| Date |
Text |
| 2007-04-25 17:04:03 | *****DENIED***** |
| | |
| | |
| | 01.THE COMPLETE ADDRESS OR ACTUAL ADDRESS OF WHERE |
| | THE SCOPE OF WORK WILL BE CONDUCTED SHALL BE IN THE |
| | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.PLEASE |
| | COMPLY |
| | |
| | 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD |
| | COMMENT TO THE APPROPIATE PLAN SHEET(S) |
| | |
| | 04.EXIT STAIRS ARE TO BE KEPT UP WITH CONSTRUCTION. |
| | ADD COMMENT TO THE APPROPIATE PLAN SHEET(S) |
| | |
| | 05.KNOX-BOX WILL BE REQUIRED FOR THE BUILDING.FOR |
| | KNOX APPLICATIONS, CONTACT WEST PALM BEACH FIRE |
| | PREVENTION BUREAU AT 561-804-4724.IT APPEARS ON SHEET |
| | P101D THAT ACCESS WITHIN THE STRUCTURE CANNOT BE GAINED |
| | THROUGH THE PUMP ROOM.ACCESS/KNOX BOX IS TO BE |
| | INSTALLED IN AN ACCESSIBLE LOCATION WHERE ACCESS TO OR |
| | WITHIN THE STRUCTURE |
| | |
| | 06. ON THE APPROPIATE EXTERIOR ELEVATION FRONTING |
| | METROCENTRE BOULEVARD EAST,POST THE NUMERICAL ADDRESS |
| | ON THE BUILDING.AS PER WEST PALM BEACH CODE, THOSE |
| | NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS |
| | THAN 1" IN WIDTH.ONCE THIS PERMIT HAS BEEN ISSUED, |
| | THE NUMERICAL ADDRESS SHALL BE TEMPORARILY POSTED |
| | BEFORE & DURING CONSTRUCTION OPERATIONS, AND PERMANENLY |
| | POSTED AFTER CONSTRUCTION PRIOR TO ATTAINING A |
| | CERTIFICATE OF OCCUPANCY.IF THE BUILDING IS SET-BACK |
| | FROM THE STREET OR ROADSIDE, A NUMERICAL ADDRESS (THE |
| | SAME DIMENSIONS AS PER WEST PALM BEACH CODE) SHALL BE |
| | REQUIRED ON THE MONUMENT SIGN OR MARQUEE IN ADDITION TO |
| | THOSE ON THE BUILDING. PLEASE COMPLY |
| | |
| | 07.TEMPORARY STANDPIPES ARE REQUIRED WHEN THE |
| | BUILDING REACHES THREE STORIES OR 30 FEET IN HEIGHT. |
| | ADD COMMENT TO THE APPROPIATE PLAN SHEET(S) |
| | |
| | 08.FIRE DOORS AND WINDOWS SHALL COMPLY WITH NFPA 80. |
| | ADD COMMENT TO PLAN SHEETS-A-603 AND A604 |
| | |
| | 09.DOORS THAT OPEN ONTO EXIT ACCESS CORRIDORS SHALL |
| | NOT HAVE LESS THAN A 20-MINUTE FIRE PROTECTION RATING. |
| | THOSE DOORS SHALL BE SELF-CLOSING AND SELF-LATCHING. |
| | ADD COMMENT TO SHEETA-603 |
| | |
| | 10.THE INTERIOR FINISH CLASSIFICATION FOR WALLS AND |
| | CEILING SHALL BE CLASS A FOR EXIT ENCLOSURES, CLASS A |
| | OR B FOR LOBBIES AND CORRIDORS, AND CLASS A, B, OR C |
| | FOR OTHER SPACES.SPECIFY WHAT THESE AREAS WILL BE ON |
| | SHEET G-000 AND A-605 |
| | |
| | 11.ELEVATOR WARNING SIGNS WILL BE REQUIRED IN THE |
| | LOBBIES.ADD COMMENT TO SHEETSA-403 AND A-404 |
| | |
| | 12.AT LEAST ONE IDENTIFIBLE ELEVATOR SHALL BE |
| | AVAILABLE FOR USE BY THE FIRE DEPARTMENT IN CASE OF |
| | EMERGENCY.ADD COMMENT TO SHEETSA-403 AND A-404 |
| | |
| | 13.A FLOOR DIAGRAM REFLECTING THE ACTUAL FLOOR |
| | ARRANGEMENT, EXIT LOCATIONS AND ROOM IDENTIFICATION |
| | SHALL BE POSTED IN A LOCATION AND MANNER ACCEPTABLE TO |
| | THE AHJ ON, OR IMMEDIATELY ADJACENT TO, EVERY GUEST |
| | ROOM IN THE HOTEL.ADD COMMENT TO THE APPROPIATE PLAN |
| | SHEET(S) |
| | |
| | 14.SMOKE DETECTORS ARE NOT SHOWN FOR THE ELEVATOR |
| | LOBBY, ICE ROOM, OR ELECTRIC ROOM ON SHEETS E-101, |
| | E-102, E-103; HOWEVER THEY ARE CORRECTLY SHOWN ON |
| | SHEETS E-203 AND E-204.BE CONSISTENT IN THE LOCATION |
| | OF DEVICES ON THE PLAN SHEETS |
| | |
| | 15.PLEASE PROVIDE A LAYOUT OF THE FIRE ALARM SYSTEM |
| | INDEPENDENT OF THE ELECTRICAL SHEETS.PLEASE COMPLY; |
| | SEE ELECTRICAL PLAN NOTE #12 |
| | |
| | 18.PLEASE PROVIDE A LAYOUT OF THE FIRE SPRINKLER |
| | SYSTEM INDEPENDENT OF THE PLUMBING SHEETS.INCLUDE THE |
| | LOCATION OF THE FIRE DEPARTMENT CONNECTION(S) AND THE |
| | DOUBLE DETECTOR CHECK VALVE ASSEMBLY.PLEASE COMPLY; |
| | SEE ELECTRICAL PLAN NOTE #12 |
| | |
| | 19.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK |
| | ARE REQUIRED FOR THE DOUBLE CHECK DETECTOR VALVE |
| | ASSEMBLY.ADD COMMENT TO THE FIRE SPRINKLER AND/OR |
| | FIRE ALARM PLAN SHEET |
| | |
| | 20.KNOX LOCKING CAPS WILL BE REQUIRED ON FIRE |
| | DEPARTMENT CONNECTIONS (FDC). CONTACT WEST PALM BEACH |
| | FIRE PREVENTION AT 561-804-4724 FOR KNOX APPLICATIONS. |
| | ADD COMMENT TO THE APPROPIATE FIRE SPRINKLER PLAN |
| | SHEET |
| | |
| | 21.PROVIDE SPECIFICATIONS FOR THE FIRE PUMP AND |
| | ASSOCIATED EQUIPMENT.PLEASE COMPLY |
| | |
| | 22.SIGNS REQUIRED IN STAIRWELLS INDICATING FLOOR |
| | IDENTITY.ADD COMMENT TO SHEET A-701 |
| | |
| | |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |