Plan Review Notes
Plan Review Notes For Permit 06111071
Permit Number 06111071
Review Stop E
Sequence Number 12
Notes
Date Text
2009-08-19 10:48:35** DENIED REVIEW **
  
 1) NOTE: REVISED ENERGY CALCULATIONS ARE NEEDED TO
 COORDINATE WITH THE REVISED SITE LIGHTING AND REVISED
 COMPONENTS OF BUILDING. AN EXAMPLE IS THE FIXTURE OC
 WAS REVISED FROM 400W TO 1000W.
 13-415.2.ABC.1.1,.1.2,.1.3
 ** THIS REVIEW SUPERCEDES PREVIOUS PASSED REVIEW ON
 SITE LIGHTING NOT DONE BY THIS REVIEWER.
  
 2) NOTE: THE TITLE BLOCK INDICATES THE REVISION AS
 DATED 20TH JULY 2007. WE ALREADY HAVE THIS REVISION AS
 NOTED IN TITLE BLOCK ON FILE. PLEASE REVISE REVISIONS,
 DATES, AND INDICATIONS ON PLANS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  