Date Text
2007-10-24 14:53:36*****DENIED*****
  
 THE FOLLOWING COMMENTS FORM THE PREVIOUS 22 STILL NEED
 TO BE ADDRESSED:
  
 06. ON THE APPROPIATE EXTERIOR ELEVATION FRONTING
 METROCENTRE BOULEVARD EAST,POST THE NUMERICAL ADDRESS
 ON THE BUILDING.AS PER WEST PALM BEACH CODE, THOSE
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH.COULD NOT LOCATE NUMERICAL ADDRESS
 ON SHEET AC-101 AS PER YOUR RESPONSE LETTER; PLEASE
 COMPLY
  
 18.PLEASE PROVIDE A LAYOUT OF THE FIRE SPRINKLER
 SYSTEM INDEPENDENT OF THE PLUMBING SHEETS.INCLUDE THE
 LOCATION OF THE FIRE DEPARTMENT CONNECTION(S) AND THE
 DOUBLE DETECTOR CHECK VALVE ASSEMBLY.COULD NOT
 LOCATE FIRE DEPARTMENT CONNECTIONS (FDC)AND THE
 DOUBLE DETECTOR CHECK VALVE ASSEMBLY.ALSO, NO PROJECT
 SITE ADDRESS IN THE TITLE BLOCK OF THE FIRE SPRINKLER
 SHEETS
  
 19.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK
 ARE REQUIRED FOR THE DOUBLE CHECK DETECTOR VALVE
 ASSEMBLY.ADD COMMENT TO THE FIRE SPRINKLER AND/OR
 FIRE ALARM PLAN SHEET
  
 20.KNOX LOCKING CAPS WILL BE REQUIRED ON FIRE
 DEPARTMENT CONNECTIONS (FDC).CONTACT WEST PALM BEACH
 FIRE PREVENTION AT 561-804-4724 FOR KNOX APPLICATIONS.
 ADD COMMENT TO THE APPROPIATE FIRE SPRINKLER PLAN
 SHEET
  
 22.SIGNS REQUIRED IN STAIRWELLS INDICATING FLOOR
 IDENTITY.ADD COMMENT TO SHEET A-701; PLEASE COMPLY
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW