| Date |
Text |
| 2007-04-30 12:53:07 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS |
| | PERMIT. PLEASE SUBMIT THE FOLLOWING: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ****RESPONSE NOTED, BUT NOT ALL SECTIONS OF PIPES SHOW |
| | THE LENGTH.--ALSO THE ISOMETRIC RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN PRIOR TO AND AT THE TOP OF |
| | THE RISER TO THE APPLIANCE THAT INDICATES 150 CFH.-- |
| | PLEASE IDENTIFY ALL GAS APPLIANCES ON THE RISER |
| | DIAGRAM. (ONLY GAS GRILLS INDICATED).--SOLENOID |
| | VALVES IN THE CEILING ARE NOT REQUIRED. PLEASE DELETE. |
| | --UPSTREAM OF THE 4 WATER (200CFH) IS INDICATED AS |
| | 600CFH. THIS SHOULD BE 800CFH. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. ****RESPONSE |
| | NOTED, BUT SPECIFICATIONS HAVE NOT BEEN LOCATED, PLEASE |
| | INDICATE WHERE THE SPECIFICATIONS CAN BE FOUND, OR |
| | INDICATE THE INFORMATION AT THE GAS RISER DIAGRAM. |
| | |
| | 3. OK,NATURAL. |
| | |
| | 4. OK - BUT RESPONSE INDICATES SHT P101. P101 NOT |
| | SUBMITTED. |
| | |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A-USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ****RESPONSE NOTED, BUT WILL NOT BE ABLE TO VERIFY |
| | UNTIL ALL CUT SECTIONS INDICATE THE LENGTH. (SEE |
| | COMMENT 31). |
| | |
| | 6. OK |
| | |
| | 7. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | ****RESPONSE NOTED, BUT THE UTILITY COMPANY DOES NOT |
| | SUPPLY 1PSI METER. THE PRESSURE WILL BE EITHER 2PSI OR |
| | .5PSI. |
| | |
| | 8. OK |
| | |
| | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED,BUT THE MANUF. SHEETS WILL BE |
| | REQUIRED TO VERIFY CFH & LISTING. PLEASE INDICATE IF |
| | THE GAS INFORMATION WILL BE SUBMITTED AT THE TIME OF |
| | GAS PERMIT APPLICATION. IF SO ALL GAS APPROVAL WILL BE |
| | WITHELD UNTIL THEN. |
| | |
| | 10. N/A |
| | 11. N/A |
| | |
| | ***********NEW COMMENT********** |
| | |
| | 1B. SHTS P102 & M-102 SHOW THE WATER HEATERS IN |
| | DIFFERENT LOCATIONS ON THE FLOOR PLAN. THIS WILL EFFECT |
| | THE PIPING OF THE WATER, GAS, VENTING ETC. PLEASE |
| | CORRELATE THE LOCATION OF THE WATER HEATERS FROM THE |
| | MECHANICAL SHEET AND THE PLUMBING SHEET. SECTION |
| | 106.1.1. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |