Plan Review Notes
Plan Review Notes For Permit 06111071
Permit Number 06111071
Review Stop G
Sequence Number 2
Notes
Date Text
2007-04-30 12:53:07DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS
 PERMIT. PLEASE SUBMIT THE FOLLOWING:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 ****RESPONSE NOTED, BUT NOT ALL SECTIONS OF PIPES SHOW
 THE LENGTH.--ALSO THE ISOMETRIC RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN PRIOR TO AND AT THE TOP OF
 THE RISER TO THE APPLIANCE THAT INDICATES 150 CFH.--
 PLEASE IDENTIFY ALL GAS APPLIANCES ON THE RISER
 DIAGRAM. (ONLY GAS GRILLS INDICATED).--SOLENOID
 VALVES IN THE CEILING ARE NOT REQUIRED. PLEASE DELETE.
 --UPSTREAM OF THE 4 WATER (200CFH) IS INDICATED AS
 600CFH. THIS SHOULD BE 800CFH.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. ****RESPONSE
 NOTED, BUT SPECIFICATIONS HAVE NOT BEEN LOCATED, PLEASE
 INDICATE WHERE THE SPECIFICATIONS CAN BE FOUND, OR
 INDICATE THE INFORMATION AT THE GAS RISER DIAGRAM.
  
 3. OK,NATURAL.
  
 4. OK - BUT RESPONSE INDICATES SHT P101. P101 NOT
 SUBMITTED.
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A-USE
 OF CAPACITY TABLES A.3.1(4).
 ****RESPONSE NOTED, BUT WILL NOT BE ABLE TO VERIFY
 UNTIL ALL CUT SECTIONS INDICATE THE LENGTH. (SEE
 COMMENT 31).
  
 6. OK
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 ****RESPONSE NOTED, BUT THE UTILITY COMPANY DOES NOT
 SUPPLY 1PSI METER. THE PRESSURE WILL BE EITHER 2PSI OR
 .5PSI.
  
 8. OK
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED,BUT THE MANUF. SHEETS WILL BE
 REQUIRED TO VERIFY CFH & LISTING. PLEASE INDICATE IF
 THE GAS INFORMATION WILL BE SUBMITTED AT THE TIME OF
 GAS PERMIT APPLICATION. IF SO ALL GAS APPROVAL WILL BE
 WITHELD UNTIL THEN.
  
 10. N/A
 11. N/A
  
 ***********NEW COMMENT**********
  
 1B. SHTS P102 & M-102 SHOW THE WATER HEATERS IN
 DIFFERENT LOCATIONS ON THE FLOOR PLAN. THIS WILL EFFECT
 THE PIPING OF THE WATER, GAS, VENTING ETC. PLEASE
 CORRELATE THE LOCATION OF THE WATER HEATERS FROM THE
 MECHANICAL SHEET AND THE PLUMBING SHEET. SECTION
 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]