| 2007-09-30 14:05:17 | 2007-09-30 14:05:17 |
| | |
| | ** DENIED 3RD REVIEW *** |
| | |
| | HOMEWOODSUITES |
| | |
| | ** PLEASE SEE THERE ARE COMMENTS FROM PREVIOUS REVIEW |
| | WHICH ARE STILL IN NEED OF ADDRESSING. |
| | |
| | ** PLEASE SEE THERE ARE SOME NEW COMMENTS BASED ON |
| | PLANS AND/OR REVISIONS TO PLANS WHICH INFORMATION IS |
| | ONLY NOW BEING SUBMITTED. DUE TO CHANGES AND |
| | INFORMATION WHICH WAS NOT ON PREVIOUS PLANS OR REVIEW, |
| | THESE ITEMS COULD NOT HAVE COMMENTED ON AS SOME ITEMS |
| | AND INFORMATION IS NEW TO PLANS AND/OR DESIGN. THESE |
| | ITEMS WILL BE CLEARLY NOTED. |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS NOTE #1 WHICH REQUESTED |
| | FOR THE PRODUCT APPROVALS ETC NOT TO BE ATTACHED TO |
| | ROLLS. THIS WAS OK, AND THESE WERE NOT ATTACHED HOWEVER |
| | OF THE ROLLS OF PLANS THIS REVIEWER REVIEWED, ALL |
| | SHEETS IN ROLLS WERE LOOSE AND NOT ATTACHED INTO |
| | SECURED ROLLS. |
| | PLEASE DO NOT SUBMIT ROLLS OF PLANS IN WHICH THE SHEETS |
| | ARE LOOSE AND NOT ATTACHED.THIS ROLL WERE SECURED BY |
| | THIS OFFICE. |
| | FBC ADMIN SECTION 106.1, 106.5 ETC. |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #2 WITH |
| | RESPECT TO SIGNATURE VERIFICATION LETTER(S). THIS WAS |
| | SUBMITTED HOWEVER WAS NOT SEALED AS PREVIOUSLY |
| | REQUESTED. |
| | THIS CAN BE SUBMITTED AT ANY TIME. |
| | FS 471.025, 481.025 AND FAC 61G15-23.002, 61G1-16.004 |
| | |
| | THIS WAS COMPLETELY STATED ON PREVIOUS NOTE #2. |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS NOTE #4 WHICH MENTIONED |
| | THE MISSING CERTIFICATE OF AUTHORIZATION NUMBER. AS |
| | PLANS WERE REVISED REMOVING ARCHITECTURAL FIRM MOST |
| | SHEETS ARE CORRECT HOWEVER PLEASE SEE THAT SOME SHEETS |
| | IN SOME SETS STILL CONTAIN PFVS (HOMEWOOD) AND COVER |
| | SHEETS (SPRINGHILL) STILL CALL FOR PFVS ARCHITECTS |
| | INC. |
| | |
| | PLEASE SEE SOME SHEETS STILL INDICATE FIRM ON SHEETS |
| | SUCH AS *S* SHEETS. |
| | THIS REVIEWER HAS SPOKEN WITH MR. KEY AND IT IS THE |
| | UNDERSTANDING THE FIRM NOW HAS OBTAINED THE REQUIRED |
| | LICENSING THROUGH THE STATE. PLEASE KNOW THAT ALL |
| | INFORMATION ON TITLE BLOCKS MAY BE REVISED AND |
| | CORRECTED ONCE ALL REVIEWS ARE COMPLETED AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS. |
| | PLEASE SEE FS481.219, FAC 61G1-16.004 |
| | |
| | 4) NOTE: THIS IS A NEW COMMENT: PLEASE SEE THE SEAL |
| | WHICH IS NOW BEING USED ON ALL THREE SETS FOR BOTH |
| | HOTELS FOR THE ARCHITECT OF RECORD MR. GREG PORTMAN IS |
| | NO LONGER ACCEPTED IN THE STATE OF FLORIDA. THE |
| | PREVIOUS ORIGINAL SHEETS DO CONTAIN THE CORRECT SEAL, |
| | ALTHOUGH AS NOTED ABOVE IN NOTE#3, THE TITLE BLOCKS |
| | NEED TO BE ADDRESSED. |
| | PLEASE SEE RULING FAC61G1-16.002 WHICH CHANGED SEVERAL |
| | YEARS AGO, WHICH NOW REQUIRES A MINIMUM SEAL SIZE OF |
| | 2INCHES. PLEASE SEE THE NEW SHEETS NOW SUBMITTED |
| | CONTAINS AN OLD SEAL. |
| | IF THIS WAS THE ONLY COMMENT ON PLANS, THE ARCHITECT OF |
| | RECORD WOULD BE ABLE TO COME INTO THIS OFFICE AND |
| | RE-SIGN, DATE AND SEAL PLANS. |
| | |
| | 5) NOTE: PLEASE SEE PREVIOUS NOTE #12 WITH RESPECT TO |
| | FBC CHAPTER 13. |
| | |
| | A) PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED |
| | STILL NEED SOME COORDINATION WITH ELECTRICAL LIGHTING |
| | ON PLANS. PLEASE THE INPUT DATA REPORT WHICH WILL BE |
| | NOTED AS IDR ON THE FOLLOWING DOES NOT CORRELATE WITH |
| | ALL LIGHTING ON PLANS AND FIXTURE LIGHTING LEGEND. |
| | PLEASE SEE SOME OF THE FOLLOWING EXAMPLES: EXTERIOR |
| | LIGHTING WHICH IS ON PLANS DOES NOT MATCH WITH THE IDR |
| | FOR THE SAME NUMBER OF FIXTURES, TYPE(S) AND WATTAGE. |
| | PLEASE SEE THE FIXTURES LISTED ON THE IDR ARE 250WATT, |
| | 70W AND 70W, YET THE FIXTURES ON PLANS ARE OD- 70W, |
| | OA-450W, OC-150W ETC. |
| | PLEASE SEE THE *K* FIXTURES FOR EXAMPLE WHICH ARE NOT |
| | ON THE IDR FOR EXTERIOR. |
| | PLEASE SEE THE OE FIXTURES ON PLANS WHICH THERE ARE 25 |
| | FIXTURES YET THE CALCULATIONS DO NOT INCLUDE THESE. |
| | PLEASE KNOW THESE ARE NOTED FOR SOME OFTHE ITEMS. |
| | |
| | B) PLEASE SEE THE INTERIOR LIGHTING ON PLANS NEEDS TO |
| | COORDINATE WITH THE IDR. PLEASE SEE FOR EXAMPLE: |
| | STORAGE 1268, 142, MEETING ROOM, PUMP ROOM, SUITE SHOP, |
| | REGISTRATION AREA, WATER HEATERS ROOM 244, AND OTHER |
| | STORAGE ROOMS. |
| | PLEASE KNOW THESE ARE ONLY SOME ROOMS/LOCATIONS WHICH |
| | DO NOT CORRELATE. |
| | PLEASE CLARIFY THE WATTAGES AS SHOWN ON THE FIXTURE |
| | LEGEND COMPARED TO THE WATTAGE ENTERED ON THE IDR. SOME |
| | SHOW WHAT WOULD BE 3-32W BULBS AT 96WATTS, YET THE IDR, |
| | SHOW A LOWER NUMBER FOR THIS SAME FIXTURE. SOME |
| | ACTUALLY SHOW A HIGHER NUMBER AS 100WATTS? |
| | PLEASE SEE FIXTURES B, A, A2 ETC, 59WATTS ON THE IDR, |
| | 51W ON FIXTURE LEGEND. |
| | |
| | C) PLEASE CLARIFY HOW THE METHOD OF CONTROL IS BEING |
| | SHOWN AS *MANUAL ON/OFF* WHEN MANY OF THESE ARE |
| | ACTUALLY AUTOMATED CONTROLS? |
| | PLEASE ADJUST METHOD OF CONTROLS FOR MANY AS LISTED ON |
| | THE IDR. |
| | |
| | ** PLEASE SEE THAT THE ABOVE IS SOME EXAMPLES OF |
| | COORDINATION WHICH NEEDS TO TAKE PLACE BETWEEN THE |
| | ELECTRICAL LIGHTING ON PLANS AND THE LIGHTING WHICH IS |
| | PLACE IN THE INPUT DATA REPORT. THIS OFFICE CAN NOT |
| | EMPHASIZE ENOUGH THE NEED FOR COORDINATION. |
| | |
| | D) PLEASE CLARIFY RECEPTACLES WHICH ARE SHOWN FOR ROOMS |
| | ARE SWITCHED OR PROVIDE POWER TO LIGHTING SUCH AS TABLE |
| | LAMPS/FLOOR LAMPS ETC. AS PLANS DO INDICATE WHAT |
| | APPEARS TO BE LAMPS ETC IN ROOMS THEN ANY OF THESE |
| | WHICH ARE PLUGGED INTO THESE RECEPTACLES WOULD BE |
| | REQUIRED TO BE PART OF THE ROOM LIGHTING CONTROLS. THIS |
| | WOULD REQUIRE THE SAME CIRCUITS FOR RECEPTACLES OR |
| | CONTROLS INSTALLED AND PROVIDING HALF SWITCHED |
| | RECEPTACLES. |
| | PLEASE SEE 13-415.1.ABC .1.1, .1.2 AND .1.3 |
| | |
| | E) NOTE: PLEASE SEE THE OWNER AGENT IS TO BE SIGNED ON |
| | THE ENERGY CALCULATIONS CERTIFICATION SHEET. THE |
| | PRINTED NAME OF THE DEVELOPER IS NOT A CERTIFICATION. |
| | 13-103.1.1.1 |
| | |
| | 6) NOTE: PLEASE SEE PREVIOUS NOTE #15 AS THIS REQUESTED |
| | ALL HORN, STROBE OR HORN/STROBE DEVICESTO INDICATE |
| | THE MINIMUM LEVELS FOR ADA PER FBC 11-4.28.1, .2 AND |
| | .3(4). THE RESPONSE LETTER MENTIONS THIS WAS DONE AT |
| | ALL LOCATIONS ON PLANS HOWEVER PLEASE CLARIFY WHERE |
| | THESE LEVELS ARE FOR THE DEVICES LOCATED IN THE ROOMS |
| | WHICH ARE ON E-206. PLEASE SEE ONLY SOME DEVICES ARE |
| | SHOWN AT LOCATIONS REQUIRED AND ONLY SOME OF THESE |
| | DEVICES WHICH ARE SHOWN INDICATE THE LEVELS. PLEASE SEE |
| | ROOM DOUBLE QUEEN ACC WHICH IS MISSING CD FOR LIVING |
| | ROOM AREA. |
| | PLEASE SEE TWO BEDROOM ACC WHICH ONLY INDICATES ONE |
| | DEVICE IN BATHROOM? |
| | ONLY NOTED SOME AREAS/LOCATIONS. |
| | PLEASE SEE THE NOTES ON E-502 WHICH WERE CORRECTED FOR |
| | THE CANADIAN CODE HOWEVER REFERENCES TO THE REQUIRED |
| | FLORIDA BUILDING CODE COULD NOT BE FOUND. PLEASE SEE |
| | CHAPTER 11 OF THE FBC IS SUBSTANTIALLY MORE RESTRICTIVE |
| | THAN THE NFPA-72 AS NOTED. |
| | |
| | 7) NOTE: PLEASE SEE PREVIOUS WHICH REQUESTED FOR ALL |
| | MANUFACTURES SPECS/CUT SHEETS TO BE SUBMITTED FOR THE |
| | FIRE PUMP, FIRE PUMP CONTROLLER ETC. |
| | PLEASE SEE THE SPECS/CUT SHEETS WERE SUBMITTED HOWEVER |
| | COORDINATION WITH PLANS AND LISTING OF ASSEMBLY COULD |
| | NOT BE VERIFIED. |
| | PLEASE SEE THE FPC IS LISTED WITH A DIFFERENT |
| | MANUFACTURE THAN THE PUMPS, PLEASE BE SURE ALL ITEMS |
| | ARE LISTED ASSEMBLIES AS REQUIRED. NEC 110.3, 90.7. |
| | PLEASE BE SURE TO COORDINATE WITH INFORMATION TO BE |
| | PROVIDED ON FIRE SPRINKLER PLANS AND ANY REVIEW |
| | COMMENTS FROM THE FIRE MARSHAL. |
| | NOTE #22 FROM PREVIOUS REVIEW IS BEING LEFT BELOW. |
| | |
| | |
| | 8) NOTE: PLEASE SEE RISER IS SHOWING AN *EQUIPMENT |
| | GROUNDING CONDUCTOR* FROM FPL TO THE FIRST MEANS OF |
| | DISCONNECT FRO THE FIRE PUMP SERVICE. |
| | PLEASE SEE 250.6, 250.24 AS THIS CREATES OBJECTIONABLE |
| | CURRENT AND IS NOT PERMITTED. |
| | |
| | 9) NOTE: PLEASE SEE THERE ARE STILL RECEPTACLES MISSING |
| | PER 210.52 FOR 2FT, 6FT AND 12FT RULES. |
| | PLEASE SEE SOME UNITS/LOCATIONS ARE GIVEN FOR |
| | EXAMPLES: |
| | PLEASE SEE DOUBLE QUEEN, AND TWO BEDROOM SUITES 2FT OF |
| | WALL. |
| | PLEASE SEE TWO BEDROOM SLEEPING ROOM WITH TWO DOUBLE |
| | BEDS WHICH HAS MORE THAN 12FT OF WALL SPACE WITHOUT |
| | RECEPTACLE. |
| | PLEASE SEE TWO BEDROOM UNITS, BOTH TYPES AND DOUBLE |
| | QUEENS BOTH TYPES AS THESE ARE MISSING RECEPTACLES |
| | WITHIN 6FT OF DOORWAY. THE STUDIO AND KING DOES CONTAIN |
| | A RECEPTACLE WITHIN 6FT OF DOORWAY GOING INTO THE |
| | BEDROOM BUT THESE OTHERS. |
| | PLEASE SEE 210.52 AND ADJUST. THESE WERE REDLINED ON |
| | PLANS. |
| | |
| | 10) NOTE: PLEASE CLARIFY PHOTO-METRICS AS SUBMITTED. |
| | THE STAIRS CONTAIN A TYPE *S* FIXTURE WHICH FIXTURE |
| | LEGEND INDICATES THIS AS A BATTERY BACK UP TYPE OF |
| | FIXTURE. HOW IS IT THAT THAT FOOT CANDLE LEVELS DROPS |
| | SUBSTANTIALLY? EVEN IF THE FIXTURE ONLY OPERATES ONLY |
| | ONE BULB, THIS WOULD ONLY BE HALF THE NORMAL LIGHTING |
| | OUTPUT. PLEASE EXPLAIN THIS SCENARIO. |
| | NFPA-101 7.8.1.3, 7.9.2.2 |
| | ** THIS IS THE SAME FOR BOTH BUILDINGS AND ALL |
| | LOCATIONS WHICH CONTAIN THE SAME SITUATION. HOW DOES |
| | THE LIGHTING DECREASE AS SHOWN? |
| | |
| | 11) NOTE: PLEASE VERIFY WHAT APPEARS TO BE A WATER |
| | HEATER DISCONNECT H1B-6 IN FIRE PUMP ROOM. |
| | PLEASE SEE NFPA-20 FOR EQUIPMENT WHICH IS PERMITTED IN |
| | THE FIRE PUMP ROOM. |
| | THIS IS NOT FOUND TO BE PERMITTED IN THIS ROOM. |
| | |
| | 12) NOTE: PLEASE SEE SHEET E-205 UNIT DOUBLE QUEEN |
| | WHICH SEEMS TO BE MISSING OCTAGONAL NOTE #6 FROM THE |
| | UNIT FOR NOTED ARC FAULT PROTECTION. |
| | (PANEL DOES CORRECT THIS ON CIRCUIT). |
| | |
| | |
| | |
| | |
| | ** PLEASE KNOW ONCE ALL REVIEWS ARE DONE, ONE ROLL MAY |
| | BE RETAINED BY THIS OFFICE DUE TO REPEAT COMMENTS FOR |
| | CODE COMPLIANCE AND PREVIOUS NOTE TO FS 553.80(2)(B). |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-09-30 11:33:04 | |
| | |
| | IN PROGRESS |
| 2007-09-28 07:08:21 | 2007-09-28 07:08:21 |
| | |
| 2007-09-27 20:02:53 | 2007-09-27 20:02:53 |
| | |
| | ONE SET IN ELECTRICAL FOR REVIEW. |