| | *** UNSAT2ND REVIEW*** |
| | |
| | HOMEWOOD SUITES |
| | 5-STORY 114 UNITS. |
| | |
| | ** PLEASE SEE MANY OF THE NOTES WILL CONTAIN |
| | ABBREVIATIONS FOR REQUIRED ITEMS. |
| | PLEASE SEE SOME OF THE FOLLOWING WHICH WILL BE COMMON * |
| | ANY REFERENCE TO THE FBC CHAPTER 1, ARE SECTIONS TO THE |
| | ADMINISTRATIVE SECTION OF THE FBC 2004 AS ADOPTED BY |
| | THE CITY OF WEST PALM BEACH. |
| | * PLEASE SEE MANY REFERENCE TO THE FLORIDA STATUTES |
| | WILL BE DONE AS FS. |
| | * PLEASE SEE MANY REFERENCES TO THE FLORIDA |
| | ADMINISTRATIVE CODE WILL BE FAC. |
| | |
| | 1) NOTE:PLEASE SEE THAT ALL ROLLS OF PLANS NEED TO BE |
| | SECURELY FASTENED AND BOUND TOGETHER SO THAT SHEETS AND |
| | SETS ARE NOT COMING APART. THE STAPLES IN PLANS DO NOT |
| | ATTACH ALL SHEETS AND GO THROUGH ALL SHEETS IN SETS. ** |
| | ALL ADDITIONAL INFORMATION BY WAY OF PRODUCT APPROVALS, |
| | DATA, REPORTS, RESPONSES ETC SHOULD NOT BE |
| | ATTACHED/STAPLED TO ROLLS OF PLANS. PLEASE PLACE IN |
| | FOLDERS/BINDERS OF SOME SORT AND LABEL ACCORDINGLY. |
| | |
| | |
| | 2) NOTE: PLEASE SEE FS 471.025, 481.025 AND FAC |
| | 61G15-23.002, 61G1-16.004 AS ALL PLANS SHALL BEAR THE |
| | ORIGINAL AND LEGAL SIGNATURE OF ALL DESIGNERS OF |
| | RECORD. |
| | ** PLEASE SEE THE ELECTRICAL SHEETS SEEMED TO BE SIGNED |
| | WITH WHAT APPEARS TO BE *INITIALS*? IF THIS IS INDEED |
| | THE LEGAL SIGNATURE OF THE DESIGNER, PLEASE SUBMIT AN |
| | ORIGINAL SIGNED, DATED AND SEALED LETTER FROM THE |
| | ENGINEER ATTESTING TO THE LEGAL SIGNATURE. THIS WILL BE |
| | PLACED IN OUR SIGNATURE FILE FOR FUTURE REFERENCE. ** |
| | PLEASE KNOW THAT THE LETTER WILL BE REQUIRED TO BE |
| | NOTARIZED. PLEASE SEE FS 117.05 FOR CORRECT NOTARY |
| | REQUIRED STATEMENTS ETC. |
| | |
| | |
| | 3) NOTE: PLEASE SEE THE NEW LICENSE INFORMATIONKNOWN |
| | AS THE CERTIFICATE OF AUTHORIZATION NUMBER WHICH HAS |
| | NOW BEEN ADDED TO THE TITLE BLOCKS ON ALL ENGINEERING |
| | SHEETS IS CURRENTLY *DELINQUENT* WITH THE DEPARTMENT OF |
| | BUSINESS AND PROFESSIONAL REGULATION. PLEASE SEE A |
| | PRINT OUT FROM THE STATE OF FLORIDA WEBSITE WHICH IS |
| | BEING ATTACHED TO THE NOTES WHICH WAS PRINTED ON 4/5/07 |
| | SHOWS THE LICENSE FOR FIRM AS BEING DELINQUENT SINCE |
| | 2/28/07. |
| | PLEASE SEE FAC 61G15-23.002 AND FS 471.023 WHICH |
| | REQUIRES THIS NUMBER TO BE CURRENT AND IN FULL EFFECT |
| | FOR SAID FIRM. |
| | PLEASE KNOW THIS IS REQUIRED ON ALL SHEETS AND FOR ALL |
| | TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | TRADE(S). |
| | |
| | |
| | 4) NOTE: PLEASE SEE MISSING THE COMPLETE INFORMATION OF |
| | THE TITLE BLOCKS FOR THE ARCHITECTURAL FIRM. FAC |
| | 61G1-16.004, FS 481.219 |
| | PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER |
| | OF THE ARCHITECT. |
| | PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION |
| | NUMBER. THIS MAY ALSO BE KNOWN AS THE FIRM LICENSE |
| | NUMBER. PLEASE SEE THAT THIS IS REQUIRED FOR ALL SHEETS |
| | WHICH CONTAIN THE TITLE BLOCK FOR SAID FIR, *PFVS* THIS |
| | IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES WHETHER OR |
| | NOT COMMENT IS MADE BY OTHER TRADES. |
| | |
| | 5) NOTE: PLEASE SEE THIS COMMENT REMAINS AS NOT ALL |
| | SHEETS FROM THE EACH DESIGN PROFESSIONALS CONTAIN THIS. |
| | THE SHEETS FROM MINICK ENGINEERING ARE OK. PLEASE SEE |
| | FBC ADMIN SECTION 109.3.6, 109.3.6.4.4 WHICH REQUIRES |
| | THE STATEMENT FOR THRESHOLD PROJECTS ON ALL ARCH AND |
| | ENG SHEETS. |
| | ? TO THE BEST OF THE ARCHITECT?S /OR ENGINEER?S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER |
| | 633 OF THE FLORIDA STATUTES?. |
| | THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON |
| | PLANS. |
| | |
| | 6) NOTE:PLEASE SEE THE *S* SHEETS WHICH DO NOT |
| | CONTAIN THE REQUIRED LICENSE INFORMATION FOR THE |
| | ENGINEERING FIRM AS REQUIRED PER FAC 61G15-23.002, FS |
| | 471.023. |
| | THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADE(S). |
| | |
| | 7) NOTE: PLEASE SEE SOME OF THE SP SHEETS ARE MISSING |
| | INFORMATION ON THE TITLE BLOCKS FOR THE PRINTED NAME |
| | AND LICENSE INFORMATION AS REQUIRED PER FAC 61G1-16.004 |
| | AND FS 481.219 |
| | |
| | 8) NOTE:PLEASE SEE SOME SHEETS AS THE SEALS ARE NOT |
| | CLEAR AND VISIBLE. THIS COMMENT IS NOT FOR ALL SHEETS |
| | OR TRADES. PLEASE SEE SP SHEETS. |
| | PLEASE SEE ALL SEALS SHALL BE CLEAR AND VISIBLE WITH |
| | ALL INFORMATION ON SAID SEAL EASILY READABLE. PLEASE |
| | SEE FAC 61G15-23.001, AND 61G1-16.003 |
| | PLEASE SEE SOME SHEETS THE SEALS ARE NOT CLEAR EVEN IF |
| | SHADOWING WITH LEAD/DUST RUB. |
| | |
| | 9) NOTE:THIS COMMENT REMAINS AS THE PHOTO-METRICS |
| | SUBMITTED WERE NOT SUBMITTED OR STAMPED FROM THE PBCHD |
| | AS NOTED. |
| | PLEASE KNOW AS THE PLANS SUBMITTED CONTAIN A POOL, |
| | PLEASE KNOW THIS WILL BE UNDER A SEPARATE PERMIT WITH |
| | PLANS, FEES AND PERMIT APPLICATION. |
| | PLEASE KNOW THAT ALL PLANS FOR THIS TYPE OF PUBLIC |
| | SWIMMING POOL WILL BE REQUIRED TO BE SUBMITTED TO THE |
| | PALM BEACH COUNTY HEALTH DEPARTMENT FOR ANY REVIEW OF |
| | COMPLETED PHOTO-METRICS FOR ANY AFTER DUSK SWIMMING. |
| | PLEASE ALSO SEE ANY PLUMBING REVIEW COMMENTS WHICH MAY |
| | ALSO REQUIRED THESE PLANS WHEN SUBMITTING FOR SEPARATE |
| | PERMIT TO ALSO BE STAMPED FOR REVIEW BY THE SAME. |
| | |
| | 10) NOTE: PLEASE SEE THAT MUCH OF THE INFORMATION |
| | NEEDED FOR REVIEW FOR CODE COMPLIANCE FOR CHAPTER 13 |
| | HAS NOT YET BEEN SUBMITTED. PLEASE SEE THE ENERGY |
| | CALCULATIONS PER FBC 2004 CHAPTER 13 THAT WERE |
| | SUBMITTED FOR REVIEW. 13-415.1.AB.1 DO NOT FULLY |
| | CORRELATE WITH THE FIXTURES, TYPES, NUMBERS, WATTAGES |
| | AS SHOWN ON PLANS AND FIXTURE LEGENDS. PLEASE BE SURE |
| | TO GO THROUGH PLANS AND ENERGY CALCULATIONS AND |
| | COORDINATE ALL INFORMATION. |
| | PLEASE SEE THERE ARE ITEMS WHICH EXCEED THE LEVELS AS |
| | PERMITTED AND/OR DO NOT COORDINATE WITH PLANS AND |
| | FIXTURE LEGENDS FOR SITE/OUTSIDE AND INTERIOR |
| | LIGHTING. |
| | **PLEASE SEE THE 2004 FBC CHAPTER 13. |
| | **PLEASE SEE 13-413.1ABC.1 WHICH REQUIRES WORST CASE |
| | VOLTAGE DROP TO BE SHOWN ON PLANS FOR FEEDERS AND |
| | BRANCH CIRCUITS. THE NOTE FOR CONDUCTOR LENGTH INCREASE |
| | IS NOTED, HOWEVER PLEASE PROVIDE ABOVE AS REQUIRED. |
| | PLEASE SEE THIS VOLTAGE DROP INFORMATION COULD NOT BE |
| | LOCATED FOR THE FEEDERS. |
| | **PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE |
| | SEE A COMPLETE LIGHTING CONTROL SYSTEM AND/OR OTHER |
| | METHODS FOR AUTOMATIC LIGHTING CONTROLS ARE REQUIRED. |
| | PLEASE SEE AS NO SYSTEM OR DEVICES WERE SUBMITTED, |
| | REVIEW FOR CODE COMPLIANCE OF SUCH ITEMS COULD NOT BE |
| | DONE AT THIS TIME. |
| | A RESPONSE IN THE PLAN REVIEW NOTES MENTIONS THAT THIS |
| | IS A 24/7/365 OPERATION AND DOES NOT NEED TO MEET ANY |
| | AUTOMATED LIGHTING CONTROLS. IT IS NOT THAT THE ENTIRE |
| | BUILDING MUST CONTAIN A FULLY AUTOMATED SYSTEM. THERE |
| | ARE SEVERAL WAYS TO ACCOMPLISH THIS IN AREAS WHICH WILL |
| | REQUIRE AUTOMATED SHUTTING OFF OF LIGHTING. |
| | PLEASE SEE THERE ARE SOME AREAS IN WHICH CAN BE |
| | CONSIDERED 24HR OPERATION HOWEVER PLEASE SEE .1.3 (3) |
| | AS THE ROOMS MUST CONTAIN AUTOMATED SHUT OFF FOR ALL |
| | LIGHTING CIRCUITS IN THESE ROOMS INCLUDING ANY SWITCHED |
| | RECEPTACLES CIRCUITS. |
| | THE NOTE ADDED TO THE SHEETS FOR ROOMS DOES NOT PROVIDE |
| | ENOUGH INFORMATION FOR THIS REQUIREMENT. |
| | PLEASE SEE ALL OTHER LOCATIONS SUCH AS STORAGE ROOMS |
| | ETC WHICH CONTAIN FLOOR TO CEILING HEIGHT PARTITIONS |
| | WILL BE REQUIRED TO CONTAIN AUTOMATED DEVICES. PLEASE |
| | KNOW THAT THIS WAS FEDERALLY MANDATED IN JULY 04 WHICH |
| | REQUIRED FOR ALL STATES BY THE NEXT CODE CYCLE TO ADOPT |
| | THE 1999 ASHAE 90.1 STANDARDS OR BETTER. THE STATE OF |
| | FLORIDA ADOPTED THE FLORIDA ENERGY EFFICIENCY CODE FOR |
| | BUILDING CONSTRUCTION.PLEASE SEE THIS WAS ADOPTED ON |
| | OCT 1ST, 2005. THIS IS REQUIRED STATEWIDE. PLEASE KNOW |
| | THAT SOME OF THE LOCATIONS WHICH WOULD BE CONSIDERED |
| | FOR 24HR OPERATION MAY BE THE LOBBY, FRONT DESK, |
| | RECEPTION OFFICE LOCATIONS ALONG WITH HALLWAYS. NOT ALL |
| | AREAS ARE OCCUPIED 24/7 THEREFORE MEETING THE INTENT OF |
| | THE CODE FOR ENERGY CONSERVATION WILL NEED TO MET IN |
| | OTHER LOCATIONS. |
| | ** PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR PERFORMANCE |
| | CALCULATIONS REQUIRED. |
| | ** PLEASE SEE TRACK LIGHTING REQUIREMENTS PER |
| | 13-415.2.ABC.1.2 |
| | |
| | |
| | 11) NOTE: PLEASE SUBMIT WIND LOAD INFORMATION FOR ALL |
| | SITE LIGHTING. PLEASE SEE THE FBC IN THE WIND REGION IS |
| | 140 MPH 3 SECOND GUSTS. PLEASE KNOW THIS WILL BE |
| | REQUIRED TO BE STATED ON PLANS AND STRUCTURAL |
| | CALCULATIONS FOR ALL POLES WITH THE EPA (EFFECTIVE |
| | PROJECTED AREA) OF LIGHT FIXTURE WILL BE CONFIRMED |
| | BASED ON THE FIXTURES AS NOTED ON PLANS. |
| | PLEASE SEE THE INFORMATION ON PLANS MENTIONS THE |
| | MINIMUM RATING AND MENTIONS INFORMATION TO THE |
| | ELECTRICAL INSPECTOR. PLEASE KNOW THAT THIS INFORMATION |
| | IS AND WILL BE REQUIRED BE DONE ON PLANS AND SUBMITTED |
| | FOR REVIEW BEFORE ANY INSTALLATION. PLEASE KNOW THAT IF |
| | THE WIND LOAD CALCULATIONS AND INFORMATION IS NOT |
| | SUBMITTED AT THIS TIME, THIS WILL BE PART OF THE |
| | CONDITIONS OF ISSUANCE WHICH MAY BE DONE |
| | |
| | 12) NOTE:PLEASE SEE THE ONLY SOME INFORMATION WAS |
| | SHOWN FOR THE FIRE ALARM INFORMATION AND NO FIRE |
| | SPRINKLER INFORMATION WAS SUBMITTED.PLEASE SEE THE |
| | BASE PLANS FOR THIS BUILDING SHALL CONTAIN THE COMPLETE |
| | FIRE SPRINKLER LAYOUT AND BASE FIRE ALARM SYSTEM PLEASE |
| | KNOW THAT BOTH OF THESE WILL STILL BE SUBMITTED FOR |
| | SEPARATE PERMITS PLANS AND FEES AT A LATER DATE ONCE |
| | THE BUILDING PERMIT IS ISSUED. BASE SYSTEM FOR FIRE |
| | ALARM IS SHOWN; HOWEVER PLEASE SEE COMMENTS WITH |
| | RESPECT TO PLANS SUBMITTED FOR THIS AND DEVICES MISSING |
| | ETC. |
| | PLEASE KNOW THAT EVEN THOUGH THESE WILL BE UNDER |
| | SEPARATE PERMIT, THE MINIMUM REQUIREMENTS FOR THE CODE |
| | SHALL BE SHOWN ON PLANS. |
| | FBC ADMIN SECTION 106.3.5.1.1 (5). |
| | |
| | |
| | 13) NOTE: PLANS DID NOT CHANGE FOR COMPLETE COMPLIANCE. |
| | PLEASE SEE THE 2004 FBC WHICH CONTAINS THE SAME |
| | REQUIREMENTS AS THE 2001 FBC. THIS HAS NOT CHANGED IN |
| | THE STATE OF FLORIDA. |
| | PLEASE SEE THAT COMPLIANCE FOR ADA DEVICES, LOCATIONS, |
| | LEVELS ETC HAS NOT BEEN MET.PLEASE SEE THERE ARE |
| | SEVERAL LOCATIONS MISSING DEVICES WHICH ARE REQUIRED |
| | AND THERE ARE SEVERAL DEVICES WHICH STILL INDICATE |
| | LEVELS WHICH DO NOT MEET THE MINIMUM LEVELS AS |
| | REQUIRED. PLEASE SEE FBC 2004 11-4.28.2, .3(4). PLEASE |
| | STATE ALL MINIMUM LEVELS AS REQUIRED FOR ALL AREAS. |
| | PLEASE KNOW THAT THE LEVELS FOR ACCESSIBLE UNITS ARE |
| | NOTED ON PLANS, HOWEVER THIS IS REQUIRED FOR ALL OTHER |
| | AREAS AS STATED IN 11-4.28.1, .2 AND .3. |
| | |
| | 14) NOTE: THIS COMMENT WILL REMAIN AS ALL LOCATIONS FOR |
| | DEVICES WILL STILL NEED TO BE REVIEWED BY THE FIRE |
| | REVIEWER AS IF THERE ARE ANY LOCATIONS MISSING THIS |
| | WILL AFFECT THE ELECTRICAL PLANS.PLEASE SEE FIRE |
| | REVIEW COMMENTS AS THERE SEEMS FOR MANY LOCATIONS WHICH |
| | SMOKE DETECTORS ARE MISSING AND WILL BE REQUIRED. |
| | PLEASE SEE THESE WILL BE STATED BY FIRE REVIEW AND IS |
| | ONLY GIVEN AS A NOTE AT THIS TIME AS SOME AREAS WHICH |
| | DO NOT CONTAIN ANY NOTATION FOR THESE DEVICES WILL |
| | REQUIRE THESE.(PUMP ROOM) ETC |
| | PLEASE SEE NFPA-72 AND NFPA-101 AND FBC 905 |
| | |
| | 15) NOTE: PLEASE SEE THAT THE REFERENCE FOR NFPA-20 |
| | WOULD BE THE 2003. PLEASE STATE ON PLANS. |
| | |
| | 16) NOTE: PLEASE SEE SOME OF THE MINIMUM LEVELS SHOWN |
| | FOR EGRESS PATHS/STAIRS DO NOT MEET THE MINIMUM LEVELS. |
| | PLEASE SEE THAT THE LIGHTING LEVELS CHANGED WITH THE |
| | 2003 NFPA-101. THIS HAS BEEN IN EFFECT SINCE JAN |
| | 1ST,2005.PLEASECOMPLETE PHOTO-METRICS FOR ALL EGRESS |
| | PATHS UNDER NORMAL LIGHTING LEVELS AND UNDER EMERGENCY |
| | LIGHTING LEVELS TO THE PUBLIC RIGHT OF WAY OUT AND AWAY |
| | FROM BUILDING. |
| | PLEASE SEE NFPA-101 7.8 AND 7.9. |
| | PLEASE ALSO SEE 7.8.1.3 AND 7.9.2.2 AS ALL STAIRS SHALL |
| | INDICATE THE 10FT CANDLES MINIMUM UNDER NORMAL AND THE |
| | ALLOWED DE-RATED LEVELS UNDER EMERGENCY CONDITIONS TO |
| | 1FT CANDLE. |
| | FBC 106.1.2 ADMIN SECTION. |
| | REVIEW FOR COMPLIANCE OF THIS CAN NOT BE DONE AT THIS |
| | TIME. |
| | |
| | 17) NOTE:PLEASE PROVIDE THE UL DETAILS FOR ANY AND |
| | ALL FIRE RATED PENETRATIONS. |
| | NEC 300.21, NFPA-221, 4.2 ETC. |
| | PLEASE PROVIDE DETAIL SHEET. |
| | |
| | 18) NOTE:PLEASE SEE MISSING ROOFTOP REQUIRED GFI |
| | RECEPTACLES PER 210.63, 210.8 B2. |
| | FBC 106.1.2, NEC 408.4, 310.16 ETC |
| | |
| | 19) NOTE: PLEASE SEE THE ELECTRICAL ROOM WHICH IS BEING |
| | SHOWN ACCESSED THROUGH THE STORAGE ROOM ON THE FIRST |
| | LEVEL WILL NOT BE PERMITTED. PLEASE SEE THAT THIS |
| | COMMENT ALSO WILL NOT PERMIT ACCESS THROUGH THE |
| | ELECTRICAL ROOM TO THE STORAGE ROOM. |
| | PLEASE KNOW THAT STORAGE ROOMS QUITE OFTEN WILL BECOME |
| | CLUTTERED EVEN WITH THE MOST DILIGENT OF |
| | *HOUSEKEEPING*. PLEASE SEE 240.24 , 110.26, 408.7, |
| | ETC. |
| | FBC 104.6. |
| | PLEASE KNOW THAT THIS COMMENT IS REQUIRED EVEN IF NOT |
| | MADE BY THE FIRE PLAN REVIEWER. |
| | PLEASE REVISE ACCESS AND LOCATION. |
| | |
| | 20) NOTE: PLEASE SEE A NOTE ON PLANS, SHEET E-503 |
| | MENTIONS THAT THE LOCATIONS FOR THE SMOKE DETECTORS |
| | SHALL BE LOCATED A MINIMUM OF 3FT FROM ANY RETURN. |
| | PLEASE SEE THE STATEMENT ALSO INCLUDES THE DISTANCE |
| | FROM SUPPLY REGISTERS. PLEASE SEE NFPA-72 11.8.3 AS THE |
| | DISTANCES FOR THE SUPPLY GRILLES ARE STATED HOWEVER THE |
| | DISTANCE FROM THE RETURNS IS NOT STATED IN THE CODE. |
| | PLEASE KNOW THAT AN A/C RETURN AIR GRILLE IS MORE OFTEN |
| | THAN NOT MUCH LARGER AND THE VOLUME OF CFM IS |
| | SUBSTANTIALLY HIGHER THAN WHAT A SUPPLY GRILLE WILL |
| | CONTAIN. PLEASE SEE THAT MANY SMOKE DEVICE MANUFACTURES |
| | WILL REQUIRE A GREATER DISTANCE FROM THE RETURNS, AS |
| | MUCH AS 5FT TO 10FT HAS BEEN SEEN BY THIS AHJ. PLEASE |
| | ADJUST NOTE AND PLEASE LOOK INTO THE DEVICES IN WHICH |
| | MAY BE USED OR INSTALLED AS THIS WILL PROVIDE THE |
| | INFORMATION NEEDED TO BE STATED ON PLANS. |
| | (A 3FT DISTANCE WILL NOT SUFFICE FOR THE RETURN AIR). |
| | |
| | 21) NOTE: PLEASE SEE THE PREVIOUS NOTE FOR THE AIC |
| | RATINGS WAS FOR ALL EQUIPMENT NOT ONLY FOR THE FIRE |
| | PUMP CONTROLLER. PLEASE SEE THE RESPONSE LETTER |
| | MENTIONS THAT THE RATINGS FOR THE FPC WAS ADDED? PLEASE |
| | SEE THE RATINGS IN PANELS ARE STILL IN QUESTION AS IT |
| | APPEARS THAT ALL OF THE BRANCH BREAKERS ARE NOTED TO BE |
| | 22K RATED. PLEASE VERIFY THE RATINGS AND ADJUST. IF THE |
| | PLANS INDICATE THE BRANCH BREAKERS AS 22K RATED THEN |
| | THAT IS WHAT WILL BE REQUIRED TO BE INSTALLED. PLEASE |
| | KNOW IT IS THE RESPONSIBILITY OF THE DESIGN |
| | PROFESSIONAL TO OBTAIN THIS INFORMATION AT THIS TIME |
| | AND PLACE ON PLANS. PLEASE CHECK WITH THE LOCAL SERVICE |
| | PLANNER FROM FLORIDA POWER AND LIGHT AND BE SURE THAT |
| | ALL INFORMATION ON THE PLANS FOR DESIGN MEETS OR |
| | EXCEEDS THE AVAILABLE FAULT CURRENT AT THE SERVICE. |
| | PLEASE SEE 110.9, 110.10, 240.12 ETC. |
| | |
| | 22) NOTE: PLEASE SEE THIS IS THE SAME COMMENT AS ONLY |
| | SOME INFORMATION WAS STATED ON PLANS. PLEASE KNOW THAT |
| | ALL THE MANUFACTURE SPEC/CUTS SHEETS FOR THE FIRE PUMP |
| | AND FIRE PUMP CONTROLLER ARE REQUIRED AT THIS TIME. |
| | PLEASE KNOW THAT THE PLANS SHALL BEAR ALL INFORMATION |
| | AS NEEDED. |
| | PLEASE SEE AS NO INFORMATION WAS SUBMITTED OF EQUIPMENT |
| | AS STATED ABOVE REVIEW FOR NUMEROUS ITEMS FOR CODE |
| | COMPLIANCE CAN NOT BE DONE AT THIS TIME. |
| | PLEASE SEE NFPA-20 2003 CHAPTER 9 AND CHAPTER 10. |
| | PLEASE ALSO SEE NEC 695.4 |
| | ** PLEASE KNOW REFERENCES TO THE CHAPTERS ARE GIVEN AND |
| | NOT SPECIFIC SECTIONS AS THERE ARE TOO MANY TO LIST. |
| | DISCONNECTING MEANS, ISOLATION SWITCH, LOCKED ROTOR, |
| | ETC. |
| | PLEASE BE SURE EQUIPMENT SHEETS CONTAIN THE LISTING |
| | FROM A NRTL PER 695.10 AND NFPA-20 10.1.2.1. |
| | |
| | 23) NOTE:PLEASE SEE THE DOOR SWINGS INTO SOME OF THE |
| | ELECTRICAL ROOMS AS THE DOOR SWING AS IN AND IN THE |
| | DIRECTION OF THE ELECTRICAL PANELS CREATES A LIFE |
| | SAFETY HAZARD. PLEASE SEE IN THE EVEN OF ELECTRICAL |
| | PERSONNEL WORKING IN THIS ELECTRICAL EQUIPMENT AND THE |
| | DOOR BEING OPENED IN HIS/HER DIRECTION MAY PUSH THIS |
| | PERSON INTO THE ELECTRICAL PANEL WHICH MAY BE |
| | ENERGIZED. PLEASE SEE PLANS WHICH ARE REDLINED FOR |
| | THESE AT THE 2-5 FLOOR LOCATIONS. |
| | PLEASE ADJUST. |
| | FBC 104.6, |
| | NEC 110.26. |
| | |
| | 24) NOTE:PLEASE SEE THE KITCHEN EQUIPMENT SCHEDULE ON |
| | E-201 AS THERE ARE SEVERAL ELECTRICAL APPLIANCES WHICH |
| | INDICATE THE WRONG OCP, AG, OR THE ACTUAL PHASES WHICH |
| | ARE FEEDING SOME OF THESE. |
| | PLEASE SEE SOME OF THE FOLLOWING LISTED BELOW: PLEASE |
| | SEE THE KITCHEN MICROWAVE SHOWN ON PLANS AS SINGLE POLE |
| | CIRCUIT, YET EQUIPMENT SCHEDULE INDICATES 3-PHASE? |
| | PLEASE SEE THE DISHWASHER ON A 1-PHASE CIRCUIT, YET |
| | SHOWN ON A 60AMP BREAKER WITH 2-PHASES ON PLANS ETC? |
| | PLEASE SEE THE 70AMP BREAKER ON 12AWG, SINGLE PHASE |
| | ETC. |
| | PLEASE SEE THE CONVECTION OVEN WHICH CONTAINS A LOAD |
| | WHICH EXCEEDS THE SINGLE PHASE 20AMP CIRCUIT WHICH IT |
| | IS SHOWN ON. PLEASE ALSO SEE THE CIRCUIT ON PLANS. ** |
| | PLEASE GO THROUGH ALL EQUIPMENT, LOADS, PHASES, THE |
| | AMOUNT AND SIZE OF CONDUCTORS |
| | 240.4, 310.16 ETC. |
| | FBC 106.1.2 ADDITIONAL INFORMATION AND COORDINATION. |
| | |
| | 25) NOTE:THIS COMMENT REMAINS AS THE SAME IS NOTED. |
| | PLEASE SEE SOME DEVICES SHOWN ON PLANS COULD NOT BE |
| | LOCATED ON THE DEVICE SYMBOL LEGEND. PLEASE COMPLETE |
| | FOR REVIEW OF THESE ITEMS. |
| | FBC ADMIN SECTION 106.1.2, 106.3.5.1.2 |
| | |
| | 26) NOTE:THIS COMMENT TO REMAIN AS THE PLANS WILL |
| | CONTAIN CHANGES WHICH NEW SYMBOLS WILL BE ADDED. PLEASE |
| | KNOW BASED ON THE REQUIREMENTS OF MANY OF THE REVIEW |
| | COMMENTS AND FBC CHAPTER 13, THE PLAN KEYNOTES WILL |
| | MOST LIKELY BE ADJUSTED. |
| | PLEASE BE SURE TO CORRELATE. |
| | FBC 106.5.3.1.2, 106.1.2. ADDITIONAL INFORMATION AND |
| | COORDINATION. |
| | |
| | 27) NOTE: PLEASE SEE PLANS WHICH INDICATES A DISCONNECT |
| | FOR THE DISHWASHER SANITIZER IN A DIFFERENT ROOM THAN |
| | THE EQUIPMENT WHICH IS BEING FED.? |
| | PLEASE SEE LOCATIONS OF DISCONNECTING MEANS FOR |
| | EQUIPMENT SHOULD BE LOCATED IN SIGHT OF EQUIPMENT. |
| | 422.30, 31 ETC |
| | FBC 106.1.2 |
| | |
| | 28) NOTE: PLEASE SEE THE TRANSFORMERS WHICH ARE BEING |
| | SHOWN ON PLANS FOR THE NOTED ACC UNITS WHICH SHOWS |
| | THESE LOCATED INSIDE THE CLOTHES CLOSETS. |
| | PLEASE SEE THAT DUE TO THE HIGH TEMPERATURE OF THESE |
| | TRANSFORMERS BEING IN THE CLOSE PROXIMITY OF EASILY |
| | IGNITABLE MATERIALS, THESE LV TRANSFORMERS ARE TO BE |
| | RELOCATED. THIS AHJ HAS SEEN FIRES WHICH HAVE BEEN |
| | CREATED BY THIS TYPE OF SCENARIO WHICH CREATES A LIFE |
| | SAFETY AND PROPERTY HAZARD. |
| | 110.26, 240.24. |
| | FBC 104.6 |
| | |
| | 29) NOTE: PLEASE SEE THE FOLLOWING COLOR CODING SHALL |
| | BE NOTED ON PLANS/RISER FOR THE FOLLOWING VOLTAGES. |
| | PLEASE KNOW THAT AS THE NEC DOES NOT PROVIDE COLOR |
| | CODING IT IS BEING PROVIDED BY THE AHJ. |
| | 277/480V SYSTEMS |
| | BROWN, PURPLE, YELLOW AND GREY. |
| | 120/208 |
| | BLACK, RED, BLUE AND WHITE. |
| | PLEASE INCLUDE. |
| | FBC 106.4 |
| | |
| | 30) NOTE: PLEASE SEE 210.60 WHICH REFERENCES TO 210.52 |
| | FOR ITEMS REQUIRED. |
| | PLEASE SEE THE FOLLOWING COMMENTS FOR ROOMS WHICH ARE |
| | CONSIDERED DWELLING UNITS BY DEFINITIONS. |
| | |
| | 31) NOTE: PLEASE SEE MISSING THE SMALL APPLIANCE |
| | CIRCUITS AS REQUIRED PER 210.52B1, 210.11C1 AND 220.16 |
| | THIS COMMENT REMAINS AS THE MINIMUM CIRCUITING IS NOT |
| | SHOWN MEETING THESE REQUIREMENTS. |
| | PLEASE KNOW THAT NO OTHER OUTLETS MAY BE FED FROM THESE |
| | CIRCUITS. |
| | |
| | 32) NOTE: PLEASE SEE 210.52B1 AS THERE ARE RECEPTACLES |
| | LOCATED IN THE KITCHEN/BREAKFAST/DINING AREAS WHICH ARE |
| | FED FROM THE SMALL APPLIANCE CIRCUITS AND LOADS SHALL |
| | BE FIGURED AS 220.16. |
| | AS NOTED IN NOTE #31 ABOVE. |
| | |
| | 33) NOTE: PLEASE SEE MISSING RECEPTACLES PER 210.52 FOR |
| | 2FT OF WALL, KITCHEN AREA, AND KITCHEN WALL OVER 2FT, |
| | WITHIN 6FT OF DOORS ETC. PLEASE SEE REDLINED PLANS AS |
| | SOME LOCATIONS ARE STILL MISSING. |
| | PLEASE KNOW AS THE CODE DOES PERMIT THE SPACING FOR |
| | HOTEL/MOTELS AND GUEST SUITES TO BE SPACE FOR FURNITURE |
| | LAYOUTS, IT ALSO STILL REQUIRES THE SAME NUMBER OF |
| | RECEPTS WHICH WOULD BE REQUIRED IN A DWELLING TO BE |
| | INSTALLED. PLEASE SEE SOME OF THESE ARE MISSING. |
| | 210.60 |
| | |
| | 34) NOTE: PLEASE SEE AREAS WHICH SEEM TO BE COUNTER |
| | PENINSULAR AREAS OFF OF KITCHEN WHICH SHOW RECEPTACLES |
| | AND IF THESE SERVE THE COUNTER SPACES THEN THE |
| | LOCATIONS OF WALL RECEPTACLES MAY STILL NEED TO BE MET |
| | AS THE SPACING AND NUMBER OF DEVICE REQUIREMENTS IN |
| | NOTE #33 ABOVE. |
| | PLEASE SEE 210.52C3/ 210.52 |
| | |
| | 35) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING |
| | KITCHEN COUNTER SPACES AND THE LIKE SHALL BE GFI/GFI |
| | PROTECTED. |
| | PLEASE SEE THE DEVICES WHICH WERE ADDED DO NOT INDICATE |
| | GFI PROTECTION. |
| | |
| | 36) NOTE: PLEASE CLARIFY WHERE THE REQUIRED ARC FAULT |
| | PROTECTION IS? PLEASE SEE RESPONSE MENTIONS THIS WAS |
| | REMOVED? THESE UNITS ARE CONSIDERED DWELLING UNITS AND |
| | THE INTENT OF 210.12 IS TO HAVE ARC FAULT PROTECTION |
| | FOR ALL OUTLETS IN SLEEPING AREAS. PLEASE SEE THE 2005 |
| | NEC 210.18 AS THE VERBIAGE WAS ADDED TO CLARIFY THIS |
| | REQUIREMENT. THIS IS AND WAS THE INTENT OF THE CODE. |
| | PLEASE ALSO SEE THE DEFINITION OF *DWELLING UNIT* HAS |
| | NOT CHANGED IN THE BUILDING CODE OR THE NEC AND |
| | REMAINED THE SAME IN THE 2002 NEC AND 2004 FBC. PLEASE |
| | INDICATE AND INCLUDE THE PROTECTION FOR UNITS. 210.12 |
| | |
| | 37) NOTE: PLEASE COMPLETE ALL PANEL BOARDS WITH THE |
| | CONDUCTOR SIZES FOR ALL BRANCH CIRCUITS. THE RESPONSE |
| | MENTIONS ALL CONDUCTORS ARE NUMBER 12AWG UNLESS OTHER |
| | WISE NOTED. YET THERE IS NO SCHEDULE FOR TYPICAL OCP |
| | DEVICES AND AWG FOR BRANCH CIRCUITS. |
| | PLEASE COMPLETE AND PROVIDE. |
| | PLEASE SEE 310.16, 240.4, FBC 106.1.2, 106.3.5.1.2 |
| | REVIEW FOR CONDUCTORS CAN NOT BE DONE AT THIS TIME. |
| | |
| | |
| | 38) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEM |
| | AT DETACHED BUILDINGS/STRUCTURES PER 250.32 |
| | PLEASE SEE THIS IS BEING SHOWN AT THE DETACHED POOL |
| | HOUSE, HOWEVER NOT FOR THE SEPARATE STORAGE/DUMPSTER |
| | BUILDING. |
| | PLEASE SEE THE CODE IF USING A SINGLE CIRCUIT THEN THIS |
| | REQUIRES THIS CIRCUIT TO BE GFI. PLEASE SEE CIRCUIT |
| | H1A-49. |
| | |
| | |
| | |
| | 39) NOTE: PLEASE SEE THE PREVIOUS COMMENT ABOUT THE |
| | MISSING PANEL SCHEDULE FOR PANEL ?P?. PLEASE CLARIFY |
| | WHERE LOADS HAVE BEEN FIGURED AT THE 125% AS REQUIRED. |
| | PLEASE SUBMIT AND COMPLETE EVEN FOR FUTURE LOAD ETC. |
| | THE MDP DOES LIST THE PANEL, YET LOADS CAN NOT BE |
| | VERIFIED FOR PANEL SCHEDULE AND SIZE NEEDED. |
| | 220, 215.3, 230.42. |
| | FBC 106.1.2 |
| | |
| | |
| | |
| | 40) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED THE |
| | GROUNDING ELECTRODE RISER WHICH WAS SUBMITTED, HOWEVER |
| | PLEASE SEE RISER AS THIS RISER UP THROUGH THE BUILDING |
| | AND TO ALL OTHER LOCATIONS IS NOT CONNECTED TO THE |
| | BUILDINGS MAIN GROUNDING ELECTRODE SYSTEM AS SHOWN ON |
| | RISER. PLEASE COORDINATE RISER AND ADJUST. |
| | |
| | 41) NOTE:PLEASE SEE 240.13 AND 230.95 AS THE MAIN IS |
| | BEING SHOWN WITH GFI PROTECTION WHICH IS THAT FOR |
| | PERSONNEL PROTECTION AND CODE REQUIRES GFP (GROUND |
| | FAULT PROTECTION WHICH IS NOT THE SAME. PLEASE ADJUST. |
| | THIS WAS ONLY CHANGED ON ONE SHEET; IN FACT THE RISER |
| | SHEET NO LONGER INDICATES ANY GF PROTECTION? |
| | |
| | 42) NOTE:PLEASE SEE THE RISER NOW INDICATES AN |
| | *EQUIPMENT GROUNDING CONDUCTOR* FROM UTILITY COMPANY |
| | WHICH IS NOT PERMITTED. |
| | PLEASE SEE 250.24B, 250.24, 250.6 AND NOTED IN PREVIOUS |
| | REVIEW. |
| | PLEASE SEE AS NOTED, (250.6) NO EQUIPMENT GROUNDING |
| | CONDUCTOR IS INSTALLED BEFORE THE FIRST MEANS OF |
| | DISCONNECT. |
| | THIS WOULD CREATE OBJECTIONABLE CURRENTS. |
| | |
| | |
| | 43) NOTE: PLEASE SEE 210.8B3 WHICH REQUIRES GFI |
| | PROTECTION ON ALL 15/20AMP 120V CIRCUITS IN KITCHENS |
| | AND AREAS OF THE LIKE. |
| | PLEASE SEE THE PLANS FOR ALL AREAS WHERE FOOD MAY BE |
| | PREPARED AND APPLIANCE LOCATIONS INCLUDING THE OUTSIDE |
| | AREAS. |
| | |
| | 44) NOTE: PLEASE SEE THE UNITS WHICH ARE MISSING SMOKE |
| | DETECTORS OUTSIDE SLEEPING ROOMS. |
| | NFPA-11.5.1.1 |
| | |
| | 45) NOTE: PLEASE SEE RISER AS BOTH THE 2ND AND 3RD |
| | FLOORS INDICATE PANELS *L2A*. |
| | |
| | 46) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | DESIGN PROFESSIONALS AND REPEAT COMMENTS. |
| | ** PLEASE KNOW THAT ONE COMPLETE SET OF PLANS IS BEING |
| | RETAINED BY THIS OFFICE. |
| | |
| | *** PLEASE KNOW AS THERE ARE MANY ITEMS NOT YET |
| | SUBMITTED FOR REVIEW, ALL ITEMS ARE NOT REVIEWED FOR |
| | CODE COMPLIANCE. |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-04-07 07:01:24 | 2007-04-07 07:01:24 |
| | REVIEW IN PROGRESS |
| 2007-04-05 14:15:17 | 1-ROLL IN ELEC FOR REVIEW. |
| | NOTES WILL FOLLOW. |