Date Text
2007-01-23 18:01:42 
 BUILDING PLAN REVIEW
 PERMIT: 06111071
 ADD: 2455 METROCENTRE BLVD
 CONT: AUTOBUILDERS
 TEL: (561)310-7735
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 HOMEWOOD SUITES HOTEL/ HILTON
 FIVE STORY/ 114 UNITS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF,
 SUCH NOTICE IS
 NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE
 OF COMMENCEMENT
 AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)FBC 1802.2.1 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL.
 WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN
 DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED,
 THE BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE.
 SUCH INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS
 1802.4 THROUGH 1802.6 .
  
 4)WEST PALM BCH ADMINISTRATIVE CODE109.3.6
 THIS BUILDING IS CONSIDERED A THRESHOLD BUILDING,
 REQUIRING THREE SETS
 OF ALL DOCUMENTS TO BE SUBMITTED TO THE BUILDING
 DEPARTMENT, PLANS,
 REPORTS, SUBMITTALS AND OR PRODUCT APPROVALS.
  
 5)FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN
 CY CLASSIFICATION AS DEINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS
 5,000 SQ FT IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE
 OF A BUILDING PERMIT FOR THE
 CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURL INSPECTION
 PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE
 BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 6)WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 7)W.P.B. AMENDMENT 105.13.4.4 ALL
 PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CON-
 TAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH
 THE APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 8) PLEASE NOTE:
 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 9)109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 10) PFVS ARCHITECTURE PLANNING AND INTERIORS
 IS MISSING THE FIRMS CERTIFICATE OF AUTHORIZATION.
 481.219 F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ARCHITECT
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL
 SERVICES, SHALL INCLUDE
 THE CERTIFICATE OF AUTHORIZATION
 NUMBER.ADD THE NUMBER TO EACH SHEET.
 THIS MAY BE ADDED BY HAND.
  
 11)MISSING INFORMATION ON THE ARCHITECTS(PFVS)
 TITLEBLOCK,
 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE A TITLE BLOCK WHICH MUST:
 - STATE THE FIRM NAME, ADDRESS AND
 TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND
 DATED SEAL
 - INCLUDE THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS
  
 12)THE STRUCTURAL SHEETS ARE ALSO MISSING THEIR
 (NIELSEN STRUCTURAL ENGINEERS)ENGINEERING CERTIFICATE
 OF AUTHORIZATION.
 471.023 F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE
 BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES,
 SHALL INCLUDE THE CERTIFICATE OF AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 13)THE STRUCTURAL ENGINEERS TITLEBLOCK SHOULD CONTAIN
 THE FOLLOWING INFORMATION:
 61G15-23.002(2) A TITLE BLOCK ON EACH SHEET SHOLD
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER, AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS .
  
 14)SHEET G-000:
 14A)PROJECT IS LOCATED IN A SHEET G-000 VSG-002,
 G-000 PROVISIONS FOR ADA INDICATES 130 ROOMSVS. G-002
 INDICATES 114 ROOMS, PLEASE CORRECT.
  
 14B) THE PROJECT INDICATES THIS TO BE A (5) STORY, TYPE
 I-B SPRINKLERED BUILDING, THERE ARE NO PLANS FOR FIRE
 SPRINKLERS IN THE PLANS. FL S S 553.895(2) REQUIRES
 BUILDINGS 3 STORIES OR MORE TO HAVE FIRE SPINKLERS,
 SUBMIT PLANS FOR REVIEW BEFORE A PERMIT CAN BE ISSUED.
  
 15) SHEET A-401:
 15A) PLEASE PROVIDE THE ELEVATIONS, CHANGE IN GRADE
 FROM UNDER THE PORTICO TO THE LOBBY, PLANS ARE NOT
 CLEAR AS TO IF THERE IS A CURB OR ALL AT GRADE LEVEL.
 11-4.5.2 CHANGES IN LEVEL.
  
 15B) THE FRONT ENTRY DOORS (158) APPEAR TO BE
 HORIZONTAL SLIDING DOORS, PLEASE PROVIDE INFORMATION
 FOR MANUAL LY OPERATED (BREAK AWAY) IF LOSS OF POWER.
 SECTION 1008.1.3.3.
  
 16) SHEETA-404
  
 16A) PLANS INDICATES BLOCK WALLS THAT SEPERATE THE
 CORRIDOR AND INDIVIDUAL SUITES WITH A SYMBLE "AO" ,
 SHEET A-601 WALL TYPE "AO" AS A STUDS AND DRYWALLWITH
 A STC RATING OF 34L, THIS IS COMMON TO ALL SLEEPING
 UNITS, SEE 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS
 AND FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS
 FROM EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL
 HAVE A SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN
 50 (45 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED
 IN ACCORDANCE WITH ASTM E 90. PENETRATIONS OR OPENINGS
 IN CONSTRUCTION ASSEMBLIES FOR PIPING; ELECTRICAL
 DEVICES; RECESSED CABINETS; BATHTUBS; SOFFITS; OR
 HEATING, VENTILATING OR EXHAUST DUCTS SHALL BE SEALED,
 LINED, INSULATED OR OTHERWISE TREATED TO MAINTAIN THE
 REQUIRED RATINGS. THIS REQUIREMENT SHALL NOT APPLY TO
 DWELLING UNIT ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL
 BE TIGHT FITTING TO THE FRAME AND SILL.
  
 16B) PROVIDE THE STC RATING FOR FLOORS TO ALL SLEEPING
 UNITS ABOVE THE FIRST FLOOR.1207.3
 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492.
  
 16C) ELEVATOR SHAFT WALL DESIGNATION MISSING, 5 STORIES
 REQUIES A 2 HR WALL RATING, 707.4
  
 16D) PLANS INDICATE THE USE OF AN ELEVATOR LOBBY THAT
 REQUIRES A 1HR FIRE RATING 707.14.1, DOOR SCHEDULE
 INDICATES A "C" RATING OF THIS DOOR.
 DOORS ARE RATED IN MINUTES AND HRS SEE TABLE
 715.3.MISSING DOOR HARDWARE SCHEDULE.
  
 16E)ELEVATOR MACHINE ROOM HAS A 2 HR RATING BUT THE
 DOOR SCHEDULE INDICATES "PER CODE" THIS TERMINOLOGY
 NEEDS TO BE REPLACED BY THE RATING IN TABLE 715.3.
  
 16F) ELEVATOR LOBBY # 130 SHOWS ELECTRIC MAGNET HOLD
 OPEN DEVICES WHERE AS E-204 IS MISSING THE HOLD OPEN
 DEVICES.
  
 16G) . THERE IS A MAKE UP AIR SHAFT NEXT TO STORAGE
 ROOM# 141, PLANS DO NOT INDICATE ANY WALL RATING,
 PLEASE PROVIDE. TABLE 707.4.
  
 16H) PLANS INDICATE A FIREEXTINGUISHER CABINET IN THE
 FIRE RATED WALL RECESSED. PROVIDE DETAIL INDICATING HOW
 THE FIRE RATING IS MAINTAINED. 707.4.
  
 16I) STAIR TOWER# 1 ALSO INDICATES WALL RATING "MISSING
 HOUR LABEL", 2HR FIRE RATING REQUIRED. SEE 707.4.
  
 16J) STAIR TOWER# 1 IS MISSING DOOR IDENTIFICATION TAG
 IN THE DOOR SCHEDULE, PLEASE SHOW RATING TABLE 715.3
 ,MISSING HARDWARE SCHEDULE.
  
 16K) STAIR TOWER# 1 NO DIMENSION IS PROVIDED AT THE
 DOOR,SHEET A-101 INDICATES A MO OF 3'-2" WHAT SIZE
 DOOR IS BEING INSTALLED? WHATWILL THE OCCUPANT LOAD
 BE FOR THIS DOORWAY? MISSING HARDWARE, TYPICAL.
  
 16L) COMMON TO ALL SLEEPING UNITS, DOOR 100 & 101 NO
 DOOR TO A SLEEPING UNIT ARE SHOWN ON THE DOOR SCHEDULE?
 PLEASE PROVIDE DOOR TYPE, DOOR WIDTH AND FIRE RATING.
 TABLE 715.3, 1008.1.1. MISSING HARDWARE SCHEDULE,
 TYPICAL.
  
 16M) STAIRWELLS ARE MISSING STANDPIPES,905.1 GENERAL.
 STANDPIPE SYSTEMS SHALL BE PROVIDED IN ALL NEW
 BUILDINGS IN WHICH:
 1.THE HIGHEST FLOOR IS GREATER THAN 30 FEET (9144
 MM) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE
 ACCESS; OR
 2.THE HIGHEST FLOOR IS MORE THAN THREE STORIES
 ABOVE GRADE.
  
 16N) PLEASE PROVIDE INFORMATION FOR ELEVATOR CARS TO
 ACCOMMODATE AMBULANCE STRETCHER.
 3002.4 ELEVATOR CAR TO ACCOMMODATE AMBULANCE
 STRETCHER.
  
 IN BUILDINGS FOUR STORIES IN HEIGHT OR MORE, AT LEAST
 ONE ELEVATOR SHALL BE PROVIDED FOR FIRE DEPARTMENT
 EMERGENCY ACCESS TO ALL FLOORS. SUCH ELEVATOR CAR SHALL
 BE OF SUCH A SIZE AND ARRANGEMENT TO ACCOMMODATE A
 24-INCH BY 76-INCH (610 MM BY 1930 MM) AMBULANCE
 STRETCHER IN THE HORIZONTAL, OPEN POSITION AND SHALL BE
 IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR EMERGENCY
 MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL SHALL NOT
 BE LESS THAN 3 INCHES (76 MM) HIGH AND SHALL BE PLACED
 INSIDE ON BOTH SIDES OF THE HOISTWAY DOOR FRAME.
  
 17) SHEET A-101:
 17A) PLANS INDICATES A DETAIL# 6 ON SHEET A-502, INDEX
 INDICATES SUCH A SHEET EXIST, PLANS ARE MISSING THIS
 DETAIL SHEET.
 ADDITIONAL COMMENTS MAY APPEAR ON THE NEXT REVIEW FOR
 THIS SECTION WITH NEW SUBMITTAL.
  
 17B) STAIRWELL# 2 IS MISSING THE STANDPIPE:
 905.1 GENERAL.
 STANDPIPE SYSTEMS SHALL BE PROVIDED IN ALL NEW
 BUILDINGS IN WHICH:
 1.THE HIGHEST FLOOR IS GREATER THAN 30 FEET (9144
 MM) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE
 ACCESS; OR
 2.THE HIGHEST FLOOR IS MORE THAN THREE STORIES
 ABOVE GRADE
  
 18)SHEET A-101 INDICATES A SECTION # 2 OF A-402 THIS
 IS THE 2ND THROUGH THE 5TH FLOOR, DETAIL (1) OF THIS
 SHEET IS THE FIRST FLOOR.
  
 18A) DETAIL A IS MISSING THE STORAGE ROOM 142, PLEASE
 IDENTIFY THE WALL RATING
 OF THE SHAFT LOCATED IN THIS ROOM AND ALL OTHER COMMON
 SHAFTS.106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 18B) DETAIL# 1 ALSO INDICATES THE LAUNDRY ROOM IS THE
 TERMINATION OF THE LAUNDRY CHUTE.
 707.13.4 TERMINATION ROOM.
 REFUSE AND LAUNDRY CHUTES SHALL DISCHARGE INTO AN
 ENCLOSED ROOM COMPLETELY SEPARATED FROM THE REMAINDER
 OF THE BUILDING BY CONSTRUCTION THAT HAS A
 FIRE-RESISTANCE RATING OF NOT LESS THAN 1 HOUR AND
 OPENINGS INTO THE TERMINATION ROOM SHALL BE PROTECTED
 BY OPENING PROTECTIVES HAVING A FIRE PROTECTION RATING
 OF NOT LESS THAN ? HOUR AND SHALL BE SELF-CLOSING OR
 AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE. REFUSE
 CHUTES SHALL NOT TERMINATE IN AN INCINERATOR ROOM.
 REFUSE AND LAUNDRY ROOMS THAT ARE NOT PROVIDED WITH
 CHUTES NEED ONLY COMPLY WITH TABLE 302.1.1 .NO DOOR
 HARDWARE SCHEDULE , TYPICAL.
  
 18C) THE DOOR SCHEDULE FOR DOOR# 124 COORIDOR TO
 LAUNDRY INDICATES A WINDOW WITH TEMPERED GLASS, FOR
 RATED DOORS SEE TABLE 715.4.3 FOR MAXIMUM SIZE OF
 WINDOW AND TYPE OF GLASS.
  
 18D) DETAIL# 22ND-5TH FLOOR LAUNDRY CHUTE AND LINEN
 STORAGE INDICATES THE LAUNDRY CHUTE WITHIN A LAUNDRY
 STORAGE ROOM,PROVIDE DETAILS ON THE LAUNDRY CHUTE
 ENCLOSURE, OPENINGS INTO THE SHAFT (DOOR) AND FIRE
 RATINGS OF LAUNDRY CHUTE DOOR.707.13.1.
  
 18E) PLEASE PROVIDE A SECTION THROUGH THE LAUNDRY CHUTE
 PROVIDING THE FOLLOWING:
 903.2.10.2 RUBBISH AND LINEN CHUTES.
 AN AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED AT THE
 TOP OF RUBBISH AND LINEN CHUTES AND IN THEIR TERMINAL
 ROOMS. CHUTES EXTENDING THROUGH THREE OR MORE FLOORS
 SHALL HAVE ADDITIONAL SPRINKLER HEADS INSTALLED WITHIN
 SUCH CHUTES AT ALTERNATE FLOORS. CHUTE SPRINKLERS SHALL
 BE ACCESSIBLE FOR SERVICING.
 PROVIDE DETAIL OF HOW SPRINKLERS WILL BE ACCESSIBLE IN
 THE 2 HR RATED SHAFT.
  
 18F) WATER HEATER ROOMS 2ND -5TH FLOOR ARE MISSING FROM
 THE DOOR SCHEDULE. PLEASE PROVIDE DOOR RATING,
 HARDWARE, ETC. TABLE 715,3.
  
 18G) FIRST FLOOR ELECTRICAL ROOM 153 IS ALSO MISSING
 WALL RATINGS SEE UTILITY OCCUPANCY RATING TABLE
 302.3.2.
  
 19) SHEET A-102:
 19A) DETAIL# 2/ 502, THE INDEX INDICATES SUCH A SHEET
 EXIST, PLANS ARE MISSING THIS SHET COMMON TO 2ND -5TH
 FLOOR.
 ADDITIONAL COMMENTS WILL APPEARON THE NEXT REVIEW FOR
 THIS SECTION WITH NEW SUBMITTAL.
  
 19B) DETAIL#2 /503,IS MISS LABELED, PLEASE CORRECT. THE
 INDEX INDICATES SUCH A SHEET EXIST, PLANS ARE MISSING
 THIS SHET COMMON TO 2ND -5TH FLOOR.
 ADDITIONAL COMMENTS WILL APPEARON THE NEXT REVIEW FOR
 THIS SECTION WITH NEW SUBMITTAL.
  
 19C) DETAIL#2 /504,IS MISS LABELED, PLEASE CORRECT. THE
 INDEX INDICATES SUCH A SHEET EXIST, PLANS ARE MISSING
 THIS SHET COMMON TO 2ND -5TH FLOOR.
 ADDITIONAL COMMENTS WILL APPEARON THE NEXT REVIEW FOR
 THIS SECTION WITH NEW SUBMITTAL.
  
 20) SHEET A-103:
 20A) SEE DETAIL 2/A-402, COMMON 2ND FL -5TH FLOOR,
 LAUNDRY CHUTE, THERE IS NO SHAFT WALL DESIGNATION FOR
 FIRE RATING, 707.2.
  
 20B)ROOMS 327 & 328 SHARE A SHFT WALL IN COMMON, THE
 SHAFT IS BUILT RIGHT INTO THE BATHROOM WALL, HOW WILL
 THE BACKING FOR SHOWER AND TUB BE INSTALLED?
  
 20C) DETAIL1/A-403 FIRST FLOOR LEVEL, INDICATES ROOM#
 114 TO THE MACHINE ROOM FOR ELEVATOR# 2, REQUIRING A 2
 HR RATING WITH 1 1/2 HR RATED DOOR. PLEASE CORRECT. THE
 WALL THE DOOR IS LOCATED IN DOESN'T EVEN HAVE A WALL
 IDENTIFICATION TAG.
  
 20D) DETAIL1/A-403 ELEVATOR MACHINE ROOMWALL
 IDENTIFICATION TAG SHOULD READ A 2HR FIRE RATING WITH 1
 1/2 HR OPENING PROTECTION.
  
 20E)ELEVATOR LOBBY TO HAVE 1HR FIRE RATING WITH
 OPENING PROTECTIVES OF 3/4 HR . 707.14.1 NOTE WILL
 THESE DOORS BE ON HOLD OPEN DEVICES? DOOR SHCEDULE
 INDICATES YES, ELECTRICAL SHEETS NO?
  
 20F) EXERCISE ROOM 1ST FL INDICATES THE USE OF A HOUSE
 PHONE PROVIDE MOUNTING HEIGTH WITHIN REACH RANGES.
 11-4.31.3.
  
 20G) EXERCISE ROOM DOOR 118 TO BE FIRE RATED IN HRS/
 MIN. TABLE 715.3SIZE OF WIRE PANEL?
  
 20H) ROOM# 116, 216, 316 THE ICE ROOM, FIRST FLOOR
 THERE IS NO SHAFT WALL AROUND THE
 MAKE UP AIR SHAFT, 2ND- 5TH FLOOR NO WALL TYPE
 IDENTIFICATION AROUND SHAFT WALL CONSTRUCTION.
  
 20I) 2ND - 5TH FLOORS SAME ISSUES, THE ELECTRICAL ROOM
 DOOR IS MISSING IDENTIFICATION TAG AND FIRE
 RATING.707.4.
  
 20I) STORAGEE ROOM 251 COMMON 2ND- 5TH FLOOR, THIS IS A
 RATED CORRIDOR TABLE 1016 WALL IDENTIFICATION TAG
 SHOULD INDICATE AS SUCH AND IN DOOR SCHEDULE. TABLE
 715.3.
  
 20K) STORAGE ROOM 318/ 418 STORAGE ROOM WALLS AS WELL
 AS THE MAINTENANCE ROOM518, 1 HR RATED, DOORS TTABLE
 TABLE 715.3.
  
 21) SHEET A-105,& A-503 PLANS CALL FOR ROOF ACCESS IN
 STORAGE ROOMS 541 & 542 TO GAIN ACCES FOR ROOF MOUNTED
 MECHANICAL EQUIPMENT. PLANS DO NOT PROVIDE HOW ONE
 GAINS ACCESS, IT IS ASSUMED BY A SHIPS LADDER. PLANS
 ALSO DO NOT PROVIDE A CUT SECTION OF THIS 5TH FLOOR
 CLOSET IN RELATION TO THE MECHANICAL WELL LOCATED AT
 THE ROOF LEVEL? WHAT DISTANCE OF TRAVEL THROUGH THE
 ATTIC AREA, LIGHTING NOR IDENTIFY THE DOOR THAT LEADS
 TO THE MECHANICAL WELL?
  
 DETAI# 1 /A-503 PROVIDES THE DEAIL BUT NO ACCESS IS
 PROVIDED FROM THE 5TH FLOOR.
  
 THIS ROOF TOP MECHANICAL WELL IS LOCATED ON A FLAT
 ROOFTOP DECK WHICH IS ALSO MORE THAN 4 STORIES ABOVE
 GRADE. SEE 1009.12 ACCESS TO ROOF.
  
 1009.12 ACCESS TO ROOF.
 BUILDINGS FOUR STORIES OR MORE IN HEIGHT, EXCEPT THOSE
 WITH A ROOF SLOPE GREATER THAN 4:12, SHALL BE PROVIDED
 WITH A STAIRWAY TO THE ROOF. SUCH STAIRWAY SHALL BE
 MARKED AT STREET AND FLOOR LEVELS WITH A SIGN
 INDICATING THAT IT CONTINUES TO THE ROOF. WHERE ROOFS
 ARE USED FOR ROOF GARDENS OR FOR OTHER PURPOSES,
 STAIRWAYS SHALL BE PROVIDED AS REQUIRED FOR SUCH USE OR
 OCCUPANCY.
 CODE COMMENTARY: IN BUILDINGS FOUR OR MORE STORIES
 HIGH, ROOF THAT ARE NOT USED FOR HABITABLE PURPOSES
 MUST BE MADE ACCESSIBLE BY CONVENTIONALSTAIRWAYS. TWO
 REASONS FOR THIS ARE ACCESS FOR ROOF OR EQUIPMENT
 REPAIR AND FIRE DEPARTMENT ACCESS DURING A FIRE EVENT.
  
 22) SHEET A-301 PLANS INDICATE THE USE OF CORRIGATED
 METAL DECK, DENSE DECK AND ICE & WATER SHIELD. THIS
 SECTION WAS TAKEN FROM THE ENTRY AREA FIRST FLOOR, IS
 THIS SAME ROOFING CONCEPT TO BE USED ON THE UPPER
 PORTION OF THE FIVE STORY BUILDING?
  
 23) SHEET A-301 ALSO INDICATES THE USE OF RIDGE VENTS,
 PLEASE PROVIDE DETAILS FOR FRAMING AT THE RIDGE AREA,
 AS WELL AS THE PRODUCT APPROVAL PROVIDING ATTACHMENT
 METHODS.
 SHEET A-504 DETAIL# 9 INDICATES A INSTALATION OF
 THE RIDGE WITHOUTA RIDGE VENT PLEASE TAKE NOTE OF
 CONCRETE TILE ATTACHMENT 1507.3.7 AND 1509.3.8
 APPLICATION BOTH REFRENCE FRSA/ RTI07320/ 4TH EDITION
 FOR THE INSTALLATION OF RIDGE AND HIP TILE. PLEASE
 CORRECT SECTION AND PROVIDE IF THE HIP/ RIDGE BACKER
 BOARD WILL BE METAL OR WOOD? PROVIDE THE CLIP SYSTEM TO
 BE USED, AND THE SIZE OF FASTENER FOR EACH.
  
 24) SHEET A-301ENLARGED SECTION DETAIL OF ROOF
 INDICATED A STEEL DECK DENSEGLASS AND ICE & WATER
 SHIELD UNDERLAYMENT, SHEET A-302DETAIL # 3INDICATES
 THE USE OF A
 (P540) U.L. LISTED ROOF/ CEILING ASSEMBLY. AS PART OF
 THIS SYSTEM PART # 5 INDICATES THE USE OF VARIOUS
 ROOFING INSULATIONS USED ABOVE THE STEEL DECK PLEASE
 CORRALATE AND CORRECT .
 THIS SAME DETAIL INDICATES THE USE OF FURRING CHANNELS
 AND 5/8" DRYWALL.
  
 25) SHEET A-303 DETAIL# 3 ALSO INDICATES THE USE OF UL
 LISTING P540 VERSES THE DETAIL 4/501WHERE NO
 INSULATION, NOR DENSEGLASS USED ABOVE THE STEEL ROOF
 DECK.
  
 26) SHEET A-501 GABLE END DETAIL INDICATES THE USE OF
 STEEL STUDS, NO INFORMATION AS TO SIZE, GAUGE, SPACING
 OFSTEEL STUDS. THE SAME DETAIL INDICATES THE USE OF
 PLYWOODSHEATHING BUT NOT THE WALL FINISH? 106.1.2.
 ADDITONAL INFOEMATION REQUIRED.S-309 INDICATES A
 DROPPED GABLE END FOR THE GABLES NO MENTION AS TO
 BRACING REQUIREMENTS
  
 27) A-702 SECTION# 1 PLEASE PROVIDE VENTING FOR
 ELEVATORS:
 3004.1 VENTS REQUIRED.
 HOISTWAYS OF ELEVATORS AND DUMBWAITERS PENETRATING MORE
 THAN THREE STORIES SHALL BE PROVIDED WITH A MEANS FOR
 VENTING SMOKE AND HOT GASES TO THE OUTER AIR IN CASE OF
 FIRE.
 3004.2 LOCATION OF VENTS.
 VENTS SHALL BE LOCATED BELOW THE FLOOR OR FLOORS AT THE
 TOP OF THE HOISTWAY, AND SHALL OPEN EITHER DIRECTLY TO
 THE OUTER AIR OR THROUGH NONCOMBUSTIBLE DUCTS TO THE
 OUTER AIR. NONCOMBUSTIBLE DUCTS SHALL BE PERMITTED TO
 PASS THROUGH THE ELEVATOR MACHINE ROOM PROVIDED THAT
 PORTIONS OF THE DUCTS LOCATED OUTSIDE THE HOISTWAY OR
 MACHINE ROOM ARE ENCLOSED BY CONSTRUCTION HAVING NOT
 LESS THAN THE FIRE PROTECTION RATING REQUIRED FOR THE
 HOISTWAY. HOLES IN THE MACHINE ROOM FLOORS FOR THE
 PASSAGE OF ROPES, CABLES OR OTHER MOVING ELEVATOR
 EQUIPMENT SHALL BE LIMITED SO AS NOT TO PROVIDE GREATER
 THAN 2 INCHES (51 MM) OF CLEARANCE ON ALL SIDES.
  
 28) A-702 PLANS DO NOT INDICATE REQUIREMEENTS FOR
 BRAILLE CHARACTERS AT HOISTWAY ENTRANCES. 11-4.10.5
 RAISED AND BRAILLE CHARACTERS ON HOISTWAY ENTRANCES.
 ALL ELEVATOR HOIST WAY ENTRANCES SHALL HAVE RAISED AND
 BRAILLE FLOOR DESIGNATIONS PROVIDED ON BOTH JAMBS. THE
 CENTERLINE OF THE CHARACTERS SHALL BE 60 INCHES (1525
 MM) ABOVE FINISH FLOOR. SUCH CHARACTERS SHALL BE 2
 INCHES (50 MM) HIGH AND SHALL COMPLY WITH SECTION
 11-4.30.4 . PERMANENTLY APPLIED PLATES ARE ACCEPTABLE
 IF THEY ARE PERMANENTLY FIXED TO THE JAMBS (SEE FIGURE
 11-20 ).
  
 29A) 1609.1.4 PROTECTION OF OPENINGS.
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND
 ASTM E 1996, OR MIAMI-DADE TAS 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 29B) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
 29C)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.]
  
 29D) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOW
 FIXED
 SINGLE HUNG
 MULLION
 B) GLAZED DOORS
 AUTOMATIC HORIZONTAL SLIDING DOORS
 EXTERIOR HOLLOW METAL DOORS
 C) LOUVERS
 D) PANEL WALL SYSTEMS
 SOFFITS- HARDI SOFFIT BOARD
 E) STRUCTURAL COMPONENTS- TRUSS ANCHORS
 F) ROOF ASSEMBLIES
 FLAT ROOFS- MODIFIED/ BITUMEN
 SLOPED:UNDERLAYMENTS, ROOF TILE ADHESIVES, ROOF
 TILE APPLICATIONS
  
 30) ASEPERATE PERMIT IS REQUIRED FOR THE POOL, POOL
 EQUIPMENT BUILDING , POOL FENCING AND SIGNAGE.
  
 31)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]