Plan Review Notes
Plan Review Notes For Permit 06111071
Permit Number 06111071
Review Stop B
Sequence Number 3
Notes
Date Text
2007-06-04 18:05:02 
 BUILDING PLAN REVIEW
 PERMIT: 06111071
 ADD: 2455 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 HOMEWOOD SUITES HOTEL/ HILTON
 FIVE STORY/ 114 UNITS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) 2ND REQUEST , ONE REPORT SUBMITTED, (3) ARE
 REQUIRED, SIGNED & SEALED ORIGINALS.
 FBC 1802.2.1 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED,
 THE BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE.
 SUCH INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS
 1802.4 THROUGH 1802.6 .
  
 4) 2ND REQUEST,WEST PALM BCH ADMINISTRATIVE
 CODE109.3.6
 THIS BUILDING IS CONSIDERED A THRESHOLD BUILDING,
 REQUIRING THREE SETS
 OF ALL DOCUMENTS TO BE SUBMITTED TO THE BUILDING
 DEPARTMENT, PLANS,
 REPORTS, SUBMITTALS AND OR PRODUCT APPROVALS.
  
 5) 2ND REQUEST THIS INSPECTION PLAN IS TO BE CREATED BY
 THE ENGINEER OF RECORD AND \
 INDICATE WHICH INSPECTION ARE TO BE COMPLETED BY THE
 THRESHOLD INSPECTOR.
 FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT FOR THE
 CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURL INSPECTION
 PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE
 BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 6)2ND REQUEST, WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 7)COMPLIED.
  
 8)COMPLIED.
 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES.ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 9) COMPLIED.
 109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 10) 2ND REQUEST, PFVS CAN NOT APPEAR ON THE TITLE BLOCK
 UNLESS THERE IS A CERTIFICATE OF AUTHORIZATION FOR THE
 ARCHITECTURAL BUSINESS.
 IS MISSING THE FIRMS CERTIFICATE OF AUTHORIZATION.
 481.219 F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 11) COMPLIED.
  
 12) 2ND EQUEST,THE STRUCTURAL SHEETS ARE ALSO MISSING
 THEIR (NIELSEN STRUCTURAL ENGINEERS)ENGINEERING
 CERTIFICATE OF AUTHORIZATION. F NEILSEN STRUCTURAL
 ENGINEERING IS THE DESIGNER FOR THIS STRUCTURE THEY ARE
 THE ENGINEERS OF RECORD AND SINCE THEY ARE A
 ENGINEERING BUSINESS A CERTIFICATE OF AUTHORIZATION IS
 REQUIRED.
 471.023 F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES,
 SHALL INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 13)2ND REQUEST, THE STRUCTURAL ENGINEERS TITLEBLOCK
 SHOULD CONTAIN THE FOLLOWING INFORMATION:
 61G15-23.002(2) A TITLE BLOCK ON EACH SHEET SHOLD
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER, AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS .
  
 14)SHEET G-000:
 14A) COMPLIED.
  
 14B) 2ND REQUEST, THE PROJECT INDICATES THIS TO BE A
 (5) STORY, TYPE I-B SPRINKLERED BUILDING, THERE ARE NO
 PLANS FOR FIRE SPRINKLERS IN THE PLANS. FL S S
 553.895(2) REQUIRES BUILDINGS 3 STORIES OR MORE TO HAVE
 FIRE SPINKLERS, SUBMIT PLANS FOR REVIEW BEFORE A PERMIT
 CAN BE ISSUED. 903.6.1 ANY BUILDING WHICH IS OF THREE
 STORIES OR MORE IN HEIGHT SHALL BE EQUIPPED WITH AN
 APPROVED AUTOMATIC SPRINKLER SYSTEM INSTALLED IN
 ACCORDANCE WITH SECTION 903.1 .
  
  
 15) SHEET A-401:
 15A) 2ND REQUEST,PLEASE PROVIDE THE ELEVATIONS,
 CHANGE IN GRADE FROM UNDER THE PORTICO TO THE LOBBY,
 PLANS ARE NOT CLEAR AS TO IF THERE IS A CURB OR ALL AT
 GRADE LEVEL. 11-4.5.2 CHANGES IN LEVEL.
 11-4.6.6 PASSENGER LOADING ZONES.
 PASSENGER LOADING ZONES SHALL PROVIDE AN ACCESS AISLE
 AT LEAST 60 INCHES (1525 MM) WIDE AND 20 FEET (6096 MM)
 LONG ADJACENT AND PARALLEL TO THE VEHICLE PULL-UP SPACE
 (SEE FIGURE 10 ). IF THERE ARE CURBS BETWEEN THE ACCESS
 AISLE AND THE VEHICLE PULL-UP SPACE, THEN A CURB RAMP
 COMPLYING WITH SECTION 11-4.7 SHALL BE PROVIDED.
 VEHICLE STANDING SPACES AND ACCESS AISLES SHALL BE
 LEVEL WITH SURFACE SLOPES NOT EXCEEDING 1:50 (2
 PERCENT) IN ALL DIRECTIONS.
  
 553.5041 PARKING SPACES FOR PERSONS WHO HAVE
 DISABILITIES.
 (1) THIS SECTION IS NOT INTENDED TO EXPAND OR DIMINISH
 THE DEFENSES AVAILABLE TO A PLACE OF PUBLIC
 ACCOMMODATION UNDER THE AMERICANS WITH DISABILITIES ACT
 AND THE FEDERAL ADAAG, INCLUDING, BUT NOT LIMITED TO,
 THE READILY ACHIEVABLE STANDARD, AND THE STANDARDS
 APPLICABLE TO ALTERATIONS TO PLACES OF PUBLIC
 ACCOMMODATION. SUBJECT TO THE EXCEPTIONS DESCRIBED IN
 SUBSECTIONS (2), (4), (5), AND (6), WHEN THE PARKING
 AND LOADING ZONE REQUIREMENTS OF THE FEDERAL ADAAG, AS
 ADOPTED BY REFERENCE IN 28 C.F.R. PART 36, SUBPARTS A
 AND D, AND TITLE II OF PUB. L. NO. 101-336, PROVIDE
 INCREASED ACCESSIBILITY, THOSE REQUIREMENTS ARE ADOPTED
 AND INCORPORATED BY REFERENCE AS THE LAW OF THIS
 STATE.
  
  
 FAIR HOUSING ANSI A117.1 SECTION 4.6.
  
 15B)2ND REQUEST, THE FRONT ENTRY DOORS (158) APPEAR TO
 BE HORIZONTAL SLIDING DOORS, PLEASE PROVIDE INFORMATION
 FOR MANUAL Y OPERATED (BREAK AWAY) IF LOSS OF POWER.
 SECTION 1008.1.3.3
 SUBMIT PRODUCT APPROVALS. SHEET A603 STILL INDICATES
 THE DOORS AS AUTOMATIC SLIDING GLASS DOORS SEE DOOR
 TYPE "J".
  
 16) SHEETA-404
  
 16A)2ND REQUESTPLANS INDICATES BLOCK WALLS THAT
 SEPERATE THE CORRIDOR AND INDIVIDUAL SUITES WITH A
 SYMBLE "AO" , SHEET A-601 WALL TYPE "AO" AS A STUDS AND
 DRYWALLWITH A STC RATING OF 34, THIS IS COMMON TO ALL
 SLEEPING UNITS, SEE 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION ASSEMBLIES
 FOR PIPING; ELECTRICAL DEVICES; RECESSED CABINETS;
 BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR EXHAUST
 DUCTS SHALL BE SEALED, LINED, INSULATED OR OTHERWISE
 TREATED TO MAINTAIN THE REQUIRED RATINGS. THIS
 REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT ENTRANCE
 DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT FITTING TO
 THE FRAME AND SILL. NOTE ON A-301 STILL DOES NOT COMPLY
 WITH THE WALL LISTINGS FOUND ON
 SHEET A-601.
  
 16B) 2ND REQUEST, PROVIDE THE STC RATING FOR FLOORS TO
 ALL SLEEPING UNITS ABOVE THE FIRST FLOOR.1207.3
 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492.
 PROVIDE DOCUMENTATION.
  
 16C) 2ND REQUEST, ELEVATOR SHAFT WALL DESIGNATION
 MISSING, 5 STORIES REQUIES A 2 HR WALL RATING, 707.4
  
 16D) COMPLIED.
  
 16E)COMPLIED.
  
 16F) ELEVATOR LOBBY # 130 SHOWS ELECTRIC MAGNET HOLD
 OPEN DEVICES WHERE AS E-204 IS MISSING THE HOLD OPEN
 DEVICES.SEMI-COMPLIED. THIS IS TYPICAL TO ALL FLOORS
 BUT THERE IS N'T AN ELECTRICALSECTION THROUGH THE 2ND
 - 5THFLOORS AT THE ELEVATOR LOBBIES INDICATING
 ELECTRIC HOLD OPEN DEVICES SEE DOOR SCHEDULE
 SHEET A-603.
  
 16G) COMPLIED.
  
 16H) 2ND REQUEST PLANS INDICATE A FIREEXTINGUISHER
 CABINET IN THE FIRE RATED WALL RECESSED. PROVIDE DETAIL
 INDICATING HOW THE FIRE RATING IS MAINTAINED. 707.4.
 RESPONCE INDICATES SEE SPECIFICATION SECTION WHERE?
  
 16I) 2ND REQUEST, STAIR TOWER# 1 ALSO INDICATES WALL
 RATING "OD", A NON-RATED WALL, REQUIRES A 2HR FIRE
 RATING REQUIRED. SEE 707.4.
  
 16J)2ND REQUEST, STAIR TOWER# 1 IS MISSING DOOR
 IDENTIFICATION TAG IN THE DOOR SCHEDULE, PLEASE SHOW
 RATING TABLE 715.3 ,MISSING HARDWARE SCHEDULE. RESPONCE
 INDICATES A PROJECT MANUAL, WHERE?
  
 16K)2ND REQUEST,STAIR TOWER# 1 NO DIMENSION IS
 PROVIDED AT THE DOOR,SHEET A-101 INDICATES A MO OF
 3'-2" WHAT SIZE DOOR IS BEING INSTALLED? WHATWILL THE
 OCCUPANT LOAD BE FOR THIS DOORWAY? MISSING HARDWARE,
 TYPICAL.
  
 16L) COMPLIED.
  
 16M) COMPLIED.
  
 16N) 2ND REQUEST PLEASE PROVIDE INFORMATION FOR
 ELEVATOR CARS TO ACCOMMODATE AMBULANCE STRETCHER.
 3002.4 ELEVATOR CAR TO ACCOMMODATE AMBULANCE STRETCHER
 PLEASE SHOW COMPLIANCE.
  
 IN BUILDINGS FOUR STORIES IN HEIGHT OR MORE, AT LEAST
 ONE ELEVATOR SHALL BE PROVIDED FOR FIRE DEPARTMENT
 EMERGENCY ACCESS TO ALL FLOORS. SUCH ELEVATOR CAR SHALL
 BE OF SUCH A SIZE AND ARRANGEMENT TO ACCOMMODATE A
 24-INCH BY 76-INCH (610 MM BY 1930 MM) AMBULANCE
 STRETCHER IN THE HORIZONTAL, OPEN POSITION AND SHALL BE
 IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR EMERGENCY
 MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL SHALL NOT
 BE LESS THAN 3 INCHES (76 MM) HIGH AND SHALL BE PLACED
 INSIDE ON BOTH SIDES OF THE HOISTWAY DOOR FRAME.
  
 17) SHEET A-101
 17A) DETAIL DELETED?
  
 17B) COMPLIED.
  
 18)SHEET A-101/ A-402
  
 18A) 2ND REQUESTDETAIL# 1 IS MISSING THE STORAGE ROOM
 142, PLEASE IDENTIFY THE WALL RATING
 OF THE SHAFT LOCATED IN THIS ROOM AND ALL OTHER COMMON
 SHAFTS.106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 18B)(1)2ND REQUEST NOT ALL WALLS OF THE TERMINATION
 ROOM ARE TAGED, DETAIL# 1 ALSO INDICATES THE LAUNDRY
 ROOM IS THE TERMINATION OF THE LAUNDRY CHUTE. 707.13.4
 TERMINATION ROOM.REFUSE AND LAUNDRY CHUTES SHALL
 DISCHARGE INTO AN ENCLOSED ROOM COMPLETELY SEPARATED
 FROM THE REMAINDER OF THE BUILDING BY CONSTRUCTION THAT
 HAS A FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR
 AND OPENINGS INTO THE TERMINATION ROOM SHALL BE
 PROTECTED BY OPENING PROTECTIVES HAVING A FIRE
 PROTECTION RATING OF NOT LESS THAN 1 HOUR AND SHALL BE
 SELF-CLOSING OR AUTOMATIC-CLOSING UPON THE DETECTION OF
 SMOKE. REFUSE CHUTES SHALL NOT TERMINATE IN AN
 INCINERATOR ROOM. REFUSE AND LAUNDRY ROOMS THAT ARE NOT
 PROVIDED WITH CHUTES NEED ONLY COMPLY WITH TABLE
 302.1.1 .NO DOOR HARDWARE SCHEDULE , TYPICAL. 18B)(2)
 NEW COMMENT- THE LAUNDRY ROOM ALSO IS MISSING WALL
 IDENTIFICATION TAGS
  
 18C) 2ND REQUEST, THE DOOR SCHEDULE FOR DOOR# 124
 COORIDOR TO LAUNDRY INDICATES A WINDOW WITH TEMPERED
 GLASS, FOR RATED DOORS SEE TABLE 715.4.3 FOR MAXIMUM
 SIZE OF WINDOW AND TYPE OF GLASS. PROVIDE THE MAXIMUM
 SQ IN ALLOWED!
  
 18D) 2ND REQUEST,DETAIL# 22ND-5TH FLOOR LAUNDRY
 CHUTE AND LINEN STORAGE INDICATES THE LAUNDRY CHUTE
 WITHIN A LAUNDRY STORAGE ROOM,PROVIDE DETAILS ON THE
 LAUNDRY CHUTE ENCLOSURE, OPENINGS INTO THE SHAFT (DOOR)
 AND FIRE RATINGS OF LAUNDRY CHUTE DOOR.707.13.1.PLEASE
 PROVIDE THE PROJECT MANUAL.
  
 18E) COMPLIED.
  
 18F) COMPLIED.
  
 18G)COMPLIED.
  
 19) SHEET A-102:
 19A) CORRECT.
  
 19B) 2ND REQUEST, DETAIL#2 /503,IS MISS LABELED, PLEASE
 CORRECT. THE INDEX INDICATES SUCH A SHEET EXIST, PLANS
 ARE MISSING THIS SHEET COMMON TO 2ND -5TH FLOOR.
 ADDITIONAL COMMENTS WILL APPEARON THE NEXT REVIEW FOR
 THIS SECTION WITH NEW SUBMITTAL.RESPONCE INDICATES
 WHERE TO FIND INTHE RESPONCE COMMENTS BUT THE DETAIL
 WAS NOT CORRECTED!!
  
 19C) COMPLIED.
  
 20) SHEET A-103:
 20A) COMPLIED.
  
 20B)2ND REQUEST, ROOMS 327 & 328 SHARE A SHFT WALL IN
 COMMON, THE SHAFT IS BUILT RIGHT INTO THE BATHROOM
 WALL, HOW WILL THE BACKING FOR SHOWER AND TUB BE
 INSTALLED? PLANS DO NOT PROVIDE WHAT TYPE OF BACKING
 WILL BE USED, RESPONCE COMMENT INDICATES SEE DETAIL ON
 A-511. IS THE BACKING TO BE APPLIED TO THE SURFACE OF
 THE ASSEMBLY UL-438?
  
 20C) 2ND REQUEST, DETAIL1/A-403 FIRST FLOOR LEVEL,
 INDICATES ROOM# 114 TO THE MACHINE ROOM FOR ELEVATOR#
 2, REQUIRING A 2 HR RATING WITH 1 1/2 HR RATED DOOR.
 PLEASE CORRECT. THE WALL THE DOOR IS LOCATED IN DOESN'T
 EVEN HAVE A WALL IDENTIFICATION TAG. NOTE NO STC RATING
 FOR 3HR BLOCK.
  
 20D) 2ND REQUEST,DETAIL1/A-403 ELEVATOR MACHINE ROOM
 WALL IDENTIFICATION TAG SHOULD READ A 2HR FIRE RATING
 WITH 1 1/2 HR OPENING PROTECTION. TAG IS NOW 1C OR 1 HR
 RATED.
  
 20E)COMPLIED. NOTE THE WALL THAT BACKS UP TO THE
 EXERCISE ROOM IS NOT LABELED.
  
 20F) COMPLIED.
  
 20G)2ND REQUEST,EXERCISE ROOM DOOR 118 TO BE FIRE
 RATED IN HRS/ MIN. TABLE 715.3SIZE OF WIRE PANEL?
  
 20H) COMPLIED.
  
 20I) 2ND REQUEST, SHOW ON PLAN, 2ND - 5TH FLOORS SAME
 ISSUES, THE ELECTRICAL ROOM DOOR IS MISSING
 IDENTIFICATION TAG AND FIRE RATING.707.4.
  
 20I)2ND REQUEST,STORAGE ROOM 251 COMMON 2ND- 5TH
 FLOOR, THIS IS A RATED CORRIDOR TABLE 1016 WALL
 IDENTIFICATION TAG SHOULD INDICATE AS SUCH AND IN DOOR
 SCHEDULE. TABLE 715.3. THIS IS A DETAIL OR ENLARGED
 PLAN AND SHOULD SHOW WALLTHE RATED WALLS.
  
 20K) 2ND REQUEST, AGAIN THIS IS AN ENLARGED PLAN AND
 SHOULD INDICATE WALL TAGS. STORAGE ROOM 318/ 418
 STORAGE ROOM WALLS AS WELL AS THE MAINTENANCE ROOM 518,
 1 HR RATED, DOORS TTABLE TABLE 715.3.
  
 21) 2ND REQUEST, SEMI COMPLIED. SHEET A-701 DOES
 INDICATE THE STAIRWAY TO THE ROOF BUT AGAIN THE DOORWAY
 TO THE ROOF IS NOT IN THE DOOR SCHEDULE AS WELL AS THE
 OTHER STAIRWELL DOORS.
  
 22) 2ND REQUEST, SHEET A-301 PLANS INDICATE THE USE OF
 CORRIGATED METAL DECK, DENSE DECK AND ICE & WATER
 SHIELD. THIS SECTION WAS TAKEN FROM THE ENTRY AREA
 FIRST FLOOR.ON THE SHEET A-301 PLANS INDICATE THE USE
 OF UL# P523 WHERE UNDER THIS LISTING C/D PLYWOOD CAN BE
 USED. PLEASE CORRECT, ALSO PROVIDE US WITH WHAT TYPE OF
 DENSE-GLASS PRODUCT WILL BE USED AS SHEATHING MATERIAL
 FOR THE ROOF?
  
 23) COMPLIED.
  
 24)2ND REQUEST,SHEET A-301ENLARGED SECTION DETAIL OF
 ROOF INDICATED A STEEL DECK DENSEGLASS AND ICE & WATER
 SHIELD UNDERLAYMENT, SHEET A-302DETAIL # 3INDICATES
 THE USE OF A (P540) U.L. LISTED ROOF/ CEILING ASSEMBLY.
 AS PART OF THIS SYSTEM PART # 5 INDICATES THE USE OF
 VARIOUS ROOFING INSULATIONS USED ABOVE THE STEEL DECK
 PLEASE CORRALATE AND CORRECT .THE PLANS INDICATE FOR
 THE SAME ROOF SECTION P523 AND P540?
  
 25) 2ND REQUEST, SHEET A-303 DETAIL# 3 NOW INDICATES
 THE USSE OF UL LISTING # J-956 FOR THE FLOOR SYSTEM AND
 ROOF SYSTEM. PLEASE PROVIDE THE EQUIVALENT THICKNESS
 REQUIRED FOR THIS FLOOR SYSTEM AND ROOF SYSTEM FOR THE
 TYPE OF AGGREGATE FOUND IN THIS AREA. UL LIST BLAST
 FURNACE SLAG AGGRIGATE FOR THE TYPE AGGREGATE FOR THEIR
 UL RATING FLOOR CEIOLING ASSEMBLIES. PLEASE SEE
 721.2.2.1.1 HOLLOW-CORE PRESTRESSED SLABS.
 FOR HOLLOW-CORE PRESTRESSED CONCRETE SLABS IN WHICH THE
 CORES ARE OF CONSTANT CROSS SECTION THROUGHOUT THE
 LENGTH, THE EQUIVALENT THICKNESS SHALL BE PERMITTED TO
 BE OBTAINED BY DIVIDING THE NET CROSS-SECTIONAL AREA OF
 THE SLAB INCLUDING GROUT IN THE JOINTS, BY ITS WIDTH.
 721.2.2.1 REINFORCED AND PRESTRESSED FLOORS AND ROOFS.
  
 THE MINIMUM THICKNESSES OF REINFORCED AND PRESTRESSED
 CONCRETE FLOOR OR ROOF SLABS FOR FIRE-RESISTANCE
 RATINGS OF 1 HOUR TO 4 HOURS ARE SHOWN IN TABLE
 721.2.2.1 .
 TABLE 601
  
 26) COMPLIED.
  
 27) COMPLIED.
  
 28) 2ND REQUEST,RESPONSE INDICATES TO SEE INTERIOR
 DRAWINGS, INDEX INDICATES THERE ARE NONE IN THIS PLAN.
 A-702 PLANS DO NOT INDICATE REQUIREMEENTS FOR BRAILLE
 CHARACTERS AT HOISTWAY ENTRANCES. 11-4.10.5 RAISED AND
 BRAILLE CHARACTERS ON HOISTWAY ENTRANCES. ALL ELEVATOR
 HOIST WAY ENTRANCES SHALL HAVE RAISED AND BRAILLE FLOOR
 DESIGNATIONS PROVIDED ON BOTH JAMBS. THE CENTERLINE OF
 THE CHARACTERS SHALL BE 60 INCHES (1525 MM) ABOVE
 FINISH FLOOR. SUCH CHARACTERS SHALL BE 2 INCHES (50 MM)
 HIGH AND SHALL COMPLY WITH SECTION 11-4.30.4 .
 PERMANENTLY APPLIED PLATES ARE ACCEPTABLE IF THEY ARE
 PERMANENTLY FIXED TO THE JAMBS (SEE FIGURE 11-20 ).
  
 29A) 2ND REQUEST1609.1.4 PROTECTION OF OPENINGS. IN
 WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 29B)2ND REQUEST, PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 29C) 2ND REQUEST, WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.]
  
 29D) 2ND REQUEST, RESPONSE INDICATES APPROVALS IN
 PACKAGE ONLY A RUSKIN LOUVER WAS SUBMITTED!!!
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, PROVIDE
 2 COPIES
 (3)IF THRESHOLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOW
 FIXED
 SINGLE HUNG
 MULLION
 B) GLAZED DOORS
 AUTOMATIC HORIZONTAL SLIDING DOORS
 EXTERIOR HOLLOW METAL DOORS
 C) LOUVERS
 D) PANEL WALL SYSTEMS
 SOFFITS- HARDI SOFFIT BOARD
 E) STRUCTURAL COMPONENTS- TRUSS ANCHORS
 F) ROOF ASSEMBLIES
 FLAT ROOFS- MODIFIED/ BITUMEN
 SLOPED:UNDERLAYMENTS, ROOF TILE ADHESIVES, ROOF
 TILE APPLICATIONS
  
 30)NOTED AND COMPLIED,ASEPERATE PERMIT IS REQUIRED
 FOR THE POOL, POOL EQUIPMENT BUILDING , POOL FENCING
 AND SIGNAGE.
  
 31) 2ND REQUEST, BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT
 OF THE ADDITIONAL INFORMATION REQUESTED ADDITIONAL
 COMMENTS
 MAY APPEAR THAT WERE NOT PART OF THIS REVIEW.
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]