Plan Review Notes
Plan Review Notes For Permit 06111071
Permit Number 06111071
Review Stop E
Sequence Number 3
Notes
Date Text
2007-09-30 14:05:172007-09-30 14:05:17
  
 ** DENIED 3RD REVIEW ***
  
 HOMEWOODSUITES
  
 ** PLEASE SEE THERE ARE COMMENTS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING.
  
 ** PLEASE SEE THERE ARE SOME NEW COMMENTS BASED ON
 PLANS AND/OR REVISIONS TO PLANS WHICH INFORMATION IS
 ONLY NOW BEING SUBMITTED. DUE TO CHANGES AND
 INFORMATION WHICH WAS NOT ON PREVIOUS PLANS OR REVIEW,
 THESE ITEMS COULD NOT HAVE COMMENTED ON AS SOME ITEMS
 AND INFORMATION IS NEW TO PLANS AND/OR DESIGN. THESE
 ITEMS WILL BE CLEARLY NOTED.
  
 1) NOTE: PLEASE SEE PREVIOUS NOTE #1 WHICH REQUESTED
 FOR THE PRODUCT APPROVALS ETC NOT TO BE ATTACHED TO
 ROLLS. THIS WAS OK, AND THESE WERE NOT ATTACHED HOWEVER
 OF THE ROLLS OF PLANS THIS REVIEWER REVIEWED, ALL
 SHEETS IN ROLLS WERE LOOSE AND NOT ATTACHED INTO
 SECURED ROLLS.
 PLEASE DO NOT SUBMIT ROLLS OF PLANS IN WHICH THE SHEETS
 ARE LOOSE AND NOT ATTACHED.THIS ROLL WERE SECURED BY
 THIS OFFICE.
 FBC ADMIN SECTION 106.1, 106.5 ETC.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #2 WITH
 RESPECT TO SIGNATURE VERIFICATION LETTER(S). THIS WAS
 SUBMITTED HOWEVER WAS NOT SEALED AS PREVIOUSLY
 REQUESTED.
 THIS CAN BE SUBMITTED AT ANY TIME.
 FS 471.025, 481.025 AND FAC 61G15-23.002, 61G1-16.004
  
 THIS WAS COMPLETELY STATED ON PREVIOUS NOTE #2.
  
 3) NOTE: PLEASE SEE PREVIOUS NOTE #4 WHICH MENTIONED
 THE MISSING CERTIFICATE OF AUTHORIZATION NUMBER. AS
 PLANS WERE REVISED REMOVING ARCHITECTURAL FIRM MOST
 SHEETS ARE CORRECT HOWEVER PLEASE SEE THAT SOME SHEETS
 IN SOME SETS STILL CONTAIN PFVS (HOMEWOOD) AND COVER
 SHEETS (SPRINGHILL) STILL CALL FOR PFVS ARCHITECTS
 INC.
  
 PLEASE SEE SOME SHEETS STILL INDICATE FIRM ON SHEETS
 SUCH AS *S* SHEETS.
 THIS REVIEWER HAS SPOKEN WITH MR. KEY AND IT IS THE
 UNDERSTANDING THE FIRM NOW HAS OBTAINED THE REQUIRED
 LICENSING THROUGH THE STATE. PLEASE KNOW THAT ALL
 INFORMATION ON TITLE BLOCKS MAY BE REVISED AND
 CORRECTED ONCE ALL REVIEWS ARE COMPLETED AND PLANS ARE
 PICKED UP FOR CORRECTIONS.
 PLEASE SEE FS481.219, FAC 61G1-16.004
  
 4) NOTE: THIS IS A NEW COMMENT: PLEASE SEE THE SEAL
 WHICH IS NOW BEING USED ON ALL THREE SETS FOR BOTH
 HOTELS FOR THE ARCHITECT OF RECORD MR. GREG PORTMAN IS
 NO LONGER ACCEPTED IN THE STATE OF FLORIDA. THE
 PREVIOUS ORIGINAL SHEETS DO CONTAIN THE CORRECT SEAL,
 ALTHOUGH AS NOTED ABOVE IN NOTE#3, THE TITLE BLOCKS
 NEED TO BE ADDRESSED.
 PLEASE SEE RULING FAC61G1-16.002 WHICH CHANGED SEVERAL
 YEARS AGO, WHICH NOW REQUIRES A MINIMUM SEAL SIZE OF
 2INCHES. PLEASE SEE THE NEW SHEETS NOW SUBMITTED
 CONTAINS AN OLD SEAL.
 IF THIS WAS THE ONLY COMMENT ON PLANS, THE ARCHITECT OF
 RECORD WOULD BE ABLE TO COME INTO THIS OFFICE AND
 RE-SIGN, DATE AND SEAL PLANS.
  
 5) NOTE: PLEASE SEE PREVIOUS NOTE #12 WITH RESPECT TO
 FBC CHAPTER 13.
  
 A) PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED
 STILL NEED SOME COORDINATION WITH ELECTRICAL LIGHTING
 ON PLANS. PLEASE THE INPUT DATA REPORT WHICH WILL BE
 NOTED AS IDR ON THE FOLLOWING DOES NOT CORRELATE WITH
 ALL LIGHTING ON PLANS AND FIXTURE LIGHTING LEGEND.
 PLEASE SEE SOME OF THE FOLLOWING EXAMPLES: EXTERIOR
 LIGHTING WHICH IS ON PLANS DOES NOT MATCH WITH THE IDR
 FOR THE SAME NUMBER OF FIXTURES, TYPE(S) AND WATTAGE.
 PLEASE SEE THE FIXTURES LISTED ON THE IDR ARE 250WATT,
 70W AND 70W, YET THE FIXTURES ON PLANS ARE OD- 70W,
 OA-450W, OC-150W ETC.
 PLEASE SEE THE *K* FIXTURES FOR EXAMPLE WHICH ARE NOT
 ON THE IDR FOR EXTERIOR.
 PLEASE SEE THE OE FIXTURES ON PLANS WHICH THERE ARE 25
 FIXTURES YET THE CALCULATIONS DO NOT INCLUDE THESE.
 PLEASE KNOW THESE ARE NOTED FOR SOME OFTHE ITEMS.
  
 B) PLEASE SEE THE INTERIOR LIGHTING ON PLANS NEEDS TO
 COORDINATE WITH THE IDR. PLEASE SEE FOR EXAMPLE:
 STORAGE 1268, 142, MEETING ROOM, PUMP ROOM, SUITE SHOP,
 REGISTRATION AREA, WATER HEATERS ROOM 244, AND OTHER
 STORAGE ROOMS.
 PLEASE KNOW THESE ARE ONLY SOME ROOMS/LOCATIONS WHICH
 DO NOT CORRELATE.
 PLEASE CLARIFY THE WATTAGES AS SHOWN ON THE FIXTURE
 LEGEND COMPARED TO THE WATTAGE ENTERED ON THE IDR. SOME
 SHOW WHAT WOULD BE 3-32W BULBS AT 96WATTS, YET THE IDR,
 SHOW A LOWER NUMBER FOR THIS SAME FIXTURE. SOME
 ACTUALLY SHOW A HIGHER NUMBER AS 100WATTS?
 PLEASE SEE FIXTURES B, A, A2 ETC, 59WATTS ON THE IDR,
 51W ON FIXTURE LEGEND.
  
 C) PLEASE CLARIFY HOW THE METHOD OF CONTROL IS BEING
 SHOWN AS *MANUAL ON/OFF* WHEN MANY OF THESE ARE
 ACTUALLY AUTOMATED CONTROLS?
 PLEASE ADJUST METHOD OF CONTROLS FOR MANY AS LISTED ON
 THE IDR.
  
 ** PLEASE SEE THAT THE ABOVE IS SOME EXAMPLES OF
 COORDINATION WHICH NEEDS TO TAKE PLACE BETWEEN THE
 ELECTRICAL LIGHTING ON PLANS AND THE LIGHTING WHICH IS
 PLACE IN THE INPUT DATA REPORT. THIS OFFICE CAN NOT
 EMPHASIZE ENOUGH THE NEED FOR COORDINATION.
  
 D) PLEASE CLARIFY RECEPTACLES WHICH ARE SHOWN FOR ROOMS
 ARE SWITCHED OR PROVIDE POWER TO LIGHTING SUCH AS TABLE
 LAMPS/FLOOR LAMPS ETC. AS PLANS DO INDICATE WHAT
 APPEARS TO BE LAMPS ETC IN ROOMS THEN ANY OF THESE
 WHICH ARE PLUGGED INTO THESE RECEPTACLES WOULD BE
 REQUIRED TO BE PART OF THE ROOM LIGHTING CONTROLS. THIS
 WOULD REQUIRE THE SAME CIRCUITS FOR RECEPTACLES OR
 CONTROLS INSTALLED AND PROVIDING HALF SWITCHED
 RECEPTACLES.
 PLEASE SEE 13-415.1.ABC .1.1, .1.2 AND .1.3
  
 E) NOTE: PLEASE SEE THE OWNER AGENT IS TO BE SIGNED ON
 THE ENERGY CALCULATIONS CERTIFICATION SHEET. THE
 PRINTED NAME OF THE DEVELOPER IS NOT A CERTIFICATION.
 13-103.1.1.1
  
 6) NOTE: PLEASE SEE PREVIOUS NOTE #15 AS THIS REQUESTED
 ALL HORN, STROBE OR HORN/STROBE DEVICESTO INDICATE
 THE MINIMUM LEVELS FOR ADA PER FBC 11-4.28.1, .2 AND
 .3(4). THE RESPONSE LETTER MENTIONS THIS WAS DONE AT
 ALL LOCATIONS ON PLANS HOWEVER PLEASE CLARIFY WHERE
 THESE LEVELS ARE FOR THE DEVICES LOCATED IN THE ROOMS
 WHICH ARE ON E-206. PLEASE SEE ONLY SOME DEVICES ARE
 SHOWN AT LOCATIONS REQUIRED AND ONLY SOME OF THESE
 DEVICES WHICH ARE SHOWN INDICATE THE LEVELS. PLEASE SEE
 ROOM DOUBLE QUEEN ACC WHICH IS MISSING CD FOR LIVING
 ROOM AREA.
 PLEASE SEE TWO BEDROOM ACC WHICH ONLY INDICATES ONE
 DEVICE IN BATHROOM?
 ONLY NOTED SOME AREAS/LOCATIONS.
 PLEASE SEE THE NOTES ON E-502 WHICH WERE CORRECTED FOR
 THE CANADIAN CODE HOWEVER REFERENCES TO THE REQUIRED
 FLORIDA BUILDING CODE COULD NOT BE FOUND. PLEASE SEE
 CHAPTER 11 OF THE FBC IS SUBSTANTIALLY MORE RESTRICTIVE
 THAN THE NFPA-72 AS NOTED.
  
 7) NOTE: PLEASE SEE PREVIOUS WHICH REQUESTED FOR ALL
 MANUFACTURES SPECS/CUT SHEETS TO BE SUBMITTED FOR THE
 FIRE PUMP, FIRE PUMP CONTROLLER ETC.
 PLEASE SEE THE SPECS/CUT SHEETS WERE SUBMITTED HOWEVER
 COORDINATION WITH PLANS AND LISTING OF ASSEMBLY COULD
 NOT BE VERIFIED.
 PLEASE SEE THE FPC IS LISTED WITH A DIFFERENT
 MANUFACTURE THAN THE PUMPS, PLEASE BE SURE ALL ITEMS
 ARE LISTED ASSEMBLIES AS REQUIRED. NEC 110.3, 90.7.
 PLEASE BE SURE TO COORDINATE WITH INFORMATION TO BE
 PROVIDED ON FIRE SPRINKLER PLANS AND ANY REVIEW
 COMMENTS FROM THE FIRE MARSHAL.
 NOTE #22 FROM PREVIOUS REVIEW IS BEING LEFT BELOW.
  
  
 8) NOTE: PLEASE SEE RISER IS SHOWING AN *EQUIPMENT
 GROUNDING CONDUCTOR* FROM FPL TO THE FIRST MEANS OF
 DISCONNECT FRO THE FIRE PUMP SERVICE.
 PLEASE SEE 250.6, 250.24 AS THIS CREATES OBJECTIONABLE
 CURRENT AND IS NOT PERMITTED.
  
 9) NOTE: PLEASE SEE THERE ARE STILL RECEPTACLES MISSING
 PER 210.52 FOR 2FT, 6FT AND 12FT RULES.
 PLEASE SEE SOME UNITS/LOCATIONS ARE GIVEN FOR
 EXAMPLES:
 PLEASE SEE DOUBLE QUEEN, AND TWO BEDROOM SUITES 2FT OF
 WALL.
 PLEASE SEE TWO BEDROOM SLEEPING ROOM WITH TWO DOUBLE
 BEDS WHICH HAS MORE THAN 12FT OF WALL SPACE WITHOUT
 RECEPTACLE.
 PLEASE SEE TWO BEDROOM UNITS, BOTH TYPES AND DOUBLE
 QUEENS BOTH TYPES AS THESE ARE MISSING RECEPTACLES
 WITHIN 6FT OF DOORWAY. THE STUDIO AND KING DOES CONTAIN
 A RECEPTACLE WITHIN 6FT OF DOORWAY GOING INTO THE
 BEDROOM BUT THESE OTHERS.
 PLEASE SEE 210.52 AND ADJUST. THESE WERE REDLINED ON
 PLANS.
  
 10) NOTE: PLEASE CLARIFY PHOTO-METRICS AS SUBMITTED.
 THE STAIRS CONTAIN A TYPE *S* FIXTURE WHICH FIXTURE
 LEGEND INDICATES THIS AS A BATTERY BACK UP TYPE OF
 FIXTURE. HOW IS IT THAT THAT FOOT CANDLE LEVELS DROPS
 SUBSTANTIALLY? EVEN IF THE FIXTURE ONLY OPERATES ONLY
 ONE BULB, THIS WOULD ONLY BE HALF THE NORMAL LIGHTING
 OUTPUT. PLEASE EXPLAIN THIS SCENARIO.
 NFPA-101 7.8.1.3, 7.9.2.2
 ** THIS IS THE SAME FOR BOTH BUILDINGS AND ALL
 LOCATIONS WHICH CONTAIN THE SAME SITUATION. HOW DOES
 THE LIGHTING DECREASE AS SHOWN?
  
 11) NOTE: PLEASE VERIFY WHAT APPEARS TO BE A WATER
 HEATER DISCONNECT H1B-6 IN FIRE PUMP ROOM.
 PLEASE SEE NFPA-20 FOR EQUIPMENT WHICH IS PERMITTED IN
 THE FIRE PUMP ROOM.
 THIS IS NOT FOUND TO BE PERMITTED IN THIS ROOM.
  
 12) NOTE: PLEASE SEE SHEET E-205 UNIT DOUBLE QUEEN
 WHICH SEEMS TO BE MISSING OCTAGONAL NOTE #6 FROM THE
 UNIT FOR NOTED ARC FAULT PROTECTION.
 (PANEL DOES CORRECT THIS ON CIRCUIT).
  
  
  
  
 ** PLEASE KNOW ONCE ALL REVIEWS ARE DONE, ONE ROLL MAY
 BE RETAINED BY THIS OFFICE DUE TO REPEAT COMMENTS FOR
 CODE COMPLIANCE AND PREVIOUS NOTE TO FS 553.80(2)(B).
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-09-30 11:33:04 
  
 IN PROGRESS
2007-09-28 07:08:212007-09-28 07:08:21
  
2007-09-27 20:02:532007-09-27 20:02:53
  
 ONE SET IN ELECTRICAL FOR REVIEW.