Plan Review Notes
Plan Review Notes For Permit 06111071
Permit Number 06111071
Review Stop E
Sequence Number 2
Notes
Date Text
2007-04-07 14:57:48 
 *** UNSAT2ND REVIEW***
  
 HOMEWOOD SUITES
 5-STORY 114 UNITS.
  
 ** PLEASE SEE MANY OF THE NOTES WILL CONTAIN
 ABBREVIATIONS FOR REQUIRED ITEMS.
 PLEASE SEE SOME OF THE FOLLOWING WHICH WILL BE COMMON *
 ANY REFERENCE TO THE FBC CHAPTER 1, ARE SECTIONS TO THE
 ADMINISTRATIVE SECTION OF THE FBC 2004 AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
 * PLEASE SEE MANY REFERENCE TO THE FLORIDA STATUTES
 WILL BE DONE AS FS.
 * PLEASE SEE MANY REFERENCES TO THE FLORIDA
 ADMINISTRATIVE CODE WILL BE FAC.
  
 1) NOTE:PLEASE SEE THAT ALL ROLLS OF PLANS NEED TO BE
 SECURELY FASTENED AND BOUND TOGETHER SO THAT SHEETS AND
 SETS ARE NOT COMING APART. THE STAPLES IN PLANS DO NOT
 ATTACH ALL SHEETS AND GO THROUGH ALL SHEETS IN SETS. **
 ALL ADDITIONAL INFORMATION BY WAY OF PRODUCT APPROVALS,
 DATA, REPORTS, RESPONSES ETC SHOULD NOT BE
 ATTACHED/STAPLED TO ROLLS OF PLANS. PLEASE PLACE IN
 FOLDERS/BINDERS OF SOME SORT AND LABEL ACCORDINGLY.
  
  
 2) NOTE: PLEASE SEE FS 471.025, 481.025 AND FAC
 61G15-23.002, 61G1-16.004 AS ALL PLANS SHALL BEAR THE
 ORIGINAL AND LEGAL SIGNATURE OF ALL DESIGNERS OF
 RECORD.
 ** PLEASE SEE THE ELECTRICAL SHEETS SEEMED TO BE SIGNED
 WITH WHAT APPEARS TO BE *INITIALS*? IF THIS IS INDEED
 THE LEGAL SIGNATURE OF THE DESIGNER, PLEASE SUBMIT AN
 ORIGINAL SIGNED, DATED AND SEALED LETTER FROM THE
 ENGINEER ATTESTING TO THE LEGAL SIGNATURE. THIS WILL BE
 PLACED IN OUR SIGNATURE FILE FOR FUTURE REFERENCE. **
 PLEASE KNOW THAT THE LETTER WILL BE REQUIRED TO BE
 NOTARIZED. PLEASE SEE FS 117.05 FOR CORRECT NOTARY
 REQUIRED STATEMENTS ETC.
  
  
 3) NOTE: PLEASE SEE THE NEW LICENSE INFORMATIONKNOWN
 AS THE CERTIFICATE OF AUTHORIZATION NUMBER WHICH HAS
 NOW BEEN ADDED TO THE TITLE BLOCKS ON ALL ENGINEERING
 SHEETS IS CURRENTLY *DELINQUENT* WITH THE DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION. PLEASE SEE A
 PRINT OUT FROM THE STATE OF FLORIDA WEBSITE WHICH IS
 BEING ATTACHED TO THE NOTES WHICH WAS PRINTED ON 4/5/07
 SHOWS THE LICENSE FOR FIRM AS BEING DELINQUENT SINCE
 2/28/07.
 PLEASE SEE FAC 61G15-23.002 AND FS 471.023 WHICH
 REQUIRES THIS NUMBER TO BE CURRENT AND IN FULL EFFECT
 FOR SAID FIRM.
 PLEASE KNOW THIS IS REQUIRED ON ALL SHEETS AND FOR ALL
 TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADE(S).
  
  
 4) NOTE: PLEASE SEE MISSING THE COMPLETE INFORMATION OF
 THE TITLE BLOCKS FOR THE ARCHITECTURAL FIRM. FAC
 61G1-16.004, FS 481.219
 PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER
 OF THE ARCHITECT.
 PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER. THIS MAY ALSO BE KNOWN AS THE FIRM LICENSE
 NUMBER. PLEASE SEE THAT THIS IS REQUIRED FOR ALL SHEETS
 WHICH CONTAIN THE TITLE BLOCK FOR SAID FIR, *PFVS* THIS
 IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES WHETHER OR
 NOT COMMENT IS MADE BY OTHER TRADES.
  
 5) NOTE: PLEASE SEE THIS COMMENT REMAINS AS NOT ALL
 SHEETS FROM THE EACH DESIGN PROFESSIONALS CONTAIN THIS.
 THE SHEETS FROM MINICK ENGINEERING ARE OK. PLEASE SEE
 FBC ADMIN SECTION 109.3.6, 109.3.6.4.4 WHICH REQUIRES
 THE STATEMENT FOR THRESHOLD PROJECTS ON ALL ARCH AND
 ENG SHEETS.
 ? TO THE BEST OF THE ARCHITECT?S /OR ENGINEER?S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633 OF THE FLORIDA STATUTES?.
 THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON
 PLANS.
  
 6) NOTE:PLEASE SEE THE *S* SHEETS WHICH DO NOT
 CONTAIN THE REQUIRED LICENSE INFORMATION FOR THE
 ENGINEERING FIRM AS REQUIRED PER FAC 61G15-23.002, FS
 471.023.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADE(S).
  
 7) NOTE: PLEASE SEE SOME OF THE SP SHEETS ARE MISSING
 INFORMATION ON THE TITLE BLOCKS FOR THE PRINTED NAME
 AND LICENSE INFORMATION AS REQUIRED PER FAC 61G1-16.004
 AND FS 481.219
  
 8) NOTE:PLEASE SEE SOME SHEETS AS THE SEALS ARE NOT
 CLEAR AND VISIBLE. THIS COMMENT IS NOT FOR ALL SHEETS
 OR TRADES. PLEASE SEE SP SHEETS.
 PLEASE SEE ALL SEALS SHALL BE CLEAR AND VISIBLE WITH
 ALL INFORMATION ON SAID SEAL EASILY READABLE. PLEASE
 SEE FAC 61G15-23.001, AND 61G1-16.003
 PLEASE SEE SOME SHEETS THE SEALS ARE NOT CLEAR EVEN IF
 SHADOWING WITH LEAD/DUST RUB.
  
 9) NOTE:THIS COMMENT REMAINS AS THE PHOTO-METRICS
 SUBMITTED WERE NOT SUBMITTED OR STAMPED FROM THE PBCHD
 AS NOTED.
 PLEASE KNOW AS THE PLANS SUBMITTED CONTAIN A POOL,
 PLEASE KNOW THIS WILL BE UNDER A SEPARATE PERMIT WITH
 PLANS, FEES AND PERMIT APPLICATION.
 PLEASE KNOW THAT ALL PLANS FOR THIS TYPE OF PUBLIC
 SWIMMING POOL WILL BE REQUIRED TO BE SUBMITTED TO THE
 PALM BEACH COUNTY HEALTH DEPARTMENT FOR ANY REVIEW OF
 COMPLETED PHOTO-METRICS FOR ANY AFTER DUSK SWIMMING.
 PLEASE ALSO SEE ANY PLUMBING REVIEW COMMENTS WHICH MAY
 ALSO REQUIRED THESE PLANS WHEN SUBMITTING FOR SEPARATE
 PERMIT TO ALSO BE STAMPED FOR REVIEW BY THE SAME.
  
 10) NOTE: PLEASE SEE THAT MUCH OF THE INFORMATION
 NEEDED FOR REVIEW FOR CODE COMPLIANCE FOR CHAPTER 13
 HAS NOT YET BEEN SUBMITTED. PLEASE SEE THE ENERGY
 CALCULATIONS PER FBC 2004 CHAPTER 13 THAT WERE
 SUBMITTED FOR REVIEW. 13-415.1.AB.1 DO NOT FULLY
 CORRELATE WITH THE FIXTURES, TYPES, NUMBERS, WATTAGES
 AS SHOWN ON PLANS AND FIXTURE LEGENDS. PLEASE BE SURE
 TO GO THROUGH PLANS AND ENERGY CALCULATIONS AND
 COORDINATE ALL INFORMATION.
 PLEASE SEE THERE ARE ITEMS WHICH EXCEED THE LEVELS AS
 PERMITTED AND/OR DO NOT COORDINATE WITH PLANS AND
 FIXTURE LEGENDS FOR SITE/OUTSIDE AND INTERIOR
 LIGHTING.
 **PLEASE SEE THE 2004 FBC CHAPTER 13.
 **PLEASE SEE 13-413.1ABC.1 WHICH REQUIRES WORST CASE
 VOLTAGE DROP TO BE SHOWN ON PLANS FOR FEEDERS AND
 BRANCH CIRCUITS. THE NOTE FOR CONDUCTOR LENGTH INCREASE
 IS NOTED, HOWEVER PLEASE PROVIDE ABOVE AS REQUIRED.
 PLEASE SEE THIS VOLTAGE DROP INFORMATION COULD NOT BE
 LOCATED FOR THE FEEDERS.
 **PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE
 SEE A COMPLETE LIGHTING CONTROL SYSTEM AND/OR OTHER
 METHODS FOR AUTOMATIC LIGHTING CONTROLS ARE REQUIRED.
 PLEASE SEE AS NO SYSTEM OR DEVICES WERE SUBMITTED,
 REVIEW FOR CODE COMPLIANCE OF SUCH ITEMS COULD NOT BE
 DONE AT THIS TIME.
 A RESPONSE IN THE PLAN REVIEW NOTES MENTIONS THAT THIS
 IS A 24/7/365 OPERATION AND DOES NOT NEED TO MEET ANY
 AUTOMATED LIGHTING CONTROLS. IT IS NOT THAT THE ENTIRE
 BUILDING MUST CONTAIN A FULLY AUTOMATED SYSTEM. THERE
 ARE SEVERAL WAYS TO ACCOMPLISH THIS IN AREAS WHICH WILL
 REQUIRE AUTOMATED SHUTTING OFF OF LIGHTING.
 PLEASE SEE THERE ARE SOME AREAS IN WHICH CAN BE
 CONSIDERED 24HR OPERATION HOWEVER PLEASE SEE .1.3 (3)
 AS THE ROOMS MUST CONTAIN AUTOMATED SHUT OFF FOR ALL
 LIGHTING CIRCUITS IN THESE ROOMS INCLUDING ANY SWITCHED
 RECEPTACLES CIRCUITS.
 THE NOTE ADDED TO THE SHEETS FOR ROOMS DOES NOT PROVIDE
 ENOUGH INFORMATION FOR THIS REQUIREMENT.
 PLEASE SEE ALL OTHER LOCATIONS SUCH AS STORAGE ROOMS
 ETC WHICH CONTAIN FLOOR TO CEILING HEIGHT PARTITIONS
 WILL BE REQUIRED TO CONTAIN AUTOMATED DEVICES. PLEASE
 KNOW THAT THIS WAS FEDERALLY MANDATED IN JULY 04 WHICH
 REQUIRED FOR ALL STATES BY THE NEXT CODE CYCLE TO ADOPT
 THE 1999 ASHAE 90.1 STANDARDS OR BETTER. THE STATE OF
 FLORIDA ADOPTED THE FLORIDA ENERGY EFFICIENCY CODE FOR
 BUILDING CONSTRUCTION.PLEASE SEE THIS WAS ADOPTED ON
 OCT 1ST, 2005. THIS IS REQUIRED STATEWIDE. PLEASE KNOW
 THAT SOME OF THE LOCATIONS WHICH WOULD BE CONSIDERED
 FOR 24HR OPERATION MAY BE THE LOBBY, FRONT DESK,
 RECEPTION OFFICE LOCATIONS ALONG WITH HALLWAYS. NOT ALL
 AREAS ARE OCCUPIED 24/7 THEREFORE MEETING THE INTENT OF
 THE CODE FOR ENERGY CONSERVATION WILL NEED TO MET IN
 OTHER LOCATIONS.
 ** PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR PERFORMANCE
 CALCULATIONS REQUIRED.
 ** PLEASE SEE TRACK LIGHTING REQUIREMENTS PER
 13-415.2.ABC.1.2
  
  
 11) NOTE: PLEASE SUBMIT WIND LOAD INFORMATION FOR ALL
 SITE LIGHTING. PLEASE SEE THE FBC IN THE WIND REGION IS
 140 MPH 3 SECOND GUSTS. PLEASE KNOW THIS WILL BE
 REQUIRED TO BE STATED ON PLANS AND STRUCTURAL
 CALCULATIONS FOR ALL POLES WITH THE EPA (EFFECTIVE
 PROJECTED AREA) OF LIGHT FIXTURE WILL BE CONFIRMED
 BASED ON THE FIXTURES AS NOTED ON PLANS.
 PLEASE SEE THE INFORMATION ON PLANS MENTIONS THE
 MINIMUM RATING AND MENTIONS INFORMATION TO THE
 ELECTRICAL INSPECTOR. PLEASE KNOW THAT THIS INFORMATION
 IS AND WILL BE REQUIRED BE DONE ON PLANS AND SUBMITTED
 FOR REVIEW BEFORE ANY INSTALLATION. PLEASE KNOW THAT IF
 THE WIND LOAD CALCULATIONS AND INFORMATION IS NOT
 SUBMITTED AT THIS TIME, THIS WILL BE PART OF THE
 CONDITIONS OF ISSUANCE WHICH MAY BE DONE
  
 12) NOTE:PLEASE SEE THE ONLY SOME INFORMATION WAS
 SHOWN FOR THE FIRE ALARM INFORMATION AND NO FIRE
 SPRINKLER INFORMATION WAS SUBMITTED.PLEASE SEE THE
 BASE PLANS FOR THIS BUILDING SHALL CONTAIN THE COMPLETE
 FIRE SPRINKLER LAYOUT AND BASE FIRE ALARM SYSTEM PLEASE
 KNOW THAT BOTH OF THESE WILL STILL BE SUBMITTED FOR
 SEPARATE PERMITS PLANS AND FEES AT A LATER DATE ONCE
 THE BUILDING PERMIT IS ISSUED. BASE SYSTEM FOR FIRE
 ALARM IS SHOWN; HOWEVER PLEASE SEE COMMENTS WITH
 RESPECT TO PLANS SUBMITTED FOR THIS AND DEVICES MISSING
 ETC.
 PLEASE KNOW THAT EVEN THOUGH THESE WILL BE UNDER
 SEPARATE PERMIT, THE MINIMUM REQUIREMENTS FOR THE CODE
 SHALL BE SHOWN ON PLANS.
 FBC ADMIN SECTION 106.3.5.1.1 (5).
  
  
 13) NOTE: PLANS DID NOT CHANGE FOR COMPLETE COMPLIANCE.
 PLEASE SEE THE 2004 FBC WHICH CONTAINS THE SAME
 REQUIREMENTS AS THE 2001 FBC. THIS HAS NOT CHANGED IN
 THE STATE OF FLORIDA.
 PLEASE SEE THAT COMPLIANCE FOR ADA DEVICES, LOCATIONS,
 LEVELS ETC HAS NOT BEEN MET.PLEASE SEE THERE ARE
 SEVERAL LOCATIONS MISSING DEVICES WHICH ARE REQUIRED
 AND THERE ARE SEVERAL DEVICES WHICH STILL INDICATE
 LEVELS WHICH DO NOT MEET THE MINIMUM LEVELS AS
 REQUIRED. PLEASE SEE FBC 2004 11-4.28.2, .3(4). PLEASE
 STATE ALL MINIMUM LEVELS AS REQUIRED FOR ALL AREAS.
 PLEASE KNOW THAT THE LEVELS FOR ACCESSIBLE UNITS ARE
 NOTED ON PLANS, HOWEVER THIS IS REQUIRED FOR ALL OTHER
 AREAS AS STATED IN 11-4.28.1, .2 AND .3.
  
 14) NOTE: THIS COMMENT WILL REMAIN AS ALL LOCATIONS FOR
 DEVICES WILL STILL NEED TO BE REVIEWED BY THE FIRE
 REVIEWER AS IF THERE ARE ANY LOCATIONS MISSING THIS
 WILL AFFECT THE ELECTRICAL PLANS.PLEASE SEE FIRE
 REVIEW COMMENTS AS THERE SEEMS FOR MANY LOCATIONS WHICH
 SMOKE DETECTORS ARE MISSING AND WILL BE REQUIRED.
 PLEASE SEE THESE WILL BE STATED BY FIRE REVIEW AND IS
 ONLY GIVEN AS A NOTE AT THIS TIME AS SOME AREAS WHICH
 DO NOT CONTAIN ANY NOTATION FOR THESE DEVICES WILL
 REQUIRE THESE.(PUMP ROOM) ETC
 PLEASE SEE NFPA-72 AND NFPA-101 AND FBC 905
  
 15) NOTE: PLEASE SEE THAT THE REFERENCE FOR NFPA-20
 WOULD BE THE 2003. PLEASE STATE ON PLANS.
  
 16) NOTE: PLEASE SEE SOME OF THE MINIMUM LEVELS SHOWN
 FOR EGRESS PATHS/STAIRS DO NOT MEET THE MINIMUM LEVELS.
 PLEASE SEE THAT THE LIGHTING LEVELS CHANGED WITH THE
 2003 NFPA-101. THIS HAS BEEN IN EFFECT SINCE JAN
 1ST,2005.PLEASECOMPLETE PHOTO-METRICS FOR ALL EGRESS
 PATHS UNDER NORMAL LIGHTING LEVELS AND UNDER EMERGENCY
 LIGHTING LEVELS TO THE PUBLIC RIGHT OF WAY OUT AND AWAY
 FROM BUILDING.
 PLEASE SEE NFPA-101 7.8 AND 7.9.
 PLEASE ALSO SEE 7.8.1.3 AND 7.9.2.2 AS ALL STAIRS SHALL
 INDICATE THE 10FT CANDLES MINIMUM UNDER NORMAL AND THE
 ALLOWED DE-RATED LEVELS UNDER EMERGENCY CONDITIONS TO
 1FT CANDLE.
 FBC 106.1.2 ADMIN SECTION.
 REVIEW FOR COMPLIANCE OF THIS CAN NOT BE DONE AT THIS
 TIME.
  
 17) NOTE:PLEASE PROVIDE THE UL DETAILS FOR ANY AND
 ALL FIRE RATED PENETRATIONS.
 NEC 300.21, NFPA-221, 4.2 ETC.
 PLEASE PROVIDE DETAIL SHEET.
  
 18) NOTE:PLEASE SEE MISSING ROOFTOP REQUIRED GFI
 RECEPTACLES PER 210.63, 210.8 B2.
 FBC 106.1.2, NEC 408.4, 310.16 ETC
  
 19) NOTE: PLEASE SEE THE ELECTRICAL ROOM WHICH IS BEING
 SHOWN ACCESSED THROUGH THE STORAGE ROOM ON THE FIRST
 LEVEL WILL NOT BE PERMITTED. PLEASE SEE THAT THIS
 COMMENT ALSO WILL NOT PERMIT ACCESS THROUGH THE
 ELECTRICAL ROOM TO THE STORAGE ROOM.
 PLEASE KNOW THAT STORAGE ROOMS QUITE OFTEN WILL BECOME
 CLUTTERED EVEN WITH THE MOST DILIGENT OF
 *HOUSEKEEPING*. PLEASE SEE 240.24 , 110.26, 408.7,
 ETC.
 FBC 104.6.
 PLEASE KNOW THAT THIS COMMENT IS REQUIRED EVEN IF NOT
 MADE BY THE FIRE PLAN REVIEWER.
 PLEASE REVISE ACCESS AND LOCATION.
  
 20) NOTE: PLEASE SEE A NOTE ON PLANS, SHEET E-503
 MENTIONS THAT THE LOCATIONS FOR THE SMOKE DETECTORS
 SHALL BE LOCATED A MINIMUM OF 3FT FROM ANY RETURN.
 PLEASE SEE THE STATEMENT ALSO INCLUDES THE DISTANCE
 FROM SUPPLY REGISTERS. PLEASE SEE NFPA-72 11.8.3 AS THE
 DISTANCES FOR THE SUPPLY GRILLES ARE STATED HOWEVER THE
 DISTANCE FROM THE RETURNS IS NOT STATED IN THE CODE.
 PLEASE KNOW THAT AN A/C RETURN AIR GRILLE IS MORE OFTEN
 THAN NOT MUCH LARGER AND THE VOLUME OF CFM IS
 SUBSTANTIALLY HIGHER THAN WHAT A SUPPLY GRILLE WILL
 CONTAIN. PLEASE SEE THAT MANY SMOKE DEVICE MANUFACTURES
 WILL REQUIRE A GREATER DISTANCE FROM THE RETURNS, AS
 MUCH AS 5FT TO 10FT HAS BEEN SEEN BY THIS AHJ. PLEASE
 ADJUST NOTE AND PLEASE LOOK INTO THE DEVICES IN WHICH
 MAY BE USED OR INSTALLED AS THIS WILL PROVIDE THE
 INFORMATION NEEDED TO BE STATED ON PLANS.
 (A 3FT DISTANCE WILL NOT SUFFICE FOR THE RETURN AIR).
  
 21) NOTE: PLEASE SEE THE PREVIOUS NOTE FOR THE AIC
 RATINGS WAS FOR ALL EQUIPMENT NOT ONLY FOR THE FIRE
 PUMP CONTROLLER. PLEASE SEE THE RESPONSE LETTER
 MENTIONS THAT THE RATINGS FOR THE FPC WAS ADDED? PLEASE
 SEE THE RATINGS IN PANELS ARE STILL IN QUESTION AS IT
 APPEARS THAT ALL OF THE BRANCH BREAKERS ARE NOTED TO BE
 22K RATED. PLEASE VERIFY THE RATINGS AND ADJUST. IF THE
 PLANS INDICATE THE BRANCH BREAKERS AS 22K RATED THEN
 THAT IS WHAT WILL BE REQUIRED TO BE INSTALLED. PLEASE
 KNOW IT IS THE RESPONSIBILITY OF THE DESIGN
 PROFESSIONAL TO OBTAIN THIS INFORMATION AT THIS TIME
 AND PLACE ON PLANS. PLEASE CHECK WITH THE LOCAL SERVICE
 PLANNER FROM FLORIDA POWER AND LIGHT AND BE SURE THAT
 ALL INFORMATION ON THE PLANS FOR DESIGN MEETS OR
 EXCEEDS THE AVAILABLE FAULT CURRENT AT THE SERVICE.
 PLEASE SEE 110.9, 110.10, 240.12 ETC.
  
 22) NOTE: PLEASE SEE THIS IS THE SAME COMMENT AS ONLY
 SOME INFORMATION WAS STATED ON PLANS. PLEASE KNOW THAT
 ALL THE MANUFACTURE SPEC/CUTS SHEETS FOR THE FIRE PUMP
 AND FIRE PUMP CONTROLLER ARE REQUIRED AT THIS TIME.
 PLEASE KNOW THAT THE PLANS SHALL BEAR ALL INFORMATION
 AS NEEDED.
 PLEASE SEE AS NO INFORMATION WAS SUBMITTED OF EQUIPMENT
 AS STATED ABOVE REVIEW FOR NUMEROUS ITEMS FOR CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME.
 PLEASE SEE NFPA-20 2003 CHAPTER 9 AND CHAPTER 10.
 PLEASE ALSO SEE NEC 695.4
 ** PLEASE KNOW REFERENCES TO THE CHAPTERS ARE GIVEN AND
 NOT SPECIFIC SECTIONS AS THERE ARE TOO MANY TO LIST.
 DISCONNECTING MEANS, ISOLATION SWITCH, LOCKED ROTOR,
 ETC.
 PLEASE BE SURE EQUIPMENT SHEETS CONTAIN THE LISTING
 FROM A NRTL PER 695.10 AND NFPA-20 10.1.2.1.
  
 23) NOTE:PLEASE SEE THE DOOR SWINGS INTO SOME OF THE
 ELECTRICAL ROOMS AS THE DOOR SWING AS IN AND IN THE
 DIRECTION OF THE ELECTRICAL PANELS CREATES A LIFE
 SAFETY HAZARD. PLEASE SEE IN THE EVEN OF ELECTRICAL
 PERSONNEL WORKING IN THIS ELECTRICAL EQUIPMENT AND THE
 DOOR BEING OPENED IN HIS/HER DIRECTION MAY PUSH THIS
 PERSON INTO THE ELECTRICAL PANEL WHICH MAY BE
 ENERGIZED. PLEASE SEE PLANS WHICH ARE REDLINED FOR
 THESE AT THE 2-5 FLOOR LOCATIONS.
 PLEASE ADJUST.
 FBC 104.6,
 NEC 110.26.
  
 24) NOTE:PLEASE SEE THE KITCHEN EQUIPMENT SCHEDULE ON
 E-201 AS THERE ARE SEVERAL ELECTRICAL APPLIANCES WHICH
 INDICATE THE WRONG OCP, AG, OR THE ACTUAL PHASES WHICH
 ARE FEEDING SOME OF THESE.
 PLEASE SEE SOME OF THE FOLLOWING LISTED BELOW: PLEASE
 SEE THE KITCHEN MICROWAVE SHOWN ON PLANS AS SINGLE POLE
 CIRCUIT, YET EQUIPMENT SCHEDULE INDICATES 3-PHASE?
 PLEASE SEE THE DISHWASHER ON A 1-PHASE CIRCUIT, YET
 SHOWN ON A 60AMP BREAKER WITH 2-PHASES ON PLANS ETC?
 PLEASE SEE THE 70AMP BREAKER ON 12AWG, SINGLE PHASE
 ETC.
 PLEASE SEE THE CONVECTION OVEN WHICH CONTAINS A LOAD
 WHICH EXCEEDS THE SINGLE PHASE 20AMP CIRCUIT WHICH IT
 IS SHOWN ON. PLEASE ALSO SEE THE CIRCUIT ON PLANS. **
 PLEASE GO THROUGH ALL EQUIPMENT, LOADS, PHASES, THE
 AMOUNT AND SIZE OF CONDUCTORS
 240.4, 310.16 ETC.
 FBC 106.1.2 ADDITIONAL INFORMATION AND COORDINATION.
  
 25) NOTE:THIS COMMENT REMAINS AS THE SAME IS NOTED.
 PLEASE SEE SOME DEVICES SHOWN ON PLANS COULD NOT BE
 LOCATED ON THE DEVICE SYMBOL LEGEND. PLEASE COMPLETE
 FOR REVIEW OF THESE ITEMS.
 FBC ADMIN SECTION 106.1.2, 106.3.5.1.2
  
 26) NOTE:THIS COMMENT TO REMAIN AS THE PLANS WILL
 CONTAIN CHANGES WHICH NEW SYMBOLS WILL BE ADDED. PLEASE
 KNOW BASED ON THE REQUIREMENTS OF MANY OF THE REVIEW
 COMMENTS AND FBC CHAPTER 13, THE PLAN KEYNOTES WILL
 MOST LIKELY BE ADJUSTED.
 PLEASE BE SURE TO CORRELATE.
 FBC 106.5.3.1.2, 106.1.2. ADDITIONAL INFORMATION AND
 COORDINATION.
  
 27) NOTE: PLEASE SEE PLANS WHICH INDICATES A DISCONNECT
 FOR THE DISHWASHER SANITIZER IN A DIFFERENT ROOM THAN
 THE EQUIPMENT WHICH IS BEING FED.?
 PLEASE SEE LOCATIONS OF DISCONNECTING MEANS FOR
 EQUIPMENT SHOULD BE LOCATED IN SIGHT OF EQUIPMENT.
 422.30, 31 ETC
 FBC 106.1.2
  
 28) NOTE: PLEASE SEE THE TRANSFORMERS WHICH ARE BEING
 SHOWN ON PLANS FOR THE NOTED ACC UNITS WHICH SHOWS
 THESE LOCATED INSIDE THE CLOTHES CLOSETS.
 PLEASE SEE THAT DUE TO THE HIGH TEMPERATURE OF THESE
 TRANSFORMERS BEING IN THE CLOSE PROXIMITY OF EASILY
 IGNITABLE MATERIALS, THESE LV TRANSFORMERS ARE TO BE
 RELOCATED. THIS AHJ HAS SEEN FIRES WHICH HAVE BEEN
 CREATED BY THIS TYPE OF SCENARIO WHICH CREATES A LIFE
 SAFETY AND PROPERTY HAZARD.
 110.26, 240.24.
 FBC 104.6
  
 29) NOTE: PLEASE SEE THE FOLLOWING COLOR CODING SHALL
 BE NOTED ON PLANS/RISER FOR THE FOLLOWING VOLTAGES.
 PLEASE KNOW THAT AS THE NEC DOES NOT PROVIDE COLOR
 CODING IT IS BEING PROVIDED BY THE AHJ.
 277/480V SYSTEMS
 BROWN, PURPLE, YELLOW AND GREY.
 120/208
 BLACK, RED, BLUE AND WHITE.
 PLEASE INCLUDE.
 FBC 106.4
  
 30) NOTE: PLEASE SEE 210.60 WHICH REFERENCES TO 210.52
 FOR ITEMS REQUIRED.
 PLEASE SEE THE FOLLOWING COMMENTS FOR ROOMS WHICH ARE
 CONSIDERED DWELLING UNITS BY DEFINITIONS.
  
 31) NOTE: PLEASE SEE MISSING THE SMALL APPLIANCE
 CIRCUITS AS REQUIRED PER 210.52B1, 210.11C1 AND 220.16
 THIS COMMENT REMAINS AS THE MINIMUM CIRCUITING IS NOT
 SHOWN MEETING THESE REQUIREMENTS.
 PLEASE KNOW THAT NO OTHER OUTLETS MAY BE FED FROM THESE
 CIRCUITS.
  
 32) NOTE: PLEASE SEE 210.52B1 AS THERE ARE RECEPTACLES
 LOCATED IN THE KITCHEN/BREAKFAST/DINING AREAS WHICH ARE
 FED FROM THE SMALL APPLIANCE CIRCUITS AND LOADS SHALL
 BE FIGURED AS 220.16.
 AS NOTED IN NOTE #31 ABOVE.
  
 33) NOTE: PLEASE SEE MISSING RECEPTACLES PER 210.52 FOR
 2FT OF WALL, KITCHEN AREA, AND KITCHEN WALL OVER 2FT,
 WITHIN 6FT OF DOORS ETC. PLEASE SEE REDLINED PLANS AS
 SOME LOCATIONS ARE STILL MISSING.
 PLEASE KNOW AS THE CODE DOES PERMIT THE SPACING FOR
 HOTEL/MOTELS AND GUEST SUITES TO BE SPACE FOR FURNITURE
 LAYOUTS, IT ALSO STILL REQUIRES THE SAME NUMBER OF
 RECEPTS WHICH WOULD BE REQUIRED IN A DWELLING TO BE
 INSTALLED. PLEASE SEE SOME OF THESE ARE MISSING.
 210.60
  
 34) NOTE: PLEASE SEE AREAS WHICH SEEM TO BE COUNTER
 PENINSULAR AREAS OFF OF KITCHEN WHICH SHOW RECEPTACLES
 AND IF THESE SERVE THE COUNTER SPACES THEN THE
 LOCATIONS OF WALL RECEPTACLES MAY STILL NEED TO BE MET
 AS THE SPACING AND NUMBER OF DEVICE REQUIREMENTS IN
 NOTE #33 ABOVE.
 PLEASE SEE 210.52C3/ 210.52
  
 35) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING
 KITCHEN COUNTER SPACES AND THE LIKE SHALL BE GFI/GFI
 PROTECTED.
 PLEASE SEE THE DEVICES WHICH WERE ADDED DO NOT INDICATE
 GFI PROTECTION.
  
 36) NOTE: PLEASE CLARIFY WHERE THE REQUIRED ARC FAULT
 PROTECTION IS? PLEASE SEE RESPONSE MENTIONS THIS WAS
 REMOVED? THESE UNITS ARE CONSIDERED DWELLING UNITS AND
 THE INTENT OF 210.12 IS TO HAVE ARC FAULT PROTECTION
 FOR ALL OUTLETS IN SLEEPING AREAS. PLEASE SEE THE 2005
 NEC 210.18 AS THE VERBIAGE WAS ADDED TO CLARIFY THIS
 REQUIREMENT. THIS IS AND WAS THE INTENT OF THE CODE.
 PLEASE ALSO SEE THE DEFINITION OF *DWELLING UNIT* HAS
 NOT CHANGED IN THE BUILDING CODE OR THE NEC AND
 REMAINED THE SAME IN THE 2002 NEC AND 2004 FBC. PLEASE
 INDICATE AND INCLUDE THE PROTECTION FOR UNITS. 210.12
  
 37) NOTE: PLEASE COMPLETE ALL PANEL BOARDS WITH THE
 CONDUCTOR SIZES FOR ALL BRANCH CIRCUITS. THE RESPONSE
 MENTIONS ALL CONDUCTORS ARE NUMBER 12AWG UNLESS OTHER
 WISE NOTED. YET THERE IS NO SCHEDULE FOR TYPICAL OCP
 DEVICES AND AWG FOR BRANCH CIRCUITS.
 PLEASE COMPLETE AND PROVIDE.
 PLEASE SEE 310.16, 240.4, FBC 106.1.2, 106.3.5.1.2
 REVIEW FOR CONDUCTORS CAN NOT BE DONE AT THIS TIME.
  
  
 38) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEM
 AT DETACHED BUILDINGS/STRUCTURES PER 250.32
 PLEASE SEE THIS IS BEING SHOWN AT THE DETACHED POOL
 HOUSE, HOWEVER NOT FOR THE SEPARATE STORAGE/DUMPSTER
 BUILDING.
 PLEASE SEE THE CODE IF USING A SINGLE CIRCUIT THEN THIS
 REQUIRES THIS CIRCUIT TO BE GFI. PLEASE SEE CIRCUIT
 H1A-49.
  
  
  
 39) NOTE: PLEASE SEE THE PREVIOUS COMMENT ABOUT THE
 MISSING PANEL SCHEDULE FOR PANEL ?P?. PLEASE CLARIFY
 WHERE LOADS HAVE BEEN FIGURED AT THE 125% AS REQUIRED.
 PLEASE SUBMIT AND COMPLETE EVEN FOR FUTURE LOAD ETC.
 THE MDP DOES LIST THE PANEL, YET LOADS CAN NOT BE
 VERIFIED FOR PANEL SCHEDULE AND SIZE NEEDED.
 220, 215.3, 230.42.
 FBC 106.1.2
  
  
  
 40) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED THE
 GROUNDING ELECTRODE RISER WHICH WAS SUBMITTED, HOWEVER
 PLEASE SEE RISER AS THIS RISER UP THROUGH THE BUILDING
 AND TO ALL OTHER LOCATIONS IS NOT CONNECTED TO THE
 BUILDINGS MAIN GROUNDING ELECTRODE SYSTEM AS SHOWN ON
 RISER. PLEASE COORDINATE RISER AND ADJUST.
  
 41) NOTE:PLEASE SEE 240.13 AND 230.95 AS THE MAIN IS
 BEING SHOWN WITH GFI PROTECTION WHICH IS THAT FOR
 PERSONNEL PROTECTION AND CODE REQUIRES GFP (GROUND
 FAULT PROTECTION WHICH IS NOT THE SAME. PLEASE ADJUST.
 THIS WAS ONLY CHANGED ON ONE SHEET; IN FACT THE RISER
 SHEET NO LONGER INDICATES ANY GF PROTECTION?
  
 42) NOTE:PLEASE SEE THE RISER NOW INDICATES AN
 *EQUIPMENT GROUNDING CONDUCTOR* FROM UTILITY COMPANY
 WHICH IS NOT PERMITTED.
 PLEASE SEE 250.24B, 250.24, 250.6 AND NOTED IN PREVIOUS
 REVIEW.
 PLEASE SEE AS NOTED, (250.6) NO EQUIPMENT GROUNDING
 CONDUCTOR IS INSTALLED BEFORE THE FIRST MEANS OF
 DISCONNECT.
 THIS WOULD CREATE OBJECTIONABLE CURRENTS.
  
  
 43) NOTE: PLEASE SEE 210.8B3 WHICH REQUIRES GFI
 PROTECTION ON ALL 15/20AMP 120V CIRCUITS IN KITCHENS
 AND AREAS OF THE LIKE.
 PLEASE SEE THE PLANS FOR ALL AREAS WHERE FOOD MAY BE
 PREPARED AND APPLIANCE LOCATIONS INCLUDING THE OUTSIDE
 AREAS.
  
 44) NOTE: PLEASE SEE THE UNITS WHICH ARE MISSING SMOKE
 DETECTORS OUTSIDE SLEEPING ROOMS.
 NFPA-11.5.1.1
  
 45) NOTE: PLEASE SEE RISER AS BOTH THE 2ND AND 3RD
 FLOORS INDICATE PANELS *L2A*.
  
 46) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS.
 ** PLEASE KNOW THAT ONE COMPLETE SET OF PLANS IS BEING
 RETAINED BY THIS OFFICE.
  
 *** PLEASE KNOW AS THERE ARE MANY ITEMS NOT YET
 SUBMITTED FOR REVIEW, ALL ITEMS ARE NOT REVIEWED FOR
 CODE COMPLIANCE.
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-04-07 07:01:242007-04-07 07:01:24
 REVIEW IN PROGRESS
2007-04-05 14:15:171-ROLL IN ELEC FOR REVIEW.
 NOTES WILL FOLLOW.