Plan Review Notes
Plan Review Notes For Permit 06111071
Permit Number 06111071
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-04-25 17:04:03*****DENIED*****
  
  
 01.THE COMPLETE ADDRESS OR ACTUAL ADDRESS OF WHERE
 THE SCOPE OF WORK WILL BE CONDUCTED SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.PLEASE
 COMPLY
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 COMMENT TO THE APPROPIATE PLAN SHEET(S)
  
 04.EXIT STAIRS ARE TO BE KEPT UP WITH CONSTRUCTION.
 ADD COMMENT TO THE APPROPIATE PLAN SHEET(S)
  
 05.KNOX-BOX WILL BE REQUIRED FOR THE BUILDING.FOR
 KNOX APPLICATIONS, CONTACT WEST PALM BEACH FIRE
 PREVENTION BUREAU AT 561-804-4724.IT APPEARS ON SHEET
 P101D THAT ACCESS WITHIN THE STRUCTURE CANNOT BE GAINED
 THROUGH THE PUMP ROOM.ACCESS/KNOX BOX IS TO BE
 INSTALLED IN AN ACCESSIBLE LOCATION WHERE ACCESS TO OR
 WITHIN THE STRUCTURE
  
 06. ON THE APPROPIATE EXTERIOR ELEVATION FRONTING
 METROCENTRE BOULEVARD EAST,POST THE NUMERICAL ADDRESS
 ON THE BUILDING.AS PER WEST PALM BEACH CODE, THOSE
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH.ONCE THIS PERMIT HAS BEEN ISSUED,
 THE NUMERICAL ADDRESS SHALL BE TEMPORARILY POSTED
 BEFORE & DURING CONSTRUCTION OPERATIONS, AND PERMANENLY
 POSTED AFTER CONSTRUCTION PRIOR TO ATTAINING A
 CERTIFICATE OF OCCUPANCY.IF THE BUILDING IS SET-BACK
 FROM THE STREET OR ROADSIDE, A NUMERICAL ADDRESS (THE
 SAME DIMENSIONS AS PER WEST PALM BEACH CODE) SHALL BE
 REQUIRED ON THE MONUMENT SIGN OR MARQUEE IN ADDITION TO
 THOSE ON THE BUILDING. PLEASE COMPLY
  
 07.TEMPORARY STANDPIPES ARE REQUIRED WHEN THE
 BUILDING REACHES THREE STORIES OR 30 FEET IN HEIGHT.
 ADD COMMENT TO THE APPROPIATE PLAN SHEET(S)
  
 08.FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA 80.
 ADD COMMENT TO PLAN SHEETS-A-603 AND A604
  
 09.DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL
 NOT HAVE LESS THAN A 20-MINUTE FIRE PROTECTION RATING.
 THOSE DOORS SHALL BE SELF-CLOSING AND SELF-LATCHING.
 ADD COMMENT TO SHEETA-603
  
 10.THE INTERIOR FINISH CLASSIFICATION FOR WALLS AND
 CEILING SHALL BE CLASS A FOR EXIT ENCLOSURES, CLASS A
 OR B FOR LOBBIES AND CORRIDORS, AND CLASS A, B, OR C
 FOR OTHER SPACES.SPECIFY WHAT THESE AREAS WILL BE ON
 SHEET G-000 AND A-605
  
 11.ELEVATOR WARNING SIGNS WILL BE REQUIRED IN THE
 LOBBIES.ADD COMMENT TO SHEETSA-403 AND A-404
  
 12.AT LEAST ONE IDENTIFIBLE ELEVATOR SHALL BE
 AVAILABLE FOR USE BY THE FIRE DEPARTMENT IN CASE OF
 EMERGENCY.ADD COMMENT TO SHEETSA-403 AND A-404
  
 13.A FLOOR DIAGRAM REFLECTING THE ACTUAL FLOOR
 ARRANGEMENT, EXIT LOCATIONS AND ROOM IDENTIFICATION
 SHALL BE POSTED IN A LOCATION AND MANNER ACCEPTABLE TO
 THE AHJ ON, OR IMMEDIATELY ADJACENT TO, EVERY GUEST
 ROOM IN THE HOTEL.ADD COMMENT TO THE APPROPIATE PLAN
 SHEET(S)
  
 14.SMOKE DETECTORS ARE NOT SHOWN FOR THE ELEVATOR
 LOBBY, ICE ROOM, OR ELECTRIC ROOM ON SHEETS E-101,
 E-102, E-103; HOWEVER THEY ARE CORRECTLY SHOWN ON
 SHEETS E-203 AND E-204.BE CONSISTENT IN THE LOCATION
 OF DEVICES ON THE PLAN SHEETS
  
 15.PLEASE PROVIDE A LAYOUT OF THE FIRE ALARM SYSTEM
 INDEPENDENT OF THE ELECTRICAL SHEETS.PLEASE COMPLY;
 SEE ELECTRICAL PLAN NOTE #12
  
 18.PLEASE PROVIDE A LAYOUT OF THE FIRE SPRINKLER
 SYSTEM INDEPENDENT OF THE PLUMBING SHEETS.INCLUDE THE
 LOCATION OF THE FIRE DEPARTMENT CONNECTION(S) AND THE
 DOUBLE DETECTOR CHECK VALVE ASSEMBLY.PLEASE COMPLY;
 SEE ELECTRICAL PLAN NOTE #12
  
 19.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK
 ARE REQUIRED FOR THE DOUBLE CHECK DETECTOR VALVE
 ASSEMBLY.ADD COMMENT TO THE FIRE SPRINKLER AND/OR
 FIRE ALARM PLAN SHEET
  
 20.KNOX LOCKING CAPS WILL BE REQUIRED ON FIRE
 DEPARTMENT CONNECTIONS (FDC). CONTACT WEST PALM BEACH
 FIRE PREVENTION AT 561-804-4724 FOR KNOX APPLICATIONS.
 ADD COMMENT TO THE APPROPIATE FIRE SPRINKLER PLAN
 SHEET
  
 21.PROVIDE SPECIFICATIONS FOR THE FIRE PUMP AND
 ASSOCIATED EQUIPMENT.PLEASE COMPLY
  
 22.SIGNS REQUIRED IN STAIRWELLS INDICATING FLOOR
 IDENTITY.ADD COMMENT TO SHEET A-701
  
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved