE |
| | INTERCEPTOR MAY BE REQUIRED. A MINIMUM 750 GAL. |
| | INTERCEPTOR IS REQUIRED. PLEASE CONTACT LMASSON, |
| | ENVIRONMENTAL COMPLIANCE MANAGER FOR SIZING OF THE |
| | GREASE INTERCEPTOR. CONTACT HER BY PHONE (561) |
| | 822-2271, FAX (561) 822-2279, OR E-MAIL |
| | [email protected]. |
| | ****RESPONSE NOTED, BUT NO APPROVAL FROM ENVIRONMENTAL |
| | COMPLIANCE HAS BEEN NOTED. I WILL PROCEED WITH AN |
| | INQUIRY AT THIS END. |
| | ******RESPONSE NOTED, BUT I AM STILL WAITING FOR THE |
| | APPROVAL FROM ENVIRONMENTAL COMPLIANCE. |
| | |
| | 37. OK |
| | |
| | *****NEW COMMENTS 3RD REVIEW***** |
| | |
| | |
| | 1B. PLANS SHALL BE SUBMITTED IN COMPLETE SETS. LOOSE |
| | SHEETS ARE NOT ACCEPTABLE. SECTION 106.1. PLEASE SUBMIT |
| | PLANS IN COMPLETE SETS. |
| | |
| | 2B. SHT G-001 NOT ALL SHEETS SHOWN ON THE DRAWING INDEX |
| | HAVE BEEN SUBMITTED, AND SOME SHEETS ARE OUT OF ORDER. |
| | PLEASE CORRELATE THE SHEETS SUBMITTED WITH THE DRAWING |
| | INDEX. SECTION 106.1.1. |
| | |
| | 3B. SHT AC-103 A URINAL IS REQUIRED IN THE MEN'S POOL |
| | TOILET ROOM. TABLE 424.1.6.1. PLEASE SHOW REQUIRED |
| | URINAL. |
| | |
| | 4B. SHT P101A THE SANITARY BUILDING DRAIN DOES NOT |
| | REFLECT THE UNIT FLOOR PLAN, NOR DOES IT REFLECT THE |
| | SANITARY RISER DIAGRAM. PLEASE CORRELATE. SECTION |
| | 106.1.1. THE UNITS SHOW THE PIPING TO THE OPPOSITE END |
| | OF THE TUBS & SHOWERS.--CONNECTIONS TO THE SANITARY |
| | BUILDING DRAIN FROM THE ELEVATOR SUMPS IS NOT APPROVED. |
| | SECTION 301.6. PLEASE DELETE FROM RISER AND FLOOR PLAN. |
| | --IDENTIFY ALL RISERS.--KEY NOTES #3 STATES "NOT |
| | USED", BUT KEY NOTE #3 IS SHOWN ON THE FLOOR PLAN ABOUT |
| | 6 TIMES. PLEASE CLARIFY. |
| | |
| | 5B. SHT P101A THE SANITARY BRANCH CONNECTIONS FROM THE |
| | FLOOR DRAINS IN THE POOL EQUIPMENT ROOM ARE SHOWN |
| | CONNECTING AGAINST THE FLOW. THIS IS NOT APPROVED PER |
| | SECTION 706.3. PLEASE SHOW FITTING INSTALLATION SO THAT |
| | IS GUIDES THE SEWAGE AND WASTE IN THE DIRECTION OF |
| | FLOW. |
| | |
| | 6B. SUBMIT THE ISOMETRIC RISER DIAGRAMS FOR THE |
| | SANITARY AND WATER FOR THE POOL TOILET ROOMS, & FLOOR |
| | DRAINS IN THE EQUIPMENT ROOM, STORAGE ROOM. SECTION |
| | 106.3.5.1.3(3)(4)(6)(10)(13). |
| | |
| | 7B. SUBMIT A UNIT PLAN FOR THE ACCESSIBLE STUDIO. (THIS |
| | IS DIFFERENT FROM THE STANDARD STUDIO). A RISER DIAGRAM |
| | TO REFLECT THE FLOOR PLAN IS REQUIRED. SECTION |
| | 106.3.5.1.3(4)(13). |
| | |
| | 8B. SHT P101B THREE BRANCH CONNECTIONS ARE SHOWN |
| | CONNECTING AGAINST THE FLOW. THIS IS NOT APPROVED PER |
| | SECTION 706.3. PLEASE SHOW FITTING INSTALLATION SO THAT |
| | IS GUIDES THE SEWAGE AND WASTE IN THE DIRECTION OF |
| | FLOW. |
| | |
| | 9B. SHT P101B THE SANITARY DRAIN PIPING DOES NOT |
| | REFLECT THE UNIT PIPING. (TUBS & SHOWERS SHOW SANT. |
| | PIPING TO OPPOSITE END OF THE FIXTURES).--THE |
| | ELEVATOR SUMP PUMPS SHALL NOT CONNECT TO THE SANITARY |
| | BUILDING DRAIN. SECTION 301.6.--2-WAY CLEANOUTS ARE |
| | REQUIRED AT THE ENTRANCE AND EXITING PIPING OF THE |
| | GREASE INTERCEPTOR AND NEAR THE JUNCTION OF THE KITCHEN |
| | DRAIN & SEWER. SECTION 708.3.5 & UTILITY STANDARD FOR |
| | GREASE INTERCEPTORS. |
| | |
| | 10B. SHT P101C PIPING IS NOT SHOWN TO STUDIOS WEST OF |
| | THE CORRIDOR.--KEY NOTES #2 STILL INDICATES 7" WC |
| | INLET PRESSURE. 11" TO 14", (1/2PSI) REQUIRED TO |
| | REFLECT CHANGES IN THE NATURAL GAS SYSTEM.-- INDICATE |
| | WHERE THE COLD WATER SUPPLY OUTSIDE THE EMPLOYEE BREAK |
| | ROOM TERMINATES OR WHAT FIXTURE IT SUPPLIES. SECTION |
| | 106.1.1. |
| | |
| | 11B. SHT P101D NO HOT & COLD PIPING IS INDICATED FOR |
| | THE STUDIOS. PLEASE SHOW PIPING. SECTION 106.3.5.1.3 |
| | |
| | 12B. SUBMIT A STORM ISOMETRIC RISER DIAGRAM FOR THE |
| | HORIZONTAL BUILDING STORM DRAIN. SHOW ALL VERTICAL |
| | RISERS FROM THE BUILDING DRAIN TO THE ROOF DRAINS. SHOW |
| | ALL PIPE SIZE, OFFSETS, CLEANOUTS REQUIRED BY SECTION |
| | 1101.8 AND INDICATE SQUARE FOOTAGE AS IT ACCUMULATES IN |
| | THE SYSTEM. SECTION 106.3.5.1.3 (7)(13). |
| | |
| | 13B. SHTS P104 & P104A SHOWS 2-1/2" FDV. PLEASE CLARIFY |
| | WHAT SYSTEM THIS PIPING IS FOR. SECTION 106.1.1. |
| | |
| | 14B. SHT P401 SOME INFORMATION AT THE BOTTOM OF THE |
| | SHEET IS NOT LEGIBLE AND NO DETAIL NUMBERS ARE |
| | INDICATED. PLEASE CLARIFY. SECTION 106.1.1.--KEY |
| | NOTES #3 STATES "NOT USED", BUT #3 IS SHOWN ON THE |
| | FLOOR PLAN.--KEY NOTES #6 STATES "NOT USED", BUT |
| | #6 IS SHOWN ON THE FLOOR PLAN.--KEY NOTES #11 IS |
| | SHOWN ON THE FLOOR PLAN, BUT NOT INDICATED ON THE KEY |
| | NOTES INDEX. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 15B. SHT P401 SUBMIT ISOMETRIC RISER DIAGRAMS FOR EACH |
| | UNIT. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER |
| | ARRESTORS REQUIRED BY SECTION 604.9 ETC TO REFLECT THE |
| | FLOOR PLAN. SECTION 106.3.5.1.3(3)(10)(13). |
| | |
| | 16B. SHT P402 SUBMIT ISOMETRIC RISER DIAGRAMS FOR EACH |
| | UNIT. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER |
| | ARRESTORS REQUIRED BY SECTION 604.9 ETC TO REFLECT THE |
| | FLOOR PLAN. SECTION 106.3.5.1.3(3)(10)(13). |
| | |
| | 17B. SHT P402 KEY NOTES #6 STATES "NOT USED", BUT IS |
| | INDICATED IN DETAILS #1 & #3. CLARIFY.--DETAIL#4 |
| | SHOWS KEY NOTES #5 AT THE WATER CLOSET AND IS INDICATED |
| | AS HOT & COLD. CLARIFY.--DETAIL #1 KEY NOTE #2 |
| | STATES "NOT USED", BUT IS INDICATED AT SHOWER WITH KEY |
| | NOTE #6. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 18B. SHT P403 INFORMATION AT THE BOTTOM OF THE SHEET IS |
| | NOT LEGIBLE. PLEASE CLARIFY. SECTION 106.1.1.--KEY |
| | NOTES #14 DISHWASHER SHALL DISCHARGE TO A FLOOR SINK, |
| | NOT A FLOOR DRAIN & SHALL DRAIN TO THE SANITARY SYSTEM, |
| | NOT THE GREASE SYSTEM. SECTION 802.3 AND ARTICLE III |
| | SECTION 90-124(7)(B).--KEY NOTES #15 DRIP LEG NOT |
| | SHOWN.--DETAIL #4 FLOOR DRAIN TO BE ACCESSIBLE. |
| | SECTION 708.9. |
| | |
| | 19B. SHT P403 SUBMIT ISOMETRIC RISER DIAGRAMS FOR THE |
| | SANITARY AND WATER FOR THE KITCHEN PIPING AND FOR THE |
| | MEN'S AND WOMEN'S TOILET ROOMS. SECTION 106.3.5.1.3 |
| | (3)(4)(6)(10)(13). |
| | |
| | 20B. SHT P404 KEY NOTES 5, 8, 11, & 13 WERE NOT FOUND |
| | IN DETAIL #1. PLEASE CLARIFY.--KEY NOTE #3 DRIP |
| | LEG SHALL BE INSTALLED IN THEVERTICAL POSITION. SHOWN |
| | AS HORIZONTAL.SECTIONS 106.1.1 & 408.2. |
| | |
| | 21B. SHT P501 DETAIL/RISER #1 DOES NOT REFLECT THE |
| | FLOOR PLAN AT FIXTURES P6 & P8.--DETAIL /RISER #5 |
| | DOES NOT REFLECT SHT P101A SAN #1 & INDICATES PASSING |
| | THRU THE 1ST FLOOR TWICE. PLEASE CLARIFY. SECTION |
| | 106.1.1.--DETAIL/RISER 3 INDICATES GUEST |
| | LAUNDRY/MAINTENANCE. THIS IS NOT FOUND ON THE FLOOR |
| | PLAN. PLEASE CLARIFY. |
| | |
| | 22B. SHT P502 THE WATER RISER DIAGRAMS DO NOT REFLECT |
| | THE FLOOR PLANS. NOT ALL FLOOR PLANS ARE SHOWN. PLEASE |
| | SUBMIT RISERS TO REFLECT THE FLOOR PLAN AND SUBMIT A |
| | FLOOR PLAN FOR EACH UNIT TYPE. SECTION 106.3.5.1.3. |
| | |
| | 23B. SHT P503 THE SANITARY RISER ISOMETRIC DOES NOT |
| | REFLECT THE FLOOR PLAN.--THE GREASE INTERCEPTOR & |
| | PIPING TO THE KITCHEN IS NOT SHOWN.--THE TOILET |
| | ROOM ARE NOT SHOWN.--ONLY ONE FLOOR DRAIN IS SHOWN |
| | ON THE FLOOR PLAN, BUT TWO ARE SHOWN ON THE RISER.-- |
| | 3" FLOOR DRAIN REQUIRES A VENT.--NO RISER DETAIL #6 |
| | WAS FOUND.--BOTH ELEVATOR SUMP PUMPS SHALL NOT |
| | CONNECT TO THE SANITARY BUILDING DRAIN.--THE BRANCH |
| | LINES TO THE STUDIO UNITS DO NOT REFLECT THE FLOOR |
| | PLAN. SECTIONS 106.1.1, 106.3.5.1.3, 901.2.1, 301.6. |
| | |
| | 24B. SHT P503 THE BUILDING DRAIN LINE SHOWS TWO |
| | BUILDING DRAINS FROM THE BUILDING ON THE RISER DIAGRAM, |
| | BUT ONLY ONE ON THE FLOOR PLAN.--THERE ARE EXTRA |
| | BRANCH LINES, ONE FOR 40DFU'S THAT THERE IS NO RISER TO |
| | REFLECT BACK TO BACK WATER CLOSETS.--SOME BRANCH |
| | CONNECTIONS TO THE BUILDING DRAIN DO NOT REFLECT THE |
| | FLOOR PLAN.--RISER DOES NOT REFLECT THE FLOOR PLAN |
| | BY THE LAUNDRY/EMPLOYEE BREAK ROOM. PLEASE CORRELATE. |
| | SECTION 106.1.1. |
| | |
| | 25B. SHT P504 LABELED WASTE & VENT RISER DIAGRAMS.-- |
| | WATER MAIN ISOMETRIC RISER DIAGRAM DOES NOT SHOW THE |
| | DROPS TO THE FIXTURES, OR THE RISERS TO THE UPPER |
| | LEVELS.--DOES NOT REFLECT THE FLOOR PLAN AT THE |
| | MENS POOL TOILET ROOM & AT THE STUDIO UNITS WEST OF THE |
| | CORRIDOR. PLEASE INDICATE WHERE THE COLD WATER LINE |
| | TERMINATES SHOWN OUTSIDE THE BUILDING BY THE EMPLOYEE |
| | BREAK ROOM AREA. PLEASE CLAIRFY. SECTION 106.1.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | -PLEASE RESUBMIT ONE SET OF OLD SHEETS |
| | FOR COMPARISON. |
| | |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |