Plan Review Notes
Plan Review Notes For Permit 06111071
Permit Number 06111071
Review Stop P
Sequence Number 2
Notes
Date Text
2007-05-02 10:04:14 
 DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2001 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHTS G-000 THRU G-003 THE FIRM LICENSE NUMBER AND
 THE PRINTED NAME OF THE PERSON SEALING THE DOCUMENT ARE
 REQUIRED ON EACH SHEET. FAC 61G1-16.004(2)(6) & FS
 481.219, 481.2055.-THE EMBOSSED SEAL SHALL IMPRESS
 ALL INFORMATION REQUIRED BY FAC G1G1-16.002 & FS
 481.2055. NOT ALL INFORMATION REQUIRED IS IMPRESSED ON
 EACH SHEET. PLEASE MAKE SURE THE REQUIRED INFORMATION
 IS IN THE TITLE BLOCK AND RESEAL THE PLANS MAKING SURE
 ALL INFORMATION IS IMPRESSED & LEGIBLE WHEN SEALING THE
 PLANS.
 ****NO RESPONSE, NOT ADDRESSED.
  
 3. ALL ARCHITECTURAL SHEETS THE TITLE BLOCK SHALL
 INDICATE THE FIRM LICENSE NUMBER,AND THE PRINTED NAME
 OF THE PERSON SEALING THE DOCUMENT. FAC
 61G1-16.004(2)(6) & FS 481.219, 481.2055.
 ****NO RESPONSE, NOT ADDRESSED.
  
 4.SHTS SP-1, LP-1, LP-2 & LP-3. THE ADDRESS OF THE
 LANDSCAPE ARCHITECT DOES NOT REFLECT THE ADDRESS
 INDICATED ON THE DBPR WEBSITE. (SEE ATTACHED SHEET FROM
 THE STATE WEBSITE). PLEASE SHOW CORRECT ADDRESS IN THE
 TITLE BLOCK OR UPDATE THE ADDRESS WITH THE STATE DBPR
 WEBSITE. FAC 61G1-16.004(1) & FS 481.2055. ****RESPONSE
 NOTED, BUT NOT ALL INFORMATION REQUIRED FOR THE SEAL
 HAS BEEN IMPRESSED ON EACH SHEET. NOT ALL INFORMATION
 IS LEGIBLE.
  
 5. ALL STRUCTURAL SHEETS. THE ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS, AND LICENSE NUMBER ON
 EACH SHEET. IF PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME & LICENSE NUMBER, AS WELL AS, THE NAME,
 ADDRESS, AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS ON EACH SHEET. FAC 61G15-23.002(2)
 & FS 471.025. THE BUSINESS NUMBER, (CERTIFICATE OF
 AUTHORIZATION), FOR PFVS ARCHITECTURE IS REQUIRED IN
 THE TITLE BLOCK AS WELL. FAC 61G1-16.004(2) & FS
 481.219, 481.2055.
 ****NO RESPONSE. THE CA NUMBER'S FOR THE STRUCTURAL
 ENGINEER AND PFVS ARCHITECTS ARE STILL REQUIRED AND NOT
 INDICATED IN THE TITLE BLOCKS. (EACH SHEET).
  
 6. OK (INFORMATIONAL ONLY)
  
 7. SHT AC104 POOL HOUSE PLAN. MENS TOILET ROOM REQUIRES
 A URINAL. PLEASE INDICATE ON PLANS. TABLE 424.1.6.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 8. SHTS G-000 GUESTROOM MATRIX DOES NOT REFLECT THE
 FLOOR PLANS ON SHTS A-101 THRU A-105. THE MATRIX
 INDICATES A STUDIO AND A TWO BEDROOM ONLY TO BE
 ACCESSIBLE, BUT THE FLOOR PLAN ALSO SHOWS AN ACCESSIBLE
 DOUBLE QUEEN. ALSO THE 5TH FLOOR ON THE MATRIX
 INDICATES AN ACCESSIBLE KING, BUT NO ACCESSIBLE UNIT IS
 INDICATED ON THE FLOOR PLAN. PLEASE CORRELATE THE
 INFORMATION BETWEEN THE MATRIX AND THE FLOOR PLANS.
 SECTIONS 106.1.1 AND 11-9.1.2.
 ****RESPONSE WAS TO CHANGE MATRIX TO SHT G-002, BUT THE
 5TH FLOOR ON THE MATRIX INDICATES AN ACCESSIBLE KING,
 BUT NO ACCESSIBLE UNIT IS INDICATED ON THE FLOOR PLAN.
  
  
 9. PER SECTION 11-9.1.3, FIVE UNITS ARE REQUIRED TO BE
 COMPLIANT FOR THE HEARING IMPAIRED. ONLY 4 UNITS, (200,
 202, 300 & 319), ARE INDICATED AS BEING COMPLIANT.
 PLEASE CLARIFY.
 ****NO RESPONSE, BUT NOW UNITS 300 & 319 HAVE BEEN
 DELETED AND ONLY 3 UNITS ARE SHOWN AS UNIT 219 HAS BEEN
 ADDED. INDICATE WHICH UNITS ARE DESIGNATED FOR THE
 HEARING IMPAIRED ON THE MATRIX AS WELL AS ON THE FLOOR
 PLANS.
  
 10. SHT A-106 SUBMIT CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE AREA TO BE DRAINED FOR
 EACH ROOF DRAIN, AND INDICATE 1/2 THE AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED TO THAT AREA.
 ALSO INDICATE ALL AREAS FROM ROOF AREAS THAT DRAIN ONTO
 THE ROOF FROM ABOVE. SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS AND TABLES. INDICATE TOTAL AREA BEING
 DRAINED BY EACH DRAIN.-ALSO SEE SHT A-503. DETAIL 1
 INDICATES A ROOF DRAIN, AN EMERGENCY OVERFLOW DRAIN AND
 AND AN OVERFLOW SCUPPER. PLEASE CLARIFY.IF THE
 OVERFLOW DRAIN AND THE OVERFLOW SCUPPER ARE BOTH
 INSTALLED, PLEASE SUBMIT A DETAIL FOR THE OVERFLOW
 SCUPPER SHOWING THE HEIGHT & WIDTH, AS WELL AS, THE
 MEASUREMENT FROM THE ROOF TO THE FLOW LINE OF THE
 OVERFLOW SCUPPER PER SECTION 1503.4.2 AND TABLE 1106.7.
 THIS IS REQUIRED FOR ALL 3 FLAT ROOF AREAS.
 ****NO RESPONSE, NOT ADDRESSED.
  
 11. SHT A-402 EMPLOYEE BREAK ROOM SINK SHALL COMPLY
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS. INDICATE ON
 FLOOR PLAN AND SINK ELEVATION.
 ****NO RESPONSE. PLEASE SHOW THE FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE
 D. 11-4.24.7 FAUCETS
  
 12. SHT A-402 EMPLOYEE TOILET ROOM SHALL COMPLY WITH
 SECTIONS 11-4.16, 11-4.19, 11-4.22 & ALL SUBSECTIONS.
 PLEASE INDICATE ON ELEVATIONS.
 ****NO RESPONSE NOTED. PLEASE SHOW THE FOLLOWING: __FOR
 W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.24.3 HEIGHT
 C. 11-4.24.5 FLUSH CONTROLS
 __FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.5 FAUCETS
 SHOW THE LAVS TO BE 15" MIN OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE.
  
 13. SHT A-406 DETAILS 1, 2, 3 & 4. SHOW THE CLEAR FLOOR
 SPACE FOR ALL ACCESSIBLE FIXTURES PER SECTIONS
 11-4.16.2, 11-4.19.3, 11-4.20.2, 11-4.21.2 &
 11-4.24.5.
 ****NO RESPONSE, NOT ADDRESSED.
  
 14. SHT A-408 SHOW THE CLEAR FLOOR SPACE FOR ALL
 ACCESSIBLE FIXTURES PER SECTIONS 11-4.15.5, 11-4.16.2,
 11-4.18.3 & 11-4.19.3, & 11-4.22..3.
 ****NO RESPONSE, NOT ADDRESSED.
  
 15. SHT A-605 THE FINISH SCHEDULE FOR ROOMS 28 & 29
 SHOW PAINT OR V.W.C. FOR THE WALLS. SECTION 1210.2
 CALLS FOR "SMOOTH, HARD, NONABSORBENT" SURFACES. PAINT
 AND V.W.C. DO NOT COMPLY WITH THE "HARD" REQUIREMENT.
 PLEASE COMPLY.
 ****RESPONSE ON PLANS INDICATE CT WAINSCOTT TO 4'0"
 AFF, BUT DOES NOT INDICATE WHICH WALLS. (N, S, E, W).
  
 16. SHT A-804 APPLICABLE ELEVATIONS 1 THRU 11,A-805
 APPLICABLE ELEVATIONS 1- THRU 9, SHALL COMPLY WITH
 SECTIONS 11-4.16, 11-4.18, 11-4.19, 11-4.20, 11-4.21 &
 11-4.22 AND ALL SUBSECTIONS. PLEASE INDICATE ON
 ELEVATIONS. ALSO SHOW ALL LAVS TO BE MIN. 15" OFF THE
 WALL TO THE CENTERLINE OF THE FIXTURE WHERE THE
 FIXTURES ARE ADJACENT TO THE WALLS. FIGURE 11-32.
 ****NO RESPONSE NOTED. SHOW THE FOLLOWING:
 __FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.3 HEIGHT
 C. 11-4.16.5 FLUSH CONTROLS
 __FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.5 FAUCETS
 __FOR TUBS:
 A. 11-4.20.2 CLEAR FLOOR SPACE
 B. 11-4.20.3 SEAT
 __FOR SHOWERS:
 A. 11-4.21.3 SEAT (FOLDING TYPE)
  
 17. SHT A-808 ELEVATION DETAIL 9. THE SINK SHALL BE
 ACCESSIBLE & SHALL COMPLY WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. PLEASE SHOW COMPLIANCE.
 ****NO RESPONSE, NOT ADDRESSED.
  
 18. SHT A-809 ELEVATIONS 4 & 9. THE SINK SHALL COMPLY
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS. A FORWARD
 APPROACH CLEAR FLOOR SPACE IS REQUIRED AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE SINK. CABINET DOORS ARE
 NOT APPROVED IN THE CLEAR FLOORSPACE AND ARE NOT TO
 BE INSTALLED. SUBMIT A SIDE ELEVATION SHOWING THE
 GARBAGE DISPOSAL. INDICTE COMPLIANCE WITH FIGURE 11-31.
 THE GARBAGE DISPOSAL SHALL BE ADA APPROVED LOW PROFILE
 TYPE THAT DOES NOT ENTER THE REQUIRED CLEAR FLOOR SPACE
 OF THE SINK.SECTION 106.1.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 19. SHT A-810 DETAILS 6, 7 & 8 SHOW A WATER FEATURE.
 MORE INFORMATION IS REQUIRED. PLEASE INDICATE IF THERE
 WILL BE A CONNECTION TO THE POTABLE WATER OR A
 CONNECTION TO THE SANITARY DRAINAGE SYSTEM. IF THE
 WATER IS CONNECTED TO THE POTABLE WATER SYSTEM,
 BACKFLOW PROTECTION WILL BE REQUIRED. SECTIONS 106.1.1
 & 608.13.
 ****NO RESPONSE, BUT NOW THE DETAILS SHOW FIREPLACE
 ELEVATIONS. PLEASE INDICATE IF THE WATER FEATURE
 DETAILS HAVE BEEN MOVED OR IF THE WATER FEATURE HAS
 BEEN DELETED.
  
 20. OK.
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
 26. OK
  
 27. SUBMIT A PLAN LAYOUT OF ALL PLUMBING SANITARY
 DRAINAGE, WASTE & VENT. INDICATE THE FIXTURE MARK
 DESIGNATION TO CORRELATE WITH THE PLUMBING SCHEDULE
 SHOWN ON SHT P601 AND REFLECT THE SANITARY RISER
 DIAGRAMS. THIS SHALL BE SUBMITTED FOR EACH UNIT TYPE.
 SHTS P401 & P402 DO NOT SHOW THE SANITARY PIPING IN THE
 UNIT, ONLY THE RISER LOCATIONS. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT SHEET P503 WAS NOT SUBMITTED.
  
 28. SHT P501 DETAIL 1 DOES NOT REFLECT THE FLOOR PLAN.
 KING UNIT SHOW A KIT SINK, (P6), A LAV (P3), A TUB
 (P8), AND A W/C (P1), BUT DETAIL SHOWS A P6, ANOTHER
 P6, A P1 THEN A P8. PLEASE CORRELATE THE RISER AND THE
 FLOOR PLAN. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT UNTILL A PLUMBING PLAN PIPING
 LAYOUT IS SUBMITTED THAT REFLECTS THE RISER DIAGRAM,
 THE RISER DIAGRAM CAN NOT BE VERIFYED OR APPROVED. (SEE
 COMMENT 27). IT STILL SEEMS LIKE THE TUB, (P8), IS
 BEFORE THE W/C, (P1), ON THE FLOOR PLAN, BUT IS SHOWN
 OPPOSITE ON THE RISER DIAGRAM.
  
 29. SHT P501 DETAIL 2 DOES NOT REFLECT THE FLOOR PLAN,
 (SHT P401) . THE TYPICAL STUDIO UNIT SHOWS A KIT SINK,
 (P6), A LAV (P3), A SHOWER (INDICATED AS 7A, NO 7A
 SHOWN ON THE FIXTURE SCHEDULE), AND A W/C (P1), BUT
 DETAIL SHOWS A P6, ANOTHER P6, A P1 THEN A P7A. PLEASE
 CORRELATE THE RISER,THE FLOOR PLAN, AND THE FIXTURE
 SCHEDULE. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE STUDIO FLOOR PLAN IS
 DIFFERENT FROM THE STUDIO ACC FLOOR PLAN. THE RISER CAN
 NOT BE TYPICAL FOR BOTH. SEPARATE RISER DIAGRAMS ARE
 REQUIRED FOR THE DIFFERENT FLOOR PLANS.
  
 30. SUBMIT A DWV RISER FOR THE GUEST LAUNDRY ROOM. SHOW
 ALL PIPE SIZES, TRAPS, STANDPIPES,ETC. SECTION
 106.3.5.1.3, 1002.1, TABLES 710.1(1) & 710.1(2).
 ****RESPONSE NOTED, BUT THE STANDPIPES ARE NOT SHOWN ON
 THE RISER DIAGRAM. ALSO THERE SHALL BE A CLEANOUT,
 MINIMUM 4'0" AFF ON EACH WASH MACHINE STACK. SECTION
 708.9.
  
 31. SUBMIT A SANITARY HORIZONTAL BUILDING DRAIN
 ISOMETRIC RISER DIAGRAM THAT REFLECT THE FLOOR PLAN.
 SHOW ALL PIPE SIZES, RISER LOCATIONS, TRAPS AND DFU'S
 AS THEY ACCUMULATE IN THE SYSTEM. SECTION 106.3.5.1.3.
 -SHOW ALL THE FIRST FLOOR FIXTURES NOT CONNECTED TO A
 VERTICAL RISER ON THE HORIZONTAL RISER DIAGRAM. (SEE
 BREAK ROOM, FOOD PREP, LAUNDRY ROOM, TOILET ROOMS, PUMP
 ROOM ETC.).
 ****RESPONSE NOTED, BUT SHEET P503 HAS NOT BEEN
 SUBMITTED.
  
 32. SUBMIT A HORIZONTAL BUILDING WATER ISOMETRIC RISER
 DIAGRAM. SHOW ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS, (REQUIRED BY SECTION 604.9 FOR ICE MAKERS,
 WASH MACHINES, AND DISHWASHERS).
 ****RESPONSE NOTED, BUT A HORIZONTAL WATER ISOMETRIC
 HAS HOT BEEN SUBMITTED. ONLY VERTICAL RISERS ARE
 SUBMITTED.
  
 33. SUBMIT A HORIZONTAL BUILDING CONDENSATE ISOMETRIC
 RISER DIAGRAM AND VERTICAL RISER DIAGRAMS. SHOW ALL
 PIPE SIZES AND INDICATE THE TERMINATION POINT.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. SUBMIT
 HORIZONTAL AND VERTICAL RISERS AS REQUESTED. IF
 CONNECTING TO THE STORM LINE, A RELIEF VENT SHALL BE
 INSTALLED IN THE CONDENSATE LINE/LINES AS THEY EXIT THE
 BUILDING.
  
 34. INDICATE A NUMBER DESIGNATION FOR EACH RISER
 INCLUDING ALL SANT., WATER, STORM, CONDENSATE. (EXAMPLE
 SANT-1, SANT-2, RWL-1, RWL-2, CON-1, CON-2, W-1, W-2
 ETC.). THIS WILL AID IN TRACKING ALL RISERS FROM THE
 UNDERGROUND PIPING THROUGH THE ROOF. SECTIONS
 106.3.5.1.3 & SECTION 106.1.1.--INDICATE WHICH
 RISER IS TYPICAL OF WHICH RISER ISOMETRIC DIAGRAM.
 (EXAMPLE SANT-1 SANT-4 TYPICAL OF DETALI 4 SHT P401) --
 INDICATE ROOM NUMBER EACH RISER CAN BE LOCATED.
 ****RESPONSE NOTED, BUT SHEET P503 HAS NOT BEEN
 SUBMITTED.
  
 35. ROUTE PLANS TO THE DEPT. OF BUSINESS REGULATION,
 HOTEL & RESTURANT DIVISION FOR REVIEW PRIOR TO
 RESUBMITTING TO THE CITY FOR REVIEW. A MINIMUM OF TWO
 SETS OF PLANS, STAMPED BY DBPR AND TWO PAGE
 "WORKSHEETS" ATTACHED TO PLAN ARE REQUIRED. SECTION
 102.2.1.
 ****NO RESPONSE, NOT ADDRESSED.
  
 36. SHT A-101, A FOOD PREP AREA IS INDICATED. A GREASE
 INTERCEPTOR MAY BE REQUIRED. A MINIMUM 750 GAL.
 INTERCEPTOR IS REQUIRED. PLEASE CONTACT LMASSON,
 ENVIRONMENTAL COMPLIANCE MANAGER FOR SIZING OF THE
 GREASE INTERCEPTOR. CONTACT HER BY PHONE (561)
 822-2271, FAX (561) 822-2279, OR E-MAIL
 [email protected].
 ****RESPONSE NOTED, BUT NO APPROVAL FROM ENVIRONMENTAL
 COMPLIANCE HAS BEEN NOTED. I WILL PROCEED WITH AN
 INQUIRY AT THIS END.
  
 37. PLANS DO NOT APPEAR TO BE 100% AT THIS TIME AND
 MORE OR DIFFERENT COMMENTS MAY BE FORTHCOMING DEPENDING
 ON THE REVISIONS OR COMMENT RESPONSES. ****INFORMATION
 REQUIRED STILL NOT ALL SUBMITTED AT THIS TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 -PLEASE RESUBMIT ONE SET OF OLD SHEETS
 FOR COMPARISON.
 ****NO RESPONSE, NOT ADDRESSED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved