| 2007-06-04 18:05:02 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 06111071 |
| | ADD: 2455 METROCENTRE BLVD |
| | CONT: AUTOBUILDERS |
| | TEL: (561)310-7735 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | HOMEWOOD SUITES HOTEL/ HILTON |
| | FIVE STORY/ 114 UNITS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| | THE COURT. |
| | NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| | NOT ACTUALLY |
| | COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, |
| | SUCH NOTICE IS |
| | NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE |
| | OF COMMENCEMENT |
| | AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) 2ND REQUEST , ONE REPORT SUBMITTED, (3) ARE |
| | REQUIRED, SIGNED & SEALED ORIGINALS. |
| | FBC 1802.2.1 QUESTIONABLE SOILS, |
| | 1802.2.1 QUESTIONABLE SOIL. |
| | WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN |
| | DOUBT, OR WHERE |
| | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| | CODE IS CLAIMED, |
| | THE BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY |
| | INVESTIGATION BE MADE. |
| | SUCH INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| | SECTIONS |
| | 1802.4 THROUGH 1802.6 . |
| | |
| | 4) 2ND REQUEST,WEST PALM BCH ADMINISTRATIVE |
| | CODE109.3.6 |
| | THIS BUILDING IS CONSIDERED A THRESHOLD BUILDING, |
| | REQUIRING THREE SETS |
| | OF ALL DOCUMENTS TO BE SUBMITTED TO THE BUILDING |
| | DEPARTMENT, PLANS, |
| | REPORTS, SUBMITTALS AND OR PRODUCT APPROVALS. |
| | |
| | 5) 2ND REQUEST THIS INSPECTION PLAN IS TO BE CREATED BY |
| | THE ENGINEER OF RECORD AND \ |
| | INDICATE WHICH INSPECTION ARE TO BE COMPLETED BY THE |
| | THRESHOLD INSPECTOR. |
| | FL S. S. 553.71(7) " THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN |
| | CY CLASSIFICATION AS DEINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS |
| | 5,000 SQ FT IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | 105.13.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| | STRUCTURAL INSPECTIONS ON A THRESHOLD |
| | BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE |
| | ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE |
| | OF A BUILDING PERMIT FOR THE |
| | CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURL INSPECTION |
| | PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| | PROCEDURES AND SCHEDULES SO THAT THE |
| | BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 6)2ND REQUEST, WPB AMENDMENT 105.13.6. W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A |
| | SPECIAL INSPECTOR AS REQUIRED BY S. |
| | 553.79(5) FLORIDA STATUTES TO THE MIN- |
| | IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| | CONTACT HAROLD PISKURA MANAGER OF THE |
| | SPECIAL INSPECTOR PROGRAM AT (561) |
| | 805-6711 FOR FURTHER INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 7)COMPLIED. |
| | |
| | 8)COMPLIED. |
| | 109.3.10* IMPACT OF CONSTRUCTION. |
| | ALL CONSTRUCTION ACTIVITY REGULATED BY |
| | THIS CODE SHALL BE PERMORMED IN A MANNER |
| | SO AS NOT TO ADVERSELY IMPACT THE |
| | CONDITION OF ADJACENT PROPERTY, UNLESS |
| | SUCH ACTIVITY IS PERMITTED TO AFFECT |
| | SAID PROPERTY PURSUANT TO A CONSENT BY |
| | THE APPLICABLE PROPERTY OWNER, UNDER |
| | TERMS & CONDITIONS AGREEABLE TO THE |
| | APPLICABLE PROPERTY OWNER.THIS INCLUDES |
| | BUT IS NOT LIMITED TO THE CONTROL OF |
| | DUST, NOISE, WATER OR DRAINAGE RUN-OFF, |
| | DEBRIS, AND THE STORAGE OF CONSTRUCTION |
| | MATERIALS. NEW CONSTRUCTION ACTIVITY |
| | SHALL NOT ADVERSELY IMPACT HISTORIC |
| | SURFACE WATER DRAINAGE FLOWS SERVING |
| | ADJACENT PROPERTIES, & MAY REQUIRE |
| | SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES.ACCORDINGLY, |
| | DEVELOPERS, CONTRACTORS, |
| | AND OWNERS OF ALL NEW RESIDENTIAL |
| | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR |
| | ITEMS, ON EXISTING PROPERTIES RESULTING |
| | IN A DECREASE IN EXCESS OF 800SQ FT OF |
| | PERMEABLE LAND AREA ON ANY PARCELL SHALL |
| | AS A PERMIT CONDITION, PROVIDE A |
| | PROFESSIONALLY PREPARED DRAINAGE PLAN |
| | CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE |
| | IMPROVEMENT, A CERTIFICATE FROM A |
| | LICENSED ENGINEER SHALL BE SUBMITTED TO |
| | THE INSPECTOR IN ORDER TO RECEIVE |
| | APPROVAL OF THE FINAL INSPECTION. |
| | |
| | 9) COMPLIED. |
| | 109.3.10.1 HURICANE PROTECTION. |
| | IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| | ALLOW CONSTRUCTION RELATED MATERIALS |
| | EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION |
| | SITE FROM 24 HRS. AFTER A HURRICANE |
| | WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN |
| | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS SHALL BE EITHER |
| | REMOVED FROM THE CONSTRUCTION SITE OR |
| | SECURED IN SUCH A MANNER AS TO MINIMIZE |
| | THE DANGER OF SUCH CONSTRUCTION |
| | MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH |
| | WINDS. |
| | ANY PERSONS WHO FAILS TO COMPLY TO |
| | REMOVE OR SECURE THE CONSTRUCTION |
| | MATERIALS EQUIPMENT AND DEBRIS WITHIN |
| | 24 HRS AFTER A HURRICANE WATCH HAS BEEN |
| | ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| | EXCEED $500.00. |
| | IN ADDITION TO THE ABOVE, A LICENSED |
| | CONTRACTOR WHO VIOLATES THIS SECTION |
| | SHALL BE SUBJECT TO DISCIPLINE PURSUANT |
| | TO SECTION 113 OF THIS CHAPTER. |
| | |
| | 10) 2ND REQUEST, PFVS CAN NOT APPEAR ON THE TITLE BLOCK |
| | UNLESS THERE IS A CERTIFICATE OF AUTHORIZATION FOR THE |
| | ARCHITECTURAL BUSINESS. |
| | IS MISSING THE FIRMS CERTIFICATE OF AUTHORIZATION. |
| | 481.219 F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE |
| | BLOCK FOR ANY |
| | SHEET BEARING THE NAME OF AN ARCHITECT |
| | PRACTICING UNDER A FICTITIOUS NAME, A |
| | CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL |
| | SERVICES, SHALL INCLUDE |
| | THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER.ADD THE NUMBER TO EACH SHEET. |
| | THIS MAY BE ADDED BY HAND. |
| | |
| | 11) COMPLIED. |
| | |
| | 12) 2ND EQUEST,THE STRUCTURAL SHEETS ARE ALSO MISSING |
| | THEIR (NIELSEN STRUCTURAL ENGINEERS)ENGINEERING |
| | CERTIFICATE OF AUTHORIZATION. F NEILSEN STRUCTURAL |
| | ENGINEERING IS THE DESIGNER FOR THIS STRUCTURE THEY ARE |
| | THE ENGINEERS OF RECORD AND SINCE THEY ARE A |
| | ENGINEERING BUSINESS A CERTIFICATE OF AUTHORIZATION IS |
| | REQUIRED. |
| | 471.023 F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE |
| | BLOCK FOR ANY |
| | SHEET BEARING THE NAME OF AN ENGINEER |
| | PRACTICING UNDER A FICTITIOUS NAME, A |
| | CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING |
| | SERVICES, |
| | SHALL INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. |
| | ADD THE NUMBER TO EACH SHEET.THIS MAY |
| | BE ADDED BY HAND. |
| | |
| | 13)2ND REQUEST, THE STRUCTURAL ENGINEERS TITLEBLOCK |
| | SHOULD CONTAIN THE FOLLOWING INFORMATION: |
| | 61G15-23.002(2) A TITLE BLOCK ON EACH SHEET SHOLD |
| | CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE |
| | NUMBER OF THE ENGINEER OR IF APPLICABLE, |
| | THE NAME AND LICENSE NUMBER OF THE ENGINEER, AND THE |
| | NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER |
| | OF THE ENGINEERING BUSINESS . |
| | |
| | 14)SHEET G-000: |
| | 14A) COMPLIED. |
| | |
| | 14B) 2ND REQUEST, THE PROJECT INDICATES THIS TO BE A |
| | (5) STORY, TYPE I-B SPRINKLERED BUILDING, THERE ARE NO |
| | PLANS FOR FIRE SPRINKLERS IN THE PLANS. FL S S |
| | 553.895(2) REQUIRES BUILDINGS 3 STORIES OR MORE TO HAVE |
| | FIRE SPINKLERS, SUBMIT PLANS FOR REVIEW BEFORE A PERMIT |
| | CAN BE ISSUED. 903.6.1 ANY BUILDING WHICH IS OF THREE |
| | STORIES OR MORE IN HEIGHT SHALL BE EQUIPPED WITH AN |
| | APPROVED AUTOMATIC SPRINKLER SYSTEM INSTALLED IN |
| | ACCORDANCE WITH SECTION 903.1 . |
| | |
| | |
| | 15) SHEET A-401: |
| | 15A) 2ND REQUEST,PLEASE PROVIDE THE ELEVATIONS, |
| | CHANGE IN GRADE FROM UNDER THE PORTICO TO THE LOBBY, |
| | PLANS ARE NOT CLEAR AS TO IF THERE IS A CURB OR ALL AT |
| | GRADE LEVEL. 11-4.5.2 CHANGES IN LEVEL. |
| | 11-4.6.6 PASSENGER LOADING ZONES. |
| | PASSENGER LOADING ZONES SHALL PROVIDE AN ACCESS AISLE |
| | AT LEAST 60 INCHES (1525 MM) WIDE AND 20 FEET (6096 MM) |
| | LONG ADJACENT AND PARALLEL TO THE VEHICLE PULL-UP SPACE |
| | (SEE FIGURE 10 ). IF THERE ARE CURBS BETWEEN THE ACCESS |
| | AISLE AND THE VEHICLE PULL-UP SPACE, THEN A CURB RAMP |
| | COMPLYING WITH SECTION 11-4.7 SHALL BE PROVIDED. |
| | VEHICLE STANDING SPACES AND ACCESS AISLES SHALL BE |
| | LEVEL WITH SURFACE SLOPES NOT EXCEEDING 1:50 (2 |
| | PERCENT) IN ALL DIRECTIONS. |
| | |
| | 553.5041 PARKING SPACES FOR PERSONS WHO HAVE |
| | DISABILITIES. |
| | (1) THIS SECTION IS NOT INTENDED TO EXPAND OR DIMINISH |
| | THE DEFENSES AVAILABLE TO A PLACE OF PUBLIC |
| | ACCOMMODATION UNDER THE AMERICANS WITH DISABILITIES ACT |
| | AND THE FEDERAL ADAAG, INCLUDING, BUT NOT LIMITED TO, |
| | THE READILY ACHIEVABLE STANDARD, AND THE STANDARDS |
| | APPLICABLE TO ALTERATIONS TO PLACES OF PUBLIC |
| | ACCOMMODATION. SUBJECT TO THE EXCEPTIONS DESCRIBED IN |
| | SUBSECTIONS (2), (4), (5), AND (6), WHEN THE PARKING |
| | AND LOADING ZONE REQUIREMENTS OF THE FEDERAL ADAAG, AS |
| | ADOPTED BY REFERENCE IN 28 C.F.R. PART 36, SUBPARTS A |
| | AND D, AND TITLE II OF PUB. L. NO. 101-336, PROVIDE |
| | INCREASED ACCESSIBILITY, THOSE REQUIREMENTS ARE ADOPTED |
| | AND INCORPORATED BY REFERENCE AS THE LAW OF THIS |
| | STATE. |
| | |
| | |
| | FAIR HOUSING ANSI A117.1 SECTION 4.6. |
| | |
| | 15B)2ND REQUEST, THE FRONT ENTRY DOORS (158) APPEAR TO |
| | BE HORIZONTAL SLIDING DOORS, PLEASE PROVIDE INFORMATION |
| | FOR MANUAL Y OPERATED (BREAK AWAY) IF LOSS OF POWER. |
| | SECTION 1008.1.3.3 |
| | SUBMIT PRODUCT APPROVALS. SHEET A603 STILL INDICATES |
| | THE DOORS AS AUTOMATIC SLIDING GLASS DOORS SEE DOOR |
| | TYPE "J". |
| | |
| | 16) SHEETA-404 |
| | |
| | 16A)2ND REQUESTPLANS INDICATES BLOCK WALLS THAT |
| | SEPERATE THE CORRIDOR AND INDIVIDUAL SUITES WITH A |
| | SYMBLE "AO" , SHEET A-601 WALL TYPE "AO" AS A STUDS AND |
| | DRYWALLWITH A STC RATING OF 34, THIS IS COMMON TO ALL |
| | SLEEPING UNITS, SEE 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION ASSEMBLIES |
| | FOR PIPING; ELECTRICAL DEVICES; RECESSED CABINETS; |
| | BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR EXHAUST |
| | DUCTS SHALL BE SEALED, LINED, INSULATED OR OTHERWISE |
| | TREATED TO MAINTAIN THE REQUIRED RATINGS. THIS |
| | REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT ENTRANCE |
| | DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT FITTING TO |
| | THE FRAME AND SILL. NOTE ON A-301 STILL DOES NOT COMPLY |
| | WITH THE WALL LISTINGS FOUND ON |
| | SHEET A-601. |
| | |
| | 16B) 2ND REQUEST, PROVIDE THE STC RATING FOR FLOORS TO |
| | ALL SLEEPING UNITS ABOVE THE FIRST FLOOR.1207.3 |
| | STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. |
| | PROVIDE DOCUMENTATION. |
| | |
| | 16C) 2ND REQUEST, ELEVATOR SHAFT WALL DESIGNATION |
| | MISSING, 5 STORIES REQUIES A 2 HR WALL RATING, 707.4 |
| | |
| | 16D) COMPLIED. |
| | |
| | 16E)COMPLIED. |
| | |
| | 16F) ELEVATOR LOBBY # 130 SHOWS ELECTRIC MAGNET HOLD |
| | OPEN DEVICES WHERE AS E-204 IS MISSING THE HOLD OPEN |
| | DEVICES.SEMI-COMPLIED. THIS IS TYPICAL TO ALL FLOORS |
| | BUT THERE IS N'T AN ELECTRICALSECTION THROUGH THE 2ND |
| | - 5THFLOORS AT THE ELEVATOR LOBBIES INDICATING |
| | ELECTRIC HOLD OPEN DEVICES SEE DOOR SCHEDULE |
| | SHEET A-603. |
| | |
| | 16G) COMPLIED. |
| | |
| | 16H) 2ND REQUEST PLANS INDICATE A FIREEXTINGUISHER |
| | CABINET IN THE FIRE RATED WALL RECESSED. PROVIDE DETAIL |
| | INDICATING HOW THE FIRE RATING IS MAINTAINED. 707.4. |
| | RESPONCE INDICATES SEE SPECIFICATION SECTION WHERE? |
| | |
| | 16I) 2ND REQUEST, STAIR TOWER# 1 ALSO INDICATES WALL |
| | RATING "OD", A NON-RATED WALL, REQUIRES A 2HR FIRE |
| | RATING REQUIRED. SEE 707.4. |
| | |
| | 16J)2ND REQUEST, STAIR TOWER# 1 IS MISSING DOOR |
| | IDENTIFICATION TAG IN THE DOOR SCHEDULE, PLEASE SHOW |
| | RATING TABLE 715.3 ,MISSING HARDWARE SCHEDULE. RESPONCE |
| | INDICATES A PROJECT MANUAL, WHERE? |
| | |
| | 16K)2ND REQUEST,STAIR TOWER# 1 NO DIMENSION IS |
| | PROVIDED AT THE DOOR,SHEET A-101 INDICATES A MO OF |
| | 3'-2" WHAT SIZE DOOR IS BEING INSTALLED? WHATWILL THE |
| | OCCUPANT LOAD BE FOR THIS DOORWAY? MISSING HARDWARE, |
| | TYPICAL. |
| | |
| | 16L) COMPLIED. |
| | |
| | 16M) COMPLIED. |
| | |
| | 16N) 2ND REQUEST PLEASE PROVIDE INFORMATION FOR |
| | ELEVATOR CARS TO ACCOMMODATE AMBULANCE STRETCHER. |
| | 3002.4 ELEVATOR CAR TO ACCOMMODATE AMBULANCE STRETCHER |
| | PLEASE SHOW COMPLIANCE. |
| | |
| | IN BUILDINGS FOUR STORIES IN HEIGHT OR MORE, AT LEAST |
| | ONE ELEVATOR SHALL BE PROVIDED FOR FIRE DEPARTMENT |
| | EMERGENCY ACCESS TO ALL FLOORS. SUCH ELEVATOR CAR SHALL |
| | BE OF SUCH A SIZE AND ARRANGEMENT TO ACCOMMODATE A |
| | 24-INCH BY 76-INCH (610 MM BY 1930 MM) AMBULANCE |
| | STRETCHER IN THE HORIZONTAL, OPEN POSITION AND SHALL BE |
| | IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR EMERGENCY |
| | MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL SHALL NOT |
| | BE LESS THAN 3 INCHES (76 MM) HIGH AND SHALL BE PLACED |
| | INSIDE ON BOTH SIDES OF THE HOISTWAY DOOR FRAME. |
| | |
| | 17) SHEET A-101 |
| | 17A) DETAIL DELETED? |
| | |
| | 17B) COMPLIED. |
| | |
| | 18)SHEET A-101/ A-402 |
| | |
| | 18A) 2ND REQUESTDETAIL# 1 IS MISSING THE STORAGE ROOM |
| | 142, PLEASE IDENTIFY THE WALL RATING |
| | OF THE SHAFT LOCATED IN THIS ROOM AND ALL OTHER COMMON |
| | SHAFTS.106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 18B)(1)2ND REQUEST NOT ALL WALLS OF THE TERMINATION |
| | ROOM ARE TAGED, DETAIL# 1 ALSO INDICATES THE LAUNDRY |
| | ROOM IS THE TERMINATION OF THE LAUNDRY CHUTE. 707.13.4 |
| | TERMINATION ROOM.REFUSE AND LAUNDRY CHUTES SHALL |
| | DISCHARGE INTO AN ENCLOSED ROOM COMPLETELY SEPARATED |
| | FROM THE REMAINDER OF THE BUILDING BY CONSTRUCTION THAT |
| | HAS A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR |
| | AND OPENINGS INTO THE TERMINATION ROOM SHALL BE |
| | PROTECTED BY OPENING PROTECTIVES HAVING A FIRE |
| | PROTECTION RATING OF NOT LESS THAN 1 HOUR AND SHALL BE |
| | SELF-CLOSING OR AUTOMATIC-CLOSING UPON THE DETECTION OF |
| | SMOKE. REFUSE CHUTES SHALL NOT TERMINATE IN AN |
| | INCINERATOR ROOM. REFUSE AND LAUNDRY ROOMS THAT ARE NOT |
| | PROVIDED WITH CHUTES NEED ONLY COMPLY WITH TABLE |
| | 302.1.1 .NO DOOR HARDWARE SCHEDULE , TYPICAL. 18B)(2) |
| | NEW COMMENT- THE LAUNDRY ROOM ALSO IS MISSING WALL |
| | IDENTIFICATION TAGS |
| | |
| | 18C) 2ND REQUEST, THE DOOR SCHEDULE FOR DOOR# 124 |
| | COORIDOR TO LAUNDRY INDICATES A WINDOW WITH TEMPERED |
| | GLASS, FOR RATED DOORS SEE TABLE 715.4.3 FOR MAXIMUM |
| | SIZE OF WINDOW AND TYPE OF GLASS. PROVIDE THE MAXIMUM |
| | SQ IN ALLOWED! |
| | |
| | 18D) 2ND REQUEST,DETAIL# 22ND-5TH FLOOR LAUNDRY |
| | CHUTE AND LINEN STORAGE INDICATES THE LAUNDRY CHUTE |
| | WITHIN A LAUNDRY STORAGE ROOM,PROVIDE DETAILS ON THE |
| | LAUNDRY CHUTE ENCLOSURE, OPENINGS INTO THE SHAFT (DOOR) |
| | AND FIRE RATINGS OF LAUNDRY CHUTE DOOR.707.13.1.PLEASE |
| | PROVIDE THE PROJECT MANUAL. |
| | |
| | 18E) COMPLIED. |
| | |
| | 18F) COMPLIED. |
| | |
| | 18G)COMPLIED. |
| | |
| | 19) SHEET A-102: |
| | 19A) CORRECT. |
| | |
| | 19B) 2ND REQUEST, DETAIL#2 /503,IS MISS LABELED, PLEASE |
| | CORRECT. THE INDEX INDICATES SUCH A SHEET EXIST, PLANS |
| | ARE MISSING THIS SHEET COMMON TO 2ND -5TH FLOOR. |
| | ADDITIONAL COMMENTS WILL APPEARON THE NEXT REVIEW FOR |
| | THIS SECTION WITH NEW SUBMITTAL.RESPONCE INDICATES |
| | WHERE TO FIND INTHE RESPONCE COMMENTS BUT THE DETAIL |
| | WAS NOT CORRECTED!! |
| | |
| | 19C) COMPLIED. |
| | |
| | 20) SHEET A-103: |
| | 20A) COMPLIED. |
| | |
| | 20B)2ND REQUEST, ROOMS 327 & 328 SHARE A SHFT WALL IN |
| | COMMON, THE SHAFT IS BUILT RIGHT INTO THE BATHROOM |
| | WALL, HOW WILL THE BACKING FOR SHOWER AND TUB BE |
| | INSTALLED? PLANS DO NOT PROVIDE WHAT TYPE OF BACKING |
| | WILL BE USED, RESPONCE COMMENT INDICATES SEE DETAIL ON |
| | A-511. IS THE BACKING TO BE APPLIED TO THE SURFACE OF |
| | THE ASSEMBLY UL-438? |
| | |
| | 20C) 2ND REQUEST, DETAIL1/A-403 FIRST FLOOR LEVEL, |
| | INDICATES ROOM# 114 TO THE MACHINE ROOM FOR ELEVATOR# |
| | 2, REQUIRING A 2 HR RATING WITH 1 1/2 HR RATED DOOR. |
| | PLEASE CORRECT. THE WALL THE DOOR IS LOCATED IN DOESN'T |
| | EVEN HAVE A WALL IDENTIFICATION TAG. NOTE NO STC RATING |
| | FOR 3HR BLOCK. |
| | |
| | 20D) 2ND REQUEST,DETAIL1/A-403 ELEVATOR MACHINE ROOM |
| | WALL IDENTIFICATION TAG SHOULD READ A 2HR FIRE RATING |
| | WITH 1 1/2 HR OPENING PROTECTION. TAG IS NOW 1C OR 1 HR |
| | RATED. |
| | |
| | 20E)COMPLIED. NOTE THE WALL THAT BACKS UP TO THE |
| | EXERCISE ROOM IS NOT LABELED. |
| | |
| | 20F) COMPLIED. |
| | |
| | 20G)2ND REQUEST,EXERCISE ROOM DOOR 118 TO BE FIRE |
| | RATED IN HRS/ MIN. TABLE 715.3SIZE OF WIRE PANEL? |
| | |
| | 20H) COMPLIED. |
| | |
| | 20I) 2ND REQUEST, SHOW ON PLAN, 2ND - 5TH FLOORS SAME |
| | ISSUES, THE ELECTRICAL ROOM DOOR IS MISSING |
| | IDENTIFICATION TAG AND FIRE RATING.707.4. |
| | |
| | 20I)2ND REQUEST,STORAGE ROOM 251 COMMON 2ND- 5TH |
| | FLOOR, THIS IS A RATED CORRIDOR TABLE 1016 WALL |
| | IDENTIFICATION TAG SHOULD INDICATE AS SUCH AND IN DOOR |
| | SCHEDULE. TABLE 715.3. THIS IS A DETAIL OR ENLARGED |
| | PLAN AND SHOULD SHOW WALLTHE RATED WALLS. |
| | |
| | 20K) 2ND REQUEST, AGAIN THIS IS AN ENLARGED PLAN AND |
| | SHOULD INDICATE WALL TAGS. STORAGE ROOM 318/ 418 |
| | STORAGE ROOM WALLS AS WELL AS THE MAINTENANCE ROOM 518, |
| | 1 HR RATED, DOORS TTABLE TABLE 715.3. |
| | |
| | 21) 2ND REQUEST, SEMI COMPLIED. SHEET A-701 DOES |
| | INDICATE THE STAIRWAY TO THE ROOF BUT AGAIN THE DOORWAY |
| | TO THE ROOF IS NOT IN THE DOOR SCHEDULE AS WELL AS THE |
| | OTHER STAIRWELL DOORS. |
| | |
| | 22) 2ND REQUEST, SHEET A-301 PLANS INDICATE THE USE OF |
| | CORRIGATED METAL DECK, DENSE DECK AND ICE & WATER |
| | SHIELD. THIS SECTION WAS TAKEN FROM THE ENTRY AREA |
| | FIRST FLOOR.ON THE SHEET A-301 PLANS INDICATE THE USE |
| | OF UL# P523 WHERE UNDER THIS LISTING C/D PLYWOOD CAN BE |
| | USED. PLEASE CORRECT, ALSO PROVIDE US WITH WHAT TYPE OF |
| | DENSE-GLASS PRODUCT WILL BE USED AS SHEATHING MATERIAL |
| | FOR THE ROOF? |
| | |
| | 23) COMPLIED. |
| | |
| | 24)2ND REQUEST,SHEET A-301ENLARGED SECTION DETAIL OF |
| | ROOF INDICATED A STEEL DECK DENSEGLASS AND ICE & WATER |
| | SHIELD UNDERLAYMENT, SHEET A-302DETAIL # 3INDICATES |
| | THE USE OF A (P540) U.L. LISTED ROOF/ CEILING ASSEMBLY. |
| | AS PART OF THIS SYSTEM PART # 5 INDICATES THE USE OF |
| | VARIOUS ROOFING INSULATIONS USED ABOVE THE STEEL DECK |
| | PLEASE CORRALATE AND CORRECT .THE PLANS INDICATE FOR |
| | THE SAME ROOF SECTION P523 AND P540? |
| | |
| | 25) 2ND REQUEST, SHEET A-303 DETAIL# 3 NOW INDICATES |
| | THE USSE OF UL LISTING # J-956 FOR THE FLOOR SYSTEM AND |
| | ROOF SYSTEM. PLEASE PROVIDE THE EQUIVALENT THICKNESS |
| | REQUIRED FOR THIS FLOOR SYSTEM AND ROOF SYSTEM FOR THE |
| | TYPE OF AGGREGATE FOUND IN THIS AREA. UL LIST BLAST |
| | FURNACE SLAG AGGRIGATE FOR THE TYPE AGGREGATE FOR THEIR |
| | UL RATING FLOOR CEIOLING ASSEMBLIES. PLEASE SEE |
| | 721.2.2.1.1 HOLLOW-CORE PRESTRESSED SLABS. |
| | FOR HOLLOW-CORE PRESTRESSED CONCRETE SLABS IN WHICH THE |
| | CORES ARE OF CONSTANT CROSS SECTION THROUGHOUT THE |
| | LENGTH, THE EQUIVALENT THICKNESS SHALL BE PERMITTED TO |
| | BE OBTAINED BY DIVIDING THE NET CROSS-SECTIONAL AREA OF |
| | THE SLAB INCLUDING GROUT IN THE JOINTS, BY ITS WIDTH. |
| | 721.2.2.1 REINFORCED AND PRESTRESSED FLOORS AND ROOFS. |
| | |
| | THE MINIMUM THICKNESSES OF REINFORCED AND PRESTRESSED |
| | CONCRETE FLOOR OR ROOF SLABS FOR FIRE-RESISTANCE |
| | RATINGS OF 1 HOUR TO 4 HOURS ARE SHOWN IN TABLE |
| | 721.2.2.1 . |
| | TABLE 601 |
| | |
| | 26) COMPLIED. |
| | |
| | 27) COMPLIED. |
| | |
| | 28) 2ND REQUEST,RESPONSE INDICATES TO SEE INTERIOR |
| | DRAWINGS, INDEX INDICATES THERE ARE NONE IN THIS PLAN. |
| | A-702 PLANS DO NOT INDICATE REQUIREMEENTS FOR BRAILLE |
| | CHARACTERS AT HOISTWAY ENTRANCES. 11-4.10.5 RAISED AND |
| | BRAILLE CHARACTERS ON HOISTWAY ENTRANCES. ALL ELEVATOR |
| | HOIST WAY ENTRANCES SHALL HAVE RAISED AND BRAILLE FLOOR |
| | DESIGNATIONS PROVIDED ON BOTH JAMBS. THE CENTERLINE OF |
| | THE CHARACTERS SHALL BE 60 INCHES (1525 MM) ABOVE |
| | FINISH FLOOR. SUCH CHARACTERS SHALL BE 2 INCHES (50 MM) |
| | HIGH AND SHALL COMPLY WITH SECTION 11-4.30.4 . |
| | PERMANENTLY APPLIED PLATES ARE ACCEPTABLE IF THEY ARE |
| | PERMANENTLY FIXED TO THE JAMBS (SEE FIGURE 11-20 ). |
| | |
| | 29A) 2ND REQUEST1609.1.4 PROTECTION OF OPENINGS. IN |
| | WIND-BORNE DEBRIS REGIONS, EXTERIOR |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE |
| | IN THE LOWER 60 FEET (18.3 M) IN |
| | BUILDINGS SHALL BE ASSUMED TO BE |
| | OPENINGS AND THE BALANCE OF GLAZED |
| | OPENINGS IN THE REST OF THE BUILDING |
| | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE |
| | IS IMPACT RESISTANT OR PROTECTED WITH AN |
| | IMPACT RESISTANT COVERING MEETING THE |
| | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND |
| | ASTM E 1996, OR MIAMI-DADE TAS 201, 202 |
| | AND 203 REFERENCED THEREIN AS FOLLOWS: |
| | 1.GLAZED OPENINGS LOCATED WITHIN 30 |
| | FEET (9.1 M) OF GRADE SHALL MEET THE |
| | REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2.GLAZED OPENINGS LOCATED MORE THAN |
| | 30 FEET (9.1 M) ABOVE GRADE SHALL MEET |
| | THE PROVISIONS OF THE SMALL MISSILE |
| | TEST. |
| | |
| | 29B)2ND REQUEST, PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | |
| | 29C) 2ND REQUEST, WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL.] |
| | |
| | 29D) 2ND REQUEST, RESPONSE INDICATES APPROVALS IN |
| | PACKAGE ONLY A RUSKIN LOUVER WAS SUBMITTED!!! |
| | FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE |
| | 2 COPIES |
| | (3)IF THRESHOLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOW |
| | FIXED |
| | SINGLE HUNG |
| | MULLION |
| | B) GLAZED DOORS |
| | AUTOMATIC HORIZONTAL SLIDING DOORS |
| | EXTERIOR HOLLOW METAL DOORS |
| | C) LOUVERS |
| | D) PANEL WALL SYSTEMS |
| | SOFFITS- HARDI SOFFIT BOARD |
| | E) STRUCTURAL COMPONENTS- TRUSS ANCHORS |
| | F) ROOF ASSEMBLIES |
| | FLAT ROOFS- MODIFIED/ BITUMEN |
| | SLOPED:UNDERLAYMENTS, ROOF TILE ADHESIVES, ROOF |
| | TILE APPLICATIONS |
| | |
| | 30)NOTED AND COMPLIED,ASEPERATE PERMIT IS REQUIRED |
| | FOR THE POOL, POOL EQUIPMENT BUILDING , POOL FENCING |
| | AND SIGNAGE. |
| | |
| | 31) 2ND REQUEST, BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT |
| | OF THE ADDITIONAL INFORMATION REQUESTED ADDITIONAL |
| | COMMENTS |
| | MAY APPEAR THAT WERE NOT PART OF THIS REVIEW. |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |