Plan Review Notes
Plan Review Notes For Permit 06111071
Permit Number 06111071
Review Stop M
Sequence Number 1
Notes
Date Text
2007-02-05 14:51:40-------------------DENIED-----------------
  
 1. PLEASE PROVIDE DETAIL SHOWING METHOD OF ATTACHMENT
 FOR ALL OUTDOOR EQUIPMENT, SUCH AS ROOFTOP UNITS
 (ROOF-TO-CURB AND CURB-TO-EQUIPMENT), DUCT SUPPORTS AND
 GROUND MOUNTED UNITS PER FBC,M 301.13. AN ENGINEERED
 SYSTEM IS REQUIRED TO MEET WIND LOAD REQUIREMENTS.
 NOTE: THE CITY OF WEST PALM BEACH IS IN THE 140MPH WIND
 ZONE. PLEASE INDICATE ON PLANS THE WIND ZONE FOR WHICH
 THE SYSTEM IS DESIGNED.
  
 2. EXHAUST FANS: APPLIANCES REQUIRING SERVICE ON A ROOF
 HAVING A SLOPE OF 3:12 (25%) OR GREATER WILL REQUIRE
 CATWALKS FOR ACCESS AND LEVEL SUPPORT PLATFORMS PER
 FBC,M 306.5 ? 306.6. THIS CONDITION EXISTS IN SEVERAL
 LOCATIONS AS SHOWN ON PAGE A-106.
  
 3. ROOFTOP UNIT DETAIL NOTE CITES IMC. PLEASE REFERENCE
 2004 FBC,M.
  
 4. ROOFTOP UNIT DETAIL SHOWS UNITS WITH DOWN DISCHARGE
 AND AN OPEN SPACE INSIDE THE CURB BEING USED FOR
 AIRFLOW. THE SUPPLY DUCT IS SHOWN ATTACKING TO THE CURB
 RATHER THAN TO THE UNIT. PLEASE CLARIFY.
  
 5. FIRE DAMPER DETAIL: FIRE DAMPERS SHALL MEET THE
 REQUIREMENTS OF UL 555 AND BE INSTALLED PER THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS AND THEIR
 LISTING PER FBC,M 607.2. A POTENTIAL CONFLICT CAN BE
 AVOIDED BY REMOVING THE CURRENT DETAIL AND REPLACING IT
 WITH A NOTE THAT THE DAMPERS ARE TO BE INSTALLED PER
 MANUFACTURER?S INSTALLATION INSTRUCTIONS. THESE
 INSTRUCTIONS SHOULD BE SUBMITTED (3 COPIES) WITH PLANS
 AS WELL AS BE MADE AVAILABLE IN THE FIELD FOR
 INSPECTION PURPOSES.
  
 6. HORIZONTAL FAN COIL UNIT DETAIL SHOWS SECONDARY
 DRAIN FROM AUXILIARY DRAIN PAN PIPED TO A CONDENSATE
 PUMP. A SECONDARY DRAIN OR AUXILIARY DRAIN PROTECTION
 IS TO BE INSTALLED PER THE REQUIREMENTS OF FBC,M
 307.2.3.
  
 7. VERTICAL FAN COIL UNIT DETAIL (IF USED) DOES NOT
 SHOW ANY SECONDARY DRAIN OR AUXILIARY DRAIN PROTECTION
 SYSTEM. PLEASE SHOW COMPLIANCE WITH FBC,M 307.2.3.
  
 8. M-101 KEY NOTES # 1 & 2: CONDENSATE DRAIN IS TO RUN
 ABOVE THE CEILING TO THE NEAREST DOWNSPOUT. SOME AREAS
 WHERE THIS IS NOTED DO NOT HAVE CEILINGS WHERE THIS
 DRAIN LINE CAN BE CONCEALED. PLEASE CLARIFY.
  
 9. M-101 SHOWS FCUS WITH DUCT SMOKE DETECTORS INSTALLED
 ON RETURN SIDE. DUCT SMOKE DETECTORS ARE TO BE LOCATED
 ON SUPPLY DUCTS PER FBC,M 606.2.1.
  
 10. PLEASE INDICATE ON PLAN TYPE OF MATERIAL TO BE USED
 FOR CONDENSATE DRAIN LINES. SEVERAL AREAS ABOVE CEILING
 ARE SHOWN TO BE PLENUMS AND ALL MATERIALS WITHIN
 PLENUMS MUST MEET THE REQUIREMENTS OF FBC,M 602.2.1.
  
 11. CONTAMINATION PREVENTION: EXHAUST DUCTS
 (BATH,DRYER) UNDER POSITIVE PRESSURE SHALL NOT EXTEND
 INTO OR PASS THROUGH DUCTS OR PLENUMS.
  
 12. PLEASE SEE ELECTRICAL PLAN REVIEW COMMENTS 2-4
 REGARDING ENGINEER/ARCHITECT STAMP, SIGNATURE AND TITLE
 BLOCK REQUIREMENTS.
  
  