| 2007-01-23 18:01:42 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 06111071 |
| | ADD: 2455 METROCENTRE BLVD |
| | CONT: AUTOBUILDERS |
| | TEL: (561)310-7735 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | HOMEWOOD SUITES HOTEL/ HILTON |
| | FIVE STORY/ 114 UNITS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| | THE COURT. |
| | NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| | NOT ACTUALLY |
| | COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, |
| | SUCH NOTICE IS |
| | NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE |
| | OF COMMENCEMENT |
| | AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3)FBC 1802.2.1 QUESTIONABLE SOILS, |
| | 1802.2.1 QUESTIONABLE SOIL. |
| | WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN |
| | DOUBT, OR WHERE |
| | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| | CODE IS CLAIMED, |
| | THE BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY |
| | INVESTIGATION BE MADE. |
| | SUCH INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| | SECTIONS |
| | 1802.4 THROUGH 1802.6 . |
| | |
| | 4)WEST PALM BCH ADMINISTRATIVE CODE109.3.6 |
| | THIS BUILDING IS CONSIDERED A THRESHOLD BUILDING, |
| | REQUIRING THREE SETS |
| | OF ALL DOCUMENTS TO BE SUBMITTED TO THE BUILDING |
| | DEPARTMENT, PLANS, |
| | REPORTS, SUBMITTALS AND OR PRODUCT APPROVALS. |
| | |
| | 5)FL S. S. 553.71(7) " THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN |
| | HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN |
| | CY CLASSIFICATION AS DEINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS |
| | 5,000 SQ FT IN AREA AND AN OCCUPANT |
| | CONTENT OF GREATER THAN 500 PERSONS. |
| | 105.13.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| | STRUCTURAL INSPECTIONS ON A THRESHOLD |
| | BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE |
| | ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE |
| | OF A BUILDING PERMIT FOR THE |
| | CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURL INSPECTION |
| | PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| | PROCEDURES AND SCHEDULES SO THAT THE |
| | BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 6)WPB AMENDMENT 105.13.6. W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A |
| | SPECIAL INSPECTOR AS REQUIRED BY S. |
| | 553.79(5) FLORIDA STATUTES TO THE MIN- |
| | IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| | CONTACT HAROLD PISKURA MANAGER OF THE |
| | SPECIAL INSPECTOR PROGRAM AT (561) |
| | 805-6711 FOR FURTHER INFORMATION BEFORE |
| | THE PERMIT MAY BE ISSUED. |
| | |
| | 7)W.P.B. AMENDMENT 105.13.4.4 ALL |
| | PLANS FOR THE BUILDING WHICH ARE |
| | REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CON- |
| | TAIN A STATEMENT THAT, TO THE BEST OF |
| | THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, |
| | THE PLANS AND SPECIFICATIONS COMPLY WITH |
| | THE APPLICABLE FIRE-SAFETY STANDARDS AS |
| | DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 8) PLEASE NOTE: |
| | 109.3.10* IMPACT OF CONSTRUCTION. |
| | ALL CONSTRUCTION ACTIVITY REGULATED BY |
| | THIS CODE SHALL BE PERMORMED IN A MANNER |
| | SO AS NOT TO ADVERSELY IMPACT THE |
| | CONDITION OF ADJACENT PROPERTY, UNLESS |
| | SUCH ACTIVITY IS PERMITTED TO AFFECT |
| | SAID PROPERTY PURSUANT TO A CONSENT BY |
| | THE APPLICABLE PROPERTY OWNER, UNDER |
| | TERMS & CONDITIONS AGREEABLE TO THE |
| | APPLICABLE PROPERTY OWNER.THIS INCLUDES |
| | BUT IS NOT LIMITED TO THE CONTROL OF |
| | DUST, NOISE, WATER OR DRAINAGE RUN-OFF, |
| | DEBRIS, AND THE STORAGE OF CONSTRUCTION |
| | MATERIALS. NEW CONSTRUCTION ACTIVITY |
| | SHALL NOT ADVERSELY IMPACT HISTORIC |
| | SURFACE WATER DRAINAGE FLOWS SERVING |
| | ADJACENT PROPERTIES, & MAY REQUIRE |
| | SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| | DEVELOPERS, CONTRACTORS, |
| | AND OWNERS OF ALL NEW RESIDENTIAL |
| | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR |
| | ITEMS, ON EXISTING PROPERTIES RESULTING |
| | IN A DECREASE IN EXCESS OF 800SQ FT OF |
| | PERMEABLE LAND AREA ON ANY PARCELL SHALL |
| | AS A PERMIT CONDITION, PROVIDE A |
| | PROFESSIONALLY PREPARED DRAINAGE PLAN |
| | CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE |
| | IMPROVEMENT, A CERTIFICATE FROM A |
| | LICENSED ENGINEER SHALL BE SUBMITTED TO |
| | THE INSPECTOR IN ORDER TO RECEIVE |
| | APPROVAL OF THE FINAL INSPECTION. |
| | |
| | 9)109.3.10.1 HURICANE PROTECTION. |
| | IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| | ALLOW CONSTRUCTION RELATED MATERIALS |
| | EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION |
| | SITE FROM 24 HRS. AFTER A HURRICANE |
| | WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN |
| | LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| | EQUIPMENT AND DEBRIS SHALL BE EITHER |
| | REMOVED FROM THE CONSTRUCTION SITE OR |
| | SECURED IN SUCH A MANNER AS TO MINIMIZE |
| | THE DANGER OF SUCH CONSTRUCTION |
| | MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH |
| | WINDS. |
| | ANY PERSONS WHO FAILS TO COMPLY TO |
| | REMOVE OR SECURE THE CONSTRUCTION |
| | MATERIALS EQUIPMENT AND DEBRIS WITHIN |
| | 24 HRS AFTER A HURRICANE WATCH HAS BEEN |
| | ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| | EXCEED $500.00. |
| | IN ADDITION TO THE ABOVE, A LICENSED |
| | CONTRACTOR WHO VIOLATES THIS SECTION |
| | SHALL BE SUBJECT TO DISCIPLINE PURSUANT |
| | TO SECTION 113 OF THIS CHAPTER. |
| | |
| | 10) PFVS ARCHITECTURE PLANNING AND INTERIORS |
| | IS MISSING THE FIRMS CERTIFICATE OF AUTHORIZATION. |
| | 481.219 F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE |
| | BLOCK FOR ANY |
| | SHEET BEARING THE NAME OF AN ARCHITECT |
| | PRACTICING UNDER A FICTITIOUS NAME, A |
| | CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL |
| | SERVICES, SHALL INCLUDE |
| | THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER.ADD THE NUMBER TO EACH SHEET. |
| | THIS MAY BE ADDED BY HAND. |
| | |
| | 11)MISSING INFORMATION ON THE ARCHITECTS(PFVS) |
| | TITLEBLOCK, |
| | 61G1-16.004FL. ADMIN. CODE.PLANS |
| | PREPARED BY A REGISTERED ARCHITECT SHALL |
| | INCLUDE A TITLE BLOCK WHICH MUST: |
| | - STATE THE FIRM NAME, ADDRESS AND |
| | TELEPHONE NUMBER |
| | - STATE THE FIRM LICENSE NUMBER |
| | - STATE PROJECT NAME OR IDENTIFICATION |
| | - STATE DATE PREPARED |
| | - INCLUDE AN ORIGINAL SIGNATURE AND |
| | DATED SEAL |
| | - INCLUDE THE PRINTED NAME OF THE |
| | ARCHITECT SEALING THE PLANS |
| | |
| | 12)THE STRUCTURAL SHEETS ARE ALSO MISSING THEIR |
| | (NIELSEN STRUCTURAL ENGINEERS)ENGINEERING CERTIFICATE |
| | OF AUTHORIZATION. |
| | 471.023 F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE |
| | BLOCK FOR ANY |
| | SHEET BEARING THE NAME OF AN ENGINEER |
| | PRACTICING UNDER A FICTITIOUS NAME, A |
| | CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING |
| | SERVICES, |
| | SHALL INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER. |
| | ADD THE NUMBER TO EACH SHEET.THIS MAY |
| | BE ADDED BY HAND. |
| | |
| | 13)THE STRUCTURAL ENGINEERS TITLEBLOCK SHOULD CONTAIN |
| | THE FOLLOWING INFORMATION: |
| | 61G15-23.002(2) A TITLE BLOCK ON EACH SHEET SHOLD |
| | CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE |
| | NUMBER OF THE ENGINEER OR IF APPLICABLE, |
| | THE NAME AND LICENSE NUMBER OF THE ENGINEER, AND THE |
| | NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER |
| | OF THE ENGINEERING BUSINESS . |
| | |
| | 14)SHEET G-000: |
| | 14A)PROJECT IS LOCATED IN A SHEET G-000 VSG-002, |
| | G-000 PROVISIONS FOR ADA INDICATES 130 ROOMSVS. G-002 |
| | INDICATES 114 ROOMS, PLEASE CORRECT. |
| | |
| | 14B) THE PROJECT INDICATES THIS TO BE A (5) STORY, TYPE |
| | I-B SPRINKLERED BUILDING, THERE ARE NO PLANS FOR FIRE |
| | SPRINKLERS IN THE PLANS. FL S S 553.895(2) REQUIRES |
| | BUILDINGS 3 STORIES OR MORE TO HAVE FIRE SPINKLERS, |
| | SUBMIT PLANS FOR REVIEW BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 15) SHEET A-401: |
| | 15A) PLEASE PROVIDE THE ELEVATIONS, CHANGE IN GRADE |
| | FROM UNDER THE PORTICO TO THE LOBBY, PLANS ARE NOT |
| | CLEAR AS TO IF THERE IS A CURB OR ALL AT GRADE LEVEL. |
| | 11-4.5.2 CHANGES IN LEVEL. |
| | |
| | 15B) THE FRONT ENTRY DOORS (158) APPEAR TO BE |
| | HORIZONTAL SLIDING DOORS, PLEASE PROVIDE INFORMATION |
| | FOR MANUAL LY OPERATED (BREAK AWAY) IF LOSS OF POWER. |
| | SECTION 1008.1.3.3. |
| | |
| | 16) SHEETA-404 |
| | |
| | 16A) PLANS INDICATES BLOCK WALLS THAT SEPERATE THE |
| | CORRIDOR AND INDIVIDUAL SUITES WITH A SYMBLE "AO" , |
| | SHEET A-601 WALL TYPE "AO" AS A STUDS AND DRYWALLWITH |
| | A STC RATING OF 34L, THIS IS COMMON TO ALL SLEEPING |
| | UNITS, SEE 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS |
| | AND FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS |
| | FROM EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL |
| | HAVE A SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED |
| | IN ACCORDANCE WITH ASTM E 90. PENETRATIONS OR OPENINGS |
| | IN CONSTRUCTION ASSEMBLIES FOR PIPING; ELECTRICAL |
| | DEVICES; RECESSED CABINETS; BATHTUBS; SOFFITS; OR |
| | HEATING, VENTILATING OR EXHAUST DUCTS SHALL BE SEALED, |
| | LINED, INSULATED OR OTHERWISE TREATED TO MAINTAIN THE |
| | REQUIRED RATINGS. THIS REQUIREMENT SHALL NOT APPLY TO |
| | DWELLING UNIT ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL |
| | BE TIGHT FITTING TO THE FRAME AND SILL. |
| | |
| | 16B) PROVIDE THE STC RATING FOR FLOORS TO ALL SLEEPING |
| | UNITS ABOVE THE FIRST FLOOR.1207.3 |
| | STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. |
| | |
| | 16C) ELEVATOR SHAFT WALL DESIGNATION MISSING, 5 STORIES |
| | REQUIES A 2 HR WALL RATING, 707.4 |
| | |
| | 16D) PLANS INDICATE THE USE OF AN ELEVATOR LOBBY THAT |
| | REQUIRES A 1HR FIRE RATING 707.14.1, DOOR SCHEDULE |
| | INDICATES A "C" RATING OF THIS DOOR. |
| | DOORS ARE RATED IN MINUTES AND HRS SEE TABLE |
| | 715.3.MISSING DOOR HARDWARE SCHEDULE. |
| | |
| | 16E)ELEVATOR MACHINE ROOM HAS A 2 HR RATING BUT THE |
| | DOOR SCHEDULE INDICATES "PER CODE" THIS TERMINOLOGY |
| | NEEDS TO BE REPLACED BY THE RATING IN TABLE 715.3. |
| | |
| | 16F) ELEVATOR LOBBY # 130 SHOWS ELECTRIC MAGNET HOLD |
| | OPEN DEVICES WHERE AS E-204 IS MISSING THE HOLD OPEN |
| | DEVICES. |
| | |
| | 16G) . THERE IS A MAKE UP AIR SHAFT NEXT TO STORAGE |
| | ROOM# 141, PLANS DO NOT INDICATE ANY WALL RATING, |
| | PLEASE PROVIDE. TABLE 707.4. |
| | |
| | 16H) PLANS INDICATE A FIREEXTINGUISHER CABINET IN THE |
| | FIRE RATED WALL RECESSED. PROVIDE DETAIL INDICATING HOW |
| | THE FIRE RATING IS MAINTAINED. 707.4. |
| | |
| | 16I) STAIR TOWER# 1 ALSO INDICATES WALL RATING "MISSING |
| | HOUR LABEL", 2HR FIRE RATING REQUIRED. SEE 707.4. |
| | |
| | 16J) STAIR TOWER# 1 IS MISSING DOOR IDENTIFICATION TAG |
| | IN THE DOOR SCHEDULE, PLEASE SHOW RATING TABLE 715.3 |
| | ,MISSING HARDWARE SCHEDULE. |
| | |
| | 16K) STAIR TOWER# 1 NO DIMENSION IS PROVIDED AT THE |
| | DOOR,SHEET A-101 INDICATES A MO OF 3'-2" WHAT SIZE |
| | DOOR IS BEING INSTALLED? WHATWILL THE OCCUPANT LOAD |
| | BE FOR THIS DOORWAY? MISSING HARDWARE, TYPICAL. |
| | |
| | 16L) COMMON TO ALL SLEEPING UNITS, DOOR 100 & 101 NO |
| | DOOR TO A SLEEPING UNIT ARE SHOWN ON THE DOOR SCHEDULE? |
| | PLEASE PROVIDE DOOR TYPE, DOOR WIDTH AND FIRE RATING. |
| | TABLE 715.3, 1008.1.1. MISSING HARDWARE SCHEDULE, |
| | TYPICAL. |
| | |
| | 16M) STAIRWELLS ARE MISSING STANDPIPES,905.1 GENERAL. |
| | STANDPIPE SYSTEMS SHALL BE PROVIDED IN ALL NEW |
| | BUILDINGS IN WHICH: |
| | 1.THE HIGHEST FLOOR IS GREATER THAN 30 FEET (9144 |
| | MM) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE |
| | ACCESS; OR |
| | 2.THE HIGHEST FLOOR IS MORE THAN THREE STORIES |
| | ABOVE GRADE. |
| | |
| | 16N) PLEASE PROVIDE INFORMATION FOR ELEVATOR CARS TO |
| | ACCOMMODATE AMBULANCE STRETCHER. |
| | 3002.4 ELEVATOR CAR TO ACCOMMODATE AMBULANCE |
| | STRETCHER. |
| | |
| | IN BUILDINGS FOUR STORIES IN HEIGHT OR MORE, AT LEAST |
| | ONE ELEVATOR SHALL BE PROVIDED FOR FIRE DEPARTMENT |
| | EMERGENCY ACCESS TO ALL FLOORS. SUCH ELEVATOR CAR SHALL |
| | BE OF SUCH A SIZE AND ARRANGEMENT TO ACCOMMODATE A |
| | 24-INCH BY 76-INCH (610 MM BY 1930 MM) AMBULANCE |
| | STRETCHER IN THE HORIZONTAL, OPEN POSITION AND SHALL BE |
| | IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR EMERGENCY |
| | MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL SHALL NOT |
| | BE LESS THAN 3 INCHES (76 MM) HIGH AND SHALL BE PLACED |
| | INSIDE ON BOTH SIDES OF THE HOISTWAY DOOR FRAME. |
| | |
| | 17) SHEET A-101: |
| | 17A) PLANS INDICATES A DETAIL# 6 ON SHEET A-502, INDEX |
| | INDICATES SUCH A SHEET EXIST, PLANS ARE MISSING THIS |
| | DETAIL SHEET. |
| | ADDITIONAL COMMENTS MAY APPEAR ON THE NEXT REVIEW FOR |
| | THIS SECTION WITH NEW SUBMITTAL. |
| | |
| | 17B) STAIRWELL# 2 IS MISSING THE STANDPIPE: |
| | 905.1 GENERAL. |
| | STANDPIPE SYSTEMS SHALL BE PROVIDED IN ALL NEW |
| | BUILDINGS IN WHICH: |
| | 1.THE HIGHEST FLOOR IS GREATER THAN 30 FEET (9144 |
| | MM) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE |
| | ACCESS; OR |
| | 2.THE HIGHEST FLOOR IS MORE THAN THREE STORIES |
| | ABOVE GRADE |
| | |
| | 18)SHEET A-101 INDICATES A SECTION # 2 OF A-402 THIS |
| | IS THE 2ND THROUGH THE 5TH FLOOR, DETAIL (1) OF THIS |
| | SHEET IS THE FIRST FLOOR. |
| | |
| | 18A) DETAIL A IS MISSING THE STORAGE ROOM 142, PLEASE |
| | IDENTIFY THE WALL RATING |
| | OF THE SHAFT LOCATED IN THIS ROOM AND ALL OTHER COMMON |
| | SHAFTS.106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 18B) DETAIL# 1 ALSO INDICATES THE LAUNDRY ROOM IS THE |
| | TERMINATION OF THE LAUNDRY CHUTE. |
| | 707.13.4 TERMINATION ROOM. |
| | REFUSE AND LAUNDRY CHUTES SHALL DISCHARGE INTO AN |
| | ENCLOSED ROOM COMPLETELY SEPARATED FROM THE REMAINDER |
| | OF THE BUILDING BY CONSTRUCTION THAT HAS A |
| | FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR AND |
| | OPENINGS INTO THE TERMINATION ROOM SHALL BE PROTECTED |
| | BY OPENING PROTECTIVES HAVING A FIRE PROTECTION RATING |
| | OF NOT LESS THAN ? HOUR AND SHALL BE SELF-CLOSING OR |
| | AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE. REFUSE |
| | CHUTES SHALL NOT TERMINATE IN AN INCINERATOR ROOM. |
| | REFUSE AND LAUNDRY ROOMS THAT ARE NOT PROVIDED WITH |
| | CHUTES NEED ONLY COMPLY WITH TABLE 302.1.1 .NO DOOR |
| | HARDWARE SCHEDULE , TYPICAL. |
| | |
| | 18C) THE DOOR SCHEDULE FOR DOOR# 124 COORIDOR TO |
| | LAUNDRY INDICATES A WINDOW WITH TEMPERED GLASS, FOR |
| | RATED DOORS SEE TABLE 715.4.3 FOR MAXIMUM SIZE OF |
| | WINDOW AND TYPE OF GLASS. |
| | |
| | 18D) DETAIL# 22ND-5TH FLOOR LAUNDRY CHUTE AND LINEN |
| | STORAGE INDICATES THE LAUNDRY CHUTE WITHIN A LAUNDRY |
| | STORAGE ROOM,PROVIDE DETAILS ON THE LAUNDRY CHUTE |
| | ENCLOSURE, OPENINGS INTO THE SHAFT (DOOR) AND FIRE |
| | RATINGS OF LAUNDRY CHUTE DOOR.707.13.1. |
| | |
| | 18E) PLEASE PROVIDE A SECTION THROUGH THE LAUNDRY CHUTE |
| | PROVIDING THE FOLLOWING: |
| | 903.2.10.2 RUBBISH AND LINEN CHUTES. |
| | AN AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED AT THE |
| | TOP OF RUBBISH AND LINEN CHUTES AND IN THEIR TERMINAL |
| | ROOMS. CHUTES EXTENDING THROUGH THREE OR MORE FLOORS |
| | SHALL HAVE ADDITIONAL SPRINKLER HEADS INSTALLED WITHIN |
| | SUCH CHUTES AT ALTERNATE FLOORS. CHUTE SPRINKLERS SHALL |
| | BE ACCESSIBLE FOR SERVICING. |
| | PROVIDE DETAIL OF HOW SPRINKLERS WILL BE ACCESSIBLE IN |
| | THE 2 HR RATED SHAFT. |
| | |
| | 18F) WATER HEATER ROOMS 2ND -5TH FLOOR ARE MISSING FROM |
| | THE DOOR SCHEDULE. PLEASE PROVIDE DOOR RATING, |
| | HARDWARE, ETC. TABLE 715,3. |
| | |
| | 18G) FIRST FLOOR ELECTRICAL ROOM 153 IS ALSO MISSING |
| | WALL RATINGS SEE UTILITY OCCUPANCY RATING TABLE |
| | 302.3.2. |
| | |
| | 19) SHEET A-102: |
| | 19A) DETAIL# 2/ 502, THE INDEX INDICATES SUCH A SHEET |
| | EXIST, PLANS ARE MISSING THIS SHET COMMON TO 2ND -5TH |
| | FLOOR. |
| | ADDITIONAL COMMENTS WILL APPEARON THE NEXT REVIEW FOR |
| | THIS SECTION WITH NEW SUBMITTAL. |
| | |
| | 19B) DETAIL#2 /503,IS MISS LABELED, PLEASE CORRECT. THE |
| | INDEX INDICATES SUCH A SHEET EXIST, PLANS ARE MISSING |
| | THIS SHET COMMON TO 2ND -5TH FLOOR. |
| | ADDITIONAL COMMENTS WILL APPEARON THE NEXT REVIEW FOR |
| | THIS SECTION WITH NEW SUBMITTAL. |
| | |
| | 19C) DETAIL#2 /504,IS MISS LABELED, PLEASE CORRECT. THE |
| | INDEX INDICATES SUCH A SHEET EXIST, PLANS ARE MISSING |
| | THIS SHET COMMON TO 2ND -5TH FLOOR. |
| | ADDITIONAL COMMENTS WILL APPEARON THE NEXT REVIEW FOR |
| | THIS SECTION WITH NEW SUBMITTAL. |
| | |
| | 20) SHEET A-103: |
| | 20A) SEE DETAIL 2/A-402, COMMON 2ND FL -5TH FLOOR, |
| | LAUNDRY CHUTE, THERE IS NO SHAFT WALL DESIGNATION FOR |
| | FIRE RATING, 707.2. |
| | |
| | 20B)ROOMS 327 & 328 SHARE A SHFT WALL IN COMMON, THE |
| | SHAFT IS BUILT RIGHT INTO THE BATHROOM WALL, HOW WILL |
| | THE BACKING FOR SHOWER AND TUB BE INSTALLED? |
| | |
| | 20C) DETAIL1/A-403 FIRST FLOOR LEVEL, INDICATES ROOM# |
| | 114 TO THE MACHINE ROOM FOR ELEVATOR# 2, REQUIRING A 2 |
| | HR RATING WITH 1 1/2 HR RATED DOOR. PLEASE CORRECT. THE |
| | WALL THE DOOR IS LOCATED IN DOESN'T EVEN HAVE A WALL |
| | IDENTIFICATION TAG. |
| | |
| | 20D) DETAIL1/A-403 ELEVATOR MACHINE ROOMWALL |
| | IDENTIFICATION TAG SHOULD READ A 2HR FIRE RATING WITH 1 |
| | 1/2 HR OPENING PROTECTION. |
| | |
| | 20E)ELEVATOR LOBBY TO HAVE 1HR FIRE RATING WITH |
| | OPENING PROTECTIVES OF 3/4 HR . 707.14.1 NOTE WILL |
| | THESE DOORS BE ON HOLD OPEN DEVICES? DOOR SHCEDULE |
| | INDICATES YES, ELECTRICAL SHEETS NO? |
| | |
| | 20F) EXERCISE ROOM 1ST FL INDICATES THE USE OF A HOUSE |
| | PHONE PROVIDE MOUNTING HEIGTH WITHIN REACH RANGES. |
| | 11-4.31.3. |
| | |
| | 20G) EXERCISE ROOM DOOR 118 TO BE FIRE RATED IN HRS/ |
| | MIN. TABLE 715.3SIZE OF WIRE PANEL? |
| | |
| | 20H) ROOM# 116, 216, 316 THE ICE ROOM, FIRST FLOOR |
| | THERE IS NO SHAFT WALL AROUND THE |
| | MAKE UP AIR SHAFT, 2ND- 5TH FLOOR NO WALL TYPE |
| | IDENTIFICATION AROUND SHAFT WALL CONSTRUCTION. |
| | |
| | 20I) 2ND - 5TH FLOORS SAME ISSUES, THE ELECTRICAL ROOM |
| | DOOR IS MISSING IDENTIFICATION TAG AND FIRE |
| | RATING.707.4. |
| | |
| | 20I) STORAGEE ROOM 251 COMMON 2ND- 5TH FLOOR, THIS IS A |
| | RATED CORRIDOR TABLE 1016 WALL IDENTIFICATION TAG |
| | SHOULD INDICATE AS SUCH AND IN DOOR SCHEDULE. TABLE |
| | 715.3. |
| | |
| | 20K) STORAGE ROOM 318/ 418 STORAGE ROOM WALLS AS WELL |
| | AS THE MAINTENANCE ROOM518, 1 HR RATED, DOORS TTABLE |
| | TABLE 715.3. |
| | |
| | 21) SHEET A-105,& A-503 PLANS CALL FOR ROOF ACCESS IN |
| | STORAGE ROOMS 541 & 542 TO GAIN ACCES FOR ROOF MOUNTED |
| | MECHANICAL EQUIPMENT. PLANS DO NOT PROVIDE HOW ONE |
| | GAINS ACCESS, IT IS ASSUMED BY A SHIPS LADDER. PLANS |
| | ALSO DO NOT PROVIDE A CUT SECTION OF THIS 5TH FLOOR |
| | CLOSET IN RELATION TO THE MECHANICAL WELL LOCATED AT |
| | THE ROOF LEVEL? WHAT DISTANCE OF TRAVEL THROUGH THE |
| | ATTIC AREA, LIGHTING NOR IDENTIFY THE DOOR THAT LEADS |
| | TO THE MECHANICAL WELL? |
| | |
| | DETAI# 1 /A-503 PROVIDES THE DEAIL BUT NO ACCESS IS |
| | PROVIDED FROM THE 5TH FLOOR. |
| | |
| | THIS ROOF TOP MECHANICAL WELL IS LOCATED ON A FLAT |
| | ROOFTOP DECK WHICH IS ALSO MORE THAN 4 STORIES ABOVE |
| | GRADE. SEE 1009.12 ACCESS TO ROOF. |
| | |
| | 1009.12 ACCESS TO ROOF. |
| | BUILDINGS FOUR STORIES OR MORE IN HEIGHT, EXCEPT THOSE |
| | WITH A ROOF SLOPE GREATER THAN 4:12, SHALL BE PROVIDED |
| | WITH A STAIRWAY TO THE ROOF. SUCH STAIRWAY SHALL BE |
| | MARKED AT STREET AND FLOOR LEVELS WITH A SIGN |
| | INDICATING THAT IT CONTINUES TO THE ROOF. WHERE ROOFS |
| | ARE USED FOR ROOF GARDENS OR FOR OTHER PURPOSES, |
| | STAIRWAYS SHALL BE PROVIDED AS REQUIRED FOR SUCH USE OR |
| | OCCUPANCY. |
| | CODE COMMENTARY: IN BUILDINGS FOUR OR MORE STORIES |
| | HIGH, ROOF THAT ARE NOT USED FOR HABITABLE PURPOSES |
| | MUST BE MADE ACCESSIBLE BY CONVENTIONALSTAIRWAYS. TWO |
| | REASONS FOR THIS ARE ACCESS FOR ROOF OR EQUIPMENT |
| | REPAIR AND FIRE DEPARTMENT ACCESS DURING A FIRE EVENT. |
| | |
| | 22) SHEET A-301 PLANS INDICATE THE USE OF CORRIGATED |
| | METAL DECK, DENSE DECK AND ICE & WATER SHIELD. THIS |
| | SECTION WAS TAKEN FROM THE ENTRY AREA FIRST FLOOR, IS |
| | THIS SAME ROOFING CONCEPT TO BE USED ON THE UPPER |
| | PORTION OF THE FIVE STORY BUILDING? |
| | |
| | 23) SHEET A-301 ALSO INDICATES THE USE OF RIDGE VENTS, |
| | PLEASE PROVIDE DETAILS FOR FRAMING AT THE RIDGE AREA, |
| | AS WELL AS THE PRODUCT APPROVAL PROVIDING ATTACHMENT |
| | METHODS. |
| | SHEET A-504 DETAIL# 9 INDICATES A INSTALATION OF |
| | THE RIDGE WITHOUTA RIDGE VENT PLEASE TAKE NOTE OF |
| | CONCRETE TILE ATTACHMENT 1507.3.7 AND 1509.3.8 |
| | APPLICATION BOTH REFRENCE FRSA/ RTI07320/ 4TH EDITION |
| | FOR THE INSTALLATION OF RIDGE AND HIP TILE. PLEASE |
| | CORRECT SECTION AND PROVIDE IF THE HIP/ RIDGE BACKER |
| | BOARD WILL BE METAL OR WOOD? PROVIDE THE CLIP SYSTEM TO |
| | BE USED, AND THE SIZE OF FASTENER FOR EACH. |
| | |
| | 24) SHEET A-301ENLARGED SECTION DETAIL OF ROOF |
| | INDICATED A STEEL DECK DENSEGLASS AND ICE & WATER |
| | SHIELD UNDERLAYMENT, SHEET A-302DETAIL # 3INDICATES |
| | THE USE OF A |
| | (P540) U.L. LISTED ROOF/ CEILING ASSEMBLY. AS PART OF |
| | THIS SYSTEM PART # 5 INDICATES THE USE OF VARIOUS |
| | ROOFING INSULATIONS USED ABOVE THE STEEL DECK PLEASE |
| | CORRALATE AND CORRECT . |
| | THIS SAME DETAIL INDICATES THE USE OF FURRING CHANNELS |
| | AND 5/8" DRYWALL. |
| | |
| | 25) SHEET A-303 DETAIL# 3 ALSO INDICATES THE USE OF UL |
| | LISTING P540 VERSES THE DETAIL 4/501WHERE NO |
| | INSULATION, NOR DENSEGLASS USED ABOVE THE STEEL ROOF |
| | DECK. |
| | |
| | 26) SHEET A-501 GABLE END DETAIL INDICATES THE USE OF |
| | STEEL STUDS, NO INFORMATION AS TO SIZE, GAUGE, SPACING |
| | OFSTEEL STUDS. THE SAME DETAIL INDICATES THE USE OF |
| | PLYWOODSHEATHING BUT NOT THE WALL FINISH? 106.1.2. |
| | ADDITONAL INFOEMATION REQUIRED.S-309 INDICATES A |
| | DROPPED GABLE END FOR THE GABLES NO MENTION AS TO |
| | BRACING REQUIREMENTS |
| | |
| | 27) A-702 SECTION# 1 PLEASE PROVIDE VENTING FOR |
| | ELEVATORS: |
| | 3004.1 VENTS REQUIRED. |
| | HOISTWAYS OF ELEVATORS AND DUMBWAITERS PENETRATING MORE |
| | THAN THREE STORIES SHALL BE PROVIDED WITH A MEANS FOR |
| | VENTING SMOKE AND HOT GASES TO THE OUTER AIR IN CASE OF |
| | FIRE. |
| | 3004.2 LOCATION OF VENTS. |
| | VENTS SHALL BE LOCATED BELOW THE FLOOR OR FLOORS AT THE |
| | TOP OF THE HOISTWAY, AND SHALL OPEN EITHER DIRECTLY TO |
| | THE OUTER AIR OR THROUGH NONCOMBUSTIBLE DUCTS TO THE |
| | OUTER AIR. NONCOMBUSTIBLE DUCTS SHALL BE PERMITTED TO |
| | PASS THROUGH THE ELEVATOR MACHINE ROOM PROVIDED THAT |
| | PORTIONS OF THE DUCTS LOCATED OUTSIDE THE HOISTWAY OR |
| | MACHINE ROOM ARE ENCLOSED BY CONSTRUCTION HAVING NOT |
| | LESS THAN THE FIRE PROTECTION RATING REQUIRED FOR THE |
| | HOISTWAY. HOLES IN THE MACHINE ROOM FLOORS FOR THE |
| | PASSAGE OF ROPES, CABLES OR OTHER MOVING ELEVATOR |
| | EQUIPMENT SHALL BE LIMITED SO AS NOT TO PROVIDE GREATER |
| | THAN 2 INCHES (51 MM) OF CLEARANCE ON ALL SIDES. |
| | |
| | 28) A-702 PLANS DO NOT INDICATE REQUIREMEENTS FOR |
| | BRAILLE CHARACTERS AT HOISTWAY ENTRANCES. 11-4.10.5 |
| | RAISED AND BRAILLE CHARACTERS ON HOISTWAY ENTRANCES. |
| | ALL ELEVATOR HOIST WAY ENTRANCES SHALL HAVE RAISED AND |
| | BRAILLE FLOOR DESIGNATIONS PROVIDED ON BOTH JAMBS. THE |
| | CENTERLINE OF THE CHARACTERS SHALL BE 60 INCHES (1525 |
| | MM) ABOVE FINISH FLOOR. SUCH CHARACTERS SHALL BE 2 |
| | INCHES (50 MM) HIGH AND SHALL COMPLY WITH SECTION |
| | 11-4.30.4 . PERMANENTLY APPLIED PLATES ARE ACCEPTABLE |
| | IF THEY ARE PERMANENTLY FIXED TO THE JAMBS (SEE FIGURE |
| | 11-20 ). |
| | |
| | 29A) 1609.1.4 PROTECTION OF OPENINGS. |
| | IN WIND-BORNE DEBRIS REGIONS, EXTERIOR |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE |
| | IN THE LOWER 60 FEET (18.3 M) IN |
| | BUILDINGS SHALL BE ASSUMED TO BE |
| | OPENINGS AND THE BALANCE OF GLAZED |
| | OPENINGS IN THE REST OF THE BUILDING |
| | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE |
| | IS IMPACT RESISTANT OR PROTECTED WITH AN |
| | IMPACT RESISTANT COVERING MEETING THE |
| | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND |
| | ASTM E 1996, OR MIAMI-DADE TAS 201, 202 |
| | AND 203 REFERENCED THEREIN AS FOLLOWS: |
| | 1.GLAZED OPENINGS LOCATED WITHIN 30 |
| | FEET (9.1 M) OF GRADE SHALL MEET THE |
| | REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2.GLAZED OPENINGS LOCATED MORE THAN |
| | 30 FEET (9.1 M) ABOVE GRADE SHALL MEET |
| | THE PROVISIONS OF THE SMALL MISSILE |
| | TEST. |
| | |
| | 29B) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | |
| | 29C)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL.] |
| | |
| | 29D) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOW |
| | FIXED |
| | SINGLE HUNG |
| | MULLION |
| | B) GLAZED DOORS |
| | AUTOMATIC HORIZONTAL SLIDING DOORS |
| | EXTERIOR HOLLOW METAL DOORS |
| | C) LOUVERS |
| | D) PANEL WALL SYSTEMS |
| | SOFFITS- HARDI SOFFIT BOARD |
| | E) STRUCTURAL COMPONENTS- TRUSS ANCHORS |
| | F) ROOF ASSEMBLIES |
| | FLAT ROOFS- MODIFIED/ BITUMEN |
| | SLOPED:UNDERLAYMENTS, ROOF TILE ADHESIVES, ROOF |
| | TILE APPLICATIONS |
| | |
| | 30) ASEPERATE PERMIT IS REQUIRED FOR THE POOL, POOL |
| | EQUIPMENT BUILDING , POOL FENCING AND SIGNAGE. |
| | |
| | 31)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |