| Date |
Text |
| 2007-05-02 10:04:14 | |
| | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2001 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | |
| | 2. SHTS G-000 THRU G-003 THE FIRM LICENSE NUMBER AND |
| | THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT ARE |
| | REQUIRED ON EACH SHEET. FAC 61G1-16.004(2)(6) & FS |
| | 481.219, 481.2055.-THE EMBOSSED SEAL SHALL IMPRESS |
| | ALL INFORMATION REQUIRED BY FAC G1G1-16.002 & FS |
| | 481.2055. NOT ALL INFORMATION REQUIRED IS IMPRESSED ON |
| | EACH SHEET. PLEASE MAKE SURE THE REQUIRED INFORMATION |
| | IS IN THE TITLE BLOCK AND RESEAL THE PLANS MAKING SURE |
| | ALL INFORMATION IS IMPRESSED & LEGIBLE WHEN SEALING THE |
| | PLANS. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 3. ALL ARCHITECTURAL SHEETS THE TITLE BLOCK SHALL |
| | INDICATE THE FIRM LICENSE NUMBER,AND THE PRINTED NAME |
| | OF THE PERSON SEALING THE DOCUMENT. FAC |
| | 61G1-16.004(2)(6) & FS 481.219, 481.2055. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 4.SHTS SP-1, LP-1, LP-2 & LP-3. THE ADDRESS OF THE |
| | LANDSCAPE ARCHITECT DOES NOT REFLECT THE ADDRESS |
| | INDICATED ON THE DBPR WEBSITE. (SEE ATTACHED SHEET FROM |
| | THE STATE WEBSITE). PLEASE SHOW CORRECT ADDRESS IN THE |
| | TITLE BLOCK OR UPDATE THE ADDRESS WITH THE STATE DBPR |
| | WEBSITE. FAC 61G1-16.004(1) & FS 481.2055. ****RESPONSE |
| | NOTED, BUT NOT ALL INFORMATION REQUIRED FOR THE SEAL |
| | HAS BEEN IMPRESSED ON EACH SHEET. NOT ALL INFORMATION |
| | IS LEGIBLE. |
| | |
| | 5. ALL STRUCTURAL SHEETS. THE ENGINEERS SHALL LEGIBLY |
| | INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON |
| | EACH SHEET. IF PRACTICING THROUGH A DULY AUTHORIZED |
| | ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE |
| | THEIR NAME & LICENSE NUMBER, AS WELL AS, THE NAME, |
| | ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE |
| | ENGINEERING BUSINESS ON EACH SHEET. FAC 61G15-23.002(2) |
| | & FS 471.025. THE BUSINESS NUMBER, (CERTIFICATE OF |
| | AUTHORIZATION), FOR PFVS ARCHITECTURE IS REQUIRED IN |
| | THE TITLE BLOCK AS WELL. FAC 61G1-16.004(2) & FS |
| | 481.219, 481.2055. |
| | ****NO RESPONSE. THE CA NUMBER'S FOR THE STRUCTURAL |
| | ENGINEER AND PFVS ARCHITECTS ARE STILL REQUIRED AND NOT |
| | INDICATED IN THE TITLE BLOCKS. (EACH SHEET). |
| | |
| | 6. OK (INFORMATIONAL ONLY) |
| | |
| | 7. SHT AC104 POOL HOUSE PLAN. MENS TOILET ROOM REQUIRES |
| | A URINAL. PLEASE INDICATE ON PLANS. TABLE 424.1.6.1. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 8. SHTS G-000 GUESTROOM MATRIX DOES NOT REFLECT THE |
| | FLOOR PLANS ON SHTS A-101 THRU A-105. THE MATRIX |
| | INDICATES A STUDIO AND A TWO BEDROOM ONLY TO BE |
| | ACCESSIBLE, BUT THE FLOOR PLAN ALSO SHOWS AN ACCESSIBLE |
| | DOUBLE QUEEN. ALSO THE 5TH FLOOR ON THE MATRIX |
| | INDICATES AN ACCESSIBLE KING, BUT NO ACCESSIBLE UNIT IS |
| | INDICATED ON THE FLOOR PLAN. PLEASE CORRELATE THE |
| | INFORMATION BETWEEN THE MATRIX AND THE FLOOR PLANS. |
| | SECTIONS 106.1.1 AND 11-9.1.2. |
| | ****RESPONSE WAS TO CHANGE MATRIX TO SHT G-002, BUT THE |
| | 5TH FLOOR ON THE MATRIX INDICATES AN ACCESSIBLE KING, |
| | BUT NO ACCESSIBLE UNIT IS INDICATED ON THE FLOOR PLAN. |
| | |
| | |
| | 9. PER SECTION 11-9.1.3, FIVE UNITS ARE REQUIRED TO BE |
| | COMPLIANT FOR THE HEARING IMPAIRED. ONLY 4 UNITS, (200, |
| | 202, 300 & 319), ARE INDICATED AS BEING COMPLIANT. |
| | PLEASE CLARIFY. |
| | ****NO RESPONSE, BUT NOW UNITS 300 & 319 HAVE BEEN |
| | DELETED AND ONLY 3 UNITS ARE SHOWN AS UNIT 219 HAS BEEN |
| | ADDED. INDICATE WHICH UNITS ARE DESIGNATED FOR THE |
| | HEARING IMPAIRED ON THE MATRIX AS WELL AS ON THE FLOOR |
| | PLANS. |
| | |
| | 10. SHT A-106 SUBMIT CALCULATIONS FOR THE PRIMARY AND |
| | SECONDARY ROOF DRAINS. SHOW THE AREA TO BE DRAINED FOR |
| | EACH ROOF DRAIN, AND INDICATE 1/2 THE AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS ADDED TO THAT AREA. |
| | ALSO INDICATE ALL AREAS FROM ROOF AREAS THAT DRAIN ONTO |
| | THE ROOF FROM ABOVE. SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS AND TABLES. INDICATE TOTAL AREA BEING |
| | DRAINED BY EACH DRAIN.-ALSO SEE SHT A-503. DETAIL 1 |
| | INDICATES A ROOF DRAIN, AN EMERGENCY OVERFLOW DRAIN AND |
| | AND AN OVERFLOW SCUPPER. PLEASE CLARIFY.IF THE |
| | OVERFLOW DRAIN AND THE OVERFLOW SCUPPER ARE BOTH |
| | INSTALLED, PLEASE SUBMIT A DETAIL FOR THE OVERFLOW |
| | SCUPPER SHOWING THE HEIGHT & WIDTH, AS WELL AS, THE |
| | MEASUREMENT FROM THE ROOF TO THE FLOW LINE OF THE |
| | OVERFLOW SCUPPER PER SECTION 1503.4.2 AND TABLE 1106.7. |
| | THIS IS REQUIRED FOR ALL 3 FLAT ROOF AREAS. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 11. SHT A-402 EMPLOYEE BREAK ROOM SINK SHALL COMPLY |
| | WITH SECTION 11-4.24 AND ALL SUBSECTIONS. INDICATE ON |
| | FLOOR PLAN AND SINK ELEVATION. |
| | ****NO RESPONSE. PLEASE SHOW THE FOLLOWING: |
| | A. 11-4.24.3 KNEE CLEARANCE |
| | B. 11-4.24.4 SINK DEPTH |
| | C. 11-4.24.5 CLEAR FLOOR SPACE |
| | D. 11-4.24.7 FAUCETS |
| | |
| | 12. SHT A-402 EMPLOYEE TOILET ROOM SHALL COMPLY WITH |
| | SECTIONS 11-4.16, 11-4.19, 11-4.22 & ALL SUBSECTIONS. |
| | PLEASE INDICATE ON ELEVATIONS. |
| | ****NO RESPONSE NOTED. PLEASE SHOW THE FOLLOWING: __FOR |
| | W/C'S: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.24.3 HEIGHT |
| | C. 11-4.24.5 FLUSH CONTROLS |
| | __FOR LAVS: |
| | A. 11-4.19.2 HEIGHT & CLEARANCES |
| | B. 11-4.19.3 CLEAR FLOOR SPACE |
| | C. 11-4.19.5 FAUCETS |
| | SHOW THE LAVS TO BE 15" MIN OFF THE WALL TO THE |
| | CENTERLINE OF THE FIXTURE. |
| | |
| | 13. SHT A-406 DETAILS 1, 2, 3 & 4. SHOW THE CLEAR FLOOR |
| | SPACE FOR ALL ACCESSIBLE FIXTURES PER SECTIONS |
| | 11-4.16.2, 11-4.19.3, 11-4.20.2, 11-4.21.2 & |
| | 11-4.24.5. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 14. SHT A-408 SHOW THE CLEAR FLOOR SPACE FOR ALL |
| | ACCESSIBLE FIXTURES PER SECTIONS 11-4.15.5, 11-4.16.2, |
| | 11-4.18.3 & 11-4.19.3, & 11-4.22..3. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 15. SHT A-605 THE FINISH SCHEDULE FOR ROOMS 28 & 29 |
| | SHOW PAINT OR V.W.C. FOR THE WALLS. SECTION 1210.2 |
| | CALLS FOR "SMOOTH, HARD, NONABSORBENT" SURFACES. PAINT |
| | AND V.W.C. DO NOT COMPLY WITH THE "HARD" REQUIREMENT. |
| | PLEASE COMPLY. |
| | ****RESPONSE ON PLANS INDICATE CT WAINSCOTT TO 4'0" |
| | AFF, BUT DOES NOT INDICATE WHICH WALLS. (N, S, E, W). |
| | |
| | 16. SHT A-804 APPLICABLE ELEVATIONS 1 THRU 11,A-805 |
| | APPLICABLE ELEVATIONS 1- THRU 9, SHALL COMPLY WITH |
| | SECTIONS 11-4.16, 11-4.18, 11-4.19, 11-4.20, 11-4.21 & |
| | 11-4.22 AND ALL SUBSECTIONS. PLEASE INDICATE ON |
| | ELEVATIONS. ALSO SHOW ALL LAVS TO BE MIN. 15" OFF THE |
| | WALL TO THE CENTERLINE OF THE FIXTURE WHERE THE |
| | FIXTURES ARE ADJACENT TO THE WALLS. FIGURE 11-32. |
| | ****NO RESPONSE NOTED. SHOW THE FOLLOWING: |
| | __FOR W/C'S: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.3 HEIGHT |
| | C. 11-4.16.5 FLUSH CONTROLS |
| | __FOR LAVS: |
| | A. 11-4.19.2 HEIGHT & CLEARANCES |
| | B. 11-4.19.3 CLEAR FLOOR SPACE |
| | C. 11-4.19.5 FAUCETS |
| | __FOR TUBS: |
| | A. 11-4.20.2 CLEAR FLOOR SPACE |
| | B. 11-4.20.3 SEAT |
| | __FOR SHOWERS: |
| | A. 11-4.21.3 SEAT (FOLDING TYPE) |
| | |
| | 17. SHT A-808 ELEVATION DETAIL 9. THE SINK SHALL BE |
| | ACCESSIBLE & SHALL COMPLY WITH SECTION 11-4.24 AND ALL |
| | SUBSECTIONS. PLEASE SHOW COMPLIANCE. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 18. SHT A-809 ELEVATIONS 4 & 9. THE SINK SHALL COMPLY |
| | WITH SECTION 11-4.24 AND ALL SUBSECTIONS. A FORWARD |
| | APPROACH CLEAR FLOOR SPACE IS REQUIRED AND SHALL EXTEND |
| | A MAXIMUM OF 19" UNDERNEATH THE SINK. CABINET DOORS ARE |
| | NOT APPROVED IN THE CLEAR FLOORSPACE AND ARE NOT TO |
| | BE INSTALLED. SUBMIT A SIDE ELEVATION SHOWING THE |
| | GARBAGE DISPOSAL. INDICTE COMPLIANCE WITH FIGURE 11-31. |
| | THE GARBAGE DISPOSAL SHALL BE ADA APPROVED LOW PROFILE |
| | TYPE THAT DOES NOT ENTER THE REQUIRED CLEAR FLOOR SPACE |
| | OF THE SINK.SECTION 106.1.1. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 19. SHT A-810 DETAILS 6, 7 & 8 SHOW A WATER FEATURE. |
| | MORE INFORMATION IS REQUIRED. PLEASE INDICATE IF THERE |
| | WILL BE A CONNECTION TO THE POTABLE WATER OR A |
| | CONNECTION TO THE SANITARY DRAINAGE SYSTEM. IF THE |
| | WATER IS CONNECTED TO THE POTABLE WATER SYSTEM, |
| | BACKFLOW PROTECTION WILL BE REQUIRED. SECTIONS 106.1.1 |
| | & 608.13. |
| | ****NO RESPONSE, BUT NOW THE DETAILS SHOW FIREPLACE |
| | ELEVATIONS. PLEASE INDICATE IF THE WATER FEATURE |
| | DETAILS HAVE BEEN MOVED OR IF THE WATER FEATURE HAS |
| | BEEN DELETED. |
| | |
| | 20. OK. |
| | 21. OK |
| | 22. OK |
| | 23. OK |
| | 24. OK |
| | 25. OK |
| | 26. OK |
| | |
| | 27. SUBMIT A PLAN LAYOUT OF ALL PLUMBING SANITARY |
| | DRAINAGE, WASTE & VENT. INDICATE THE FIXTURE MARK |
| | DESIGNATION TO CORRELATE WITH THE PLUMBING SCHEDULE |
| | SHOWN ON SHT P601 AND REFLECT THE SANITARY RISER |
| | DIAGRAMS. THIS SHALL BE SUBMITTED FOR EACH UNIT TYPE. |
| | SHTS P401 & P402 DO NOT SHOW THE SANITARY PIPING IN THE |
| | UNIT, ONLY THE RISER LOCATIONS. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT SHEET P503 WAS NOT SUBMITTED. |
| | |
| | 28. SHT P501 DETAIL 1 DOES NOT REFLECT THE FLOOR PLAN. |
| | KING UNIT SHOW A KIT SINK, (P6), A LAV (P3), A TUB |
| | (P8), AND A W/C (P1), BUT DETAIL SHOWS A P6, ANOTHER |
| | P6, A P1 THEN A P8. PLEASE CORRELATE THE RISER AND THE |
| | FLOOR PLAN. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT UNTILL A PLUMBING PLAN PIPING |
| | LAYOUT IS SUBMITTED THAT REFLECTS THE RISER DIAGRAM, |
| | THE RISER DIAGRAM CAN NOT BE VERIFYED OR APPROVED. (SEE |
| | COMMENT 27). IT STILL SEEMS LIKE THE TUB, (P8), IS |
| | BEFORE THE W/C, (P1), ON THE FLOOR PLAN, BUT IS SHOWN |
| | OPPOSITE ON THE RISER DIAGRAM. |
| | |
| | 29. SHT P501 DETAIL 2 DOES NOT REFLECT THE FLOOR PLAN, |
| | (SHT P401) . THE TYPICAL STUDIO UNIT SHOWS A KIT SINK, |
| | (P6), A LAV (P3), A SHOWER (INDICATED AS 7A, NO 7A |
| | SHOWN ON THE FIXTURE SCHEDULE), AND A W/C (P1), BUT |
| | DETAIL SHOWS A P6, ANOTHER P6, A P1 THEN A P7A. PLEASE |
| | CORRELATE THE RISER,THE FLOOR PLAN, AND THE FIXTURE |
| | SCHEDULE. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THE STUDIO FLOOR PLAN IS |
| | DIFFERENT FROM THE STUDIO ACC FLOOR PLAN. THE RISER CAN |
| | NOT BE TYPICAL FOR BOTH. SEPARATE RISER DIAGRAMS ARE |
| | REQUIRED FOR THE DIFFERENT FLOOR PLANS. |
| | |
| | 30. SUBMIT A DWV RISER FOR THE GUEST LAUNDRY ROOM. SHOW |
| | ALL PIPE SIZES, TRAPS, STANDPIPES,ETC. SECTION |
| | 106.3.5.1.3, 1002.1, TABLES 710.1(1) & 710.1(2). |
| | ****RESPONSE NOTED, BUT THE STANDPIPES ARE NOT SHOWN ON |
| | THE RISER DIAGRAM. ALSO THERE SHALL BE A CLEANOUT, |
| | MINIMUM 4'0" AFF ON EACH WASH MACHINE STACK. SECTION |
| | 708.9. |
| | |
| | 31. SUBMIT A SANITARY HORIZONTAL BUILDING DRAIN |
| | ISOMETRIC RISER DIAGRAM THAT REFLECT THE FLOOR PLAN. |
| | SHOW ALL PIPE SIZES, RISER LOCATIONS, TRAPS AND DFU'S |
| | AS THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3. |
| | -SHOW ALL THE FIRST FLOOR FIXTURES NOT CONNECTED TO A |
| | VERTICAL RISER ON THE HORIZONTAL RISER DIAGRAM. (SEE |
| | BREAK ROOM, FOOD PREP, LAUNDRY ROOM, TOILET ROOMS, PUMP |
| | ROOM ETC.). |
| | ****RESPONSE NOTED, BUT SHEET P503 HAS NOT BEEN |
| | SUBMITTED. |
| | |
| | 32. SUBMIT A HORIZONTAL BUILDING WATER ISOMETRIC RISER |
| | DIAGRAM. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER |
| | ARRESTORS, (REQUIRED BY SECTION 604.9 FOR ICE MAKERS, |
| | WASH MACHINES, AND DISHWASHERS). |
| | ****RESPONSE NOTED, BUT A HORIZONTAL WATER ISOMETRIC |
| | HAS HOT BEEN SUBMITTED. ONLY VERTICAL RISERS ARE |
| | SUBMITTED. |
| | |
| | 33. SUBMIT A HORIZONTAL BUILDING CONDENSATE ISOMETRIC |
| | RISER DIAGRAM AND VERTICAL RISER DIAGRAMS. SHOW ALL |
| | PIPE SIZES AND INDICATE THE TERMINATION POINT. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. SUBMIT |
| | HORIZONTAL AND VERTICAL RISERS AS REQUESTED. IF |
| | CONNECTING TO THE STORM LINE, A RELIEF VENT SHALL BE |
| | INSTALLED IN THE CONDENSATE LINE/LINES AS THEY EXIT THE |
| | BUILDING. |
| | |
| | 34. INDICATE A NUMBER DESIGNATION FOR EACH RISER |
| | INCLUDING ALL SANT., WATER, STORM, CONDENSATE. (EXAMPLE |
| | SANT-1, SANT-2, RWL-1, RWL-2, CON-1, CON-2, W-1, W-2 |
| | ETC.). THIS WILL AID IN TRACKING ALL RISERS FROM THE |
| | UNDERGROUND PIPING THROUGH THE ROOF. SECTIONS |
| | 106.3.5.1.3 & SECTION 106.1.1.--INDICATE WHICH |
| | RISER IS TYPICAL OF WHICH RISER ISOMETRIC DIAGRAM. |
| | (EXAMPLE SANT-1 SANT-4 TYPICAL OF DETALI 4 SHT P401) -- |
| | INDICATE ROOM NUMBER EACH RISER CAN BE LOCATED. |
| | ****RESPONSE NOTED, BUT SHEET P503 HAS NOT BEEN |
| | SUBMITTED. |
| | |
| | 35. ROUTE PLANS TO THE DEPT. OF BUSINESS REGULATION, |
| | HOTEL & RESTURANT DIVISION FOR REVIEW PRIOR TO |
| | RESUBMITTING TO THE CITY FOR REVIEW. A MINIMUM OF TWO |
| | SETS OF PLANS, STAMPED BY DBPR AND TWO PAGE |
| | "WORKSHEETS" ATTACHED TO PLAN ARE REQUIRED. SECTION |
| | 102.2.1. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | 36. SHT A-101, A FOOD PREP AREA IS INDICATED. A GREASE |
| | INTERCEPTOR MAY BE REQUIRED. A MINIMUM 750 GAL. |
| | INTERCEPTOR IS REQUIRED. PLEASE CONTACT LMASSON, |
| | ENVIRONMENTAL COMPLIANCE MANAGER FOR SIZING OF THE |
| | GREASE INTERCEPTOR. CONTACT HER BY PHONE (561) |
| | 822-2271, FAX (561) 822-2279, OR E-MAIL |
| | [email protected]. |
| | ****RESPONSE NOTED, BUT NO APPROVAL FROM ENVIRONMENTAL |
| | COMPLIANCE HAS BEEN NOTED. I WILL PROCEED WITH AN |
| | INQUIRY AT THIS END. |
| | |
| | 37. PLANS DO NOT APPEAR TO BE 100% AT THIS TIME AND |
| | MORE OR DIFFERENT COMMENTS MAY BE FORTHCOMING DEPENDING |
| | ON THE REVISIONS OR COMMENT RESPONSES. ****INFORMATION |
| | REQUIRED STILL NOT ALL SUBMITTED AT THIS TIME. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | -PLEASE RESUBMIT ONE SET OF OLD SHEETS |
| | FOR COMPARISON. |
| | ****NO RESPONSE, NOT ADDRESSED. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |