| 2007-01-03 07:20:09 | *** UNSAT *** |
| | |
| | HOMEWOOD SUITES |
| | 5-STORY 114 UNITS. |
| | |
| | ** PLEASE SEE MANY OF THE NOTES WILL CONTAIN |
| | ABBREVIATIONS FOR REQUIRED ITEMS. |
| | PLEASE SEE SOME OF THE FOLLOWING WHICH WILL BE COMMON * |
| | ANY REFERENCE TO THE FBC CHAPTER 1, ARE SECTIONS TO THE |
| | ADMINISTRATIVE SECTION OF THE FBC 2004 AS ADOPTED BY |
| | THE CITY OF WEST PALM BEACH. |
| | * PLEASE SEE MANY REFERENCE TO THE FLORIDA STATUTES |
| | WILL BE DONE AS FS. |
| | * PLEASE SEE MANY REFERENCES TO THE FLORIDA |
| | ADMINISTRATIVE CODE WILL BE FAC. |
| | |
| | 1) NOTE: PLEASE KNOW AS THIS WILL BE A THRESHOLD |
| | PROJECT AND THREE SETS OF ALL PLANS DOCUMENTS SHALL BE |
| | SUBMITTED FOR REVIEW AND STAMPING. |
| | FBC ADMIN SECTIONS 109.3.6, 106.1.2 |
| | |
| | 2) NOTE: PLEASE SEE FS 471.025 AND FAC 61G15-23.002 AS |
| | ALL PLANS SHALL BEAR THE ORIGINAL AND LEGAL SIGNATURE |
| | FOR THE ENGINEER OF RECORD ON ALL DOCUMENTS. PLEASE SEE |
| | ONE SET OF PLANS SUBMITTED IN FACT CONTAIN A RAISED |
| | SEAL OVER A PHOTO-COPIED SIGNATURE AND DATE. PLEASE |
| | KNOW THE COMMENT IS FOR ALL MEP PLANS WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER TRADE(S). |
| | PLEASE ALSO KNOW ONE SET WILL BE RETAINED BY THIS |
| | OFFICE. |
| | |
| | 3) NOTE: PLEASE SEE MISSING TITLE BLOCKS ON ALL |
| | ENGINEERING SHEETS WHICH ARE REQUIRED PER FAC |
| | 61G15-23.002 AND FS 471.023 |
| | PLEASE ALSO SEE MISSING THE FOLLOWING. |
| | THE PRINTED NAME AND LICENSE NUMBER OF THE ENGINEER. |
| | THE CERTIFICATE OF AUTHORIZATION NUMBER/ALSO KNOWN AS |
| | THE ENGINEERING BUSINESS #. |
| | PLEASE KNOW THIS IS REQUIRED ON ALL SHEETS AND FOR ALL |
| | TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER |
| | TRADE(S). |
| | |
| | 4) NOTE: PLEASE SEE MISSING THE COMPLETE INFORMATION OF |
| | THE TITLE BLOCKS FOR THE ARCHITECTURAL FIRM. FAC |
| | 61G1-16.004, FS 481.219 |
| | PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER |
| | OF THE ARCHITECT. |
| | PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION |
| | NUMBER. THIS MAY ALSO BE KNOWN AS THE FIRM LICENSE |
| | NUMBER. |
| | THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. |
| | |
| | 5) NOTE: PLEASE SEE FBC ADMIN SECTION 109.3.6, |
| | 109.3.6.4.4 WHICH REQUIRES THE STATEMENT FOR THRESHOLD |
| | PROJECTS ON ALL ARCH AND ENG SHEETS. |
| | " TO THE BEST OF THE ARCHITECT'S /OR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER |
| | 633 OF THE FLORIDA STATUTES". |
| | THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON |
| | PLANS. |
| | |
| | 6) NOTE: PLEASE SEE THE MECHANICAL AND PLUMBING SHEETS |
| | WHICH ARE SEALED WITH A RAISED SEAL WHICH IS NO LONGER |
| | VALID FOR USE IN THE STATE OF FLORIDA. PLEASE SEE THE |
| | FAC 61G1-16.001 WHICH RULED IN FEBRUARY OF 2004 THAT |
| | ALL SEALS SHALL BEAR THE WORDING OF "LICENSE" AND THE |
| | PREVIOUS WORDING OF "CERTIFICATE" WOULD NO LONGER BE |
| | PERMITTED IN THE STATE OF FLORIDA. PLEASE KNOW AN |
| | EXTENSION WAS GRANTED TO THE DATE OF DECEMBER 31ST, |
| | 2005 HOWEVER ALL PLANS AFTER THIS DATE SHALL CONTAIN |
| | THE NEW WORDING OF LICENSE. PLEASE OBTAIN NEW SEAL. |
| | THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADE(S). |
| | |
| | 7) NOTE: PLEASE SEE THAT ONCE THE ADDRESS FOR SAID |
| | PROJECT IS FINALIZED; PLEASE BE SURE THE TITLE BLOCKS |
| | FOR ALL SHEETS CONTAIN THE CORRECT ADDRESS. |
| | PLEASE SEE A PRELIMINARY ADDRESS OF 2455 METROCENTRE |
| | BLVD IS CURRENTLY IN OUR SYSTEM FOR THE PCN/ PARCEL |
| | CONTROL NUMBER APPLIED WITH APPLICATION HOWEVER THIS |
| | ADDRESS MAY CHANGE AS DETERMINED BY THE ADDRESSING |
| | REVIEWER AND THE FIRE MARSHAL?S OFFICE. |
| | FAC 61G1-16.004, FAC 61G15-23.002 |
| | * THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES. |
| | |
| | 8) NOTE: PLEASE SEE ALL SEALS SHALL BE CLEAR AND |
| | VISIBLE WITH ALL INFORMATION ON SAID SEAL EASILY |
| | READABLE. PLEASE SEE FAC 61G15-23.001, AND 61G1-16.003 |
| | PLEASE SEE SOME SHEETS THE SEALS ARE NOT CLEAR EVEN IF |
| | SHADOWING WITH LEAD/DUST RUB. |
| | |
| | 9) NOTE: PLEASE KNOW AS THE PLANS SUBMITTED CONTAIN A |
| | POOL, PLEASE KNOW THIS WILL BE UNDER A SEPARATE PERMIT |
| | WITH PLANS, FEES AND PERMIT APPLICATION. |
| | PLEASE KNOW THAT ALL PLANS FOR THIS TYPE OF PUBLIC |
| | SWIMMING POOL WILL BE REQUIRED TO BE SUBMITTED TO THE |
| | PALM BEACH COUNTY HEALTH DEPARTMENT FOR ANY REVIEW OF |
| | COMPLETED PHOTO-METRICS FOR ANY AFTER DUSK SWIMMING. |
| | PLEASE ALSO SEE ANY PLUMBING REVIEW COMMENTS WHICH MAY |
| | ALSO REQUIRED THESE PLANS WHEN SUBMITTING FOR SEPARATE |
| | PERMIT TO ALSO BE STAMPED FOR REVIEW BY THE SAME. |
| | |
| | 10) NOTE: PLEASE SEE NO ENERGY CALCULATIONS PER FBC |
| | 2004 CHAPTER 13 WERE SUBMITTED FOR REVIEW. |
| | 13-415.1.AB.1 |
| | **PLEASE SEE THE 2004 FBC CHAPTER 13. |
| | **PLEASE SEE 13-413.1ABC.1 WHICH REQUIRES WORST CASE |
| | VOLTAGE DROP TO BE SHOWN ON PLANS FOR FEEDERS AND |
| | BRANCH CIRCUITS. THE NOTE FOR CONDUCTOR LENGTH INCREASE |
| | IS NOTED, HOWEVER PLEASE PROVIDE ABOVE AS REQUIRED. |
| | **PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE |
| | SEE A COMPLETE LIGHTING CONTROL SYSTEM AND/OR OTHER |
| | METHODS FOR AUTOMATIC LIGHTING CONTROLS ARE REQUIRED. |
| | PLEASE SEE AS NO SYSTEM OR DEVICES WERE SUBMITTED, |
| | REVIEW FOR CODE COMPLIANCE OF SUCH ITEMS COULD NOT BE |
| | DONE AT THIS TIME. |
| | ** PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR PERFORMANCE |
| | CALCULATIONS REQUIRED. |
| | ** PLEASE BE SURE WITH SYSTEM AND/OR DEVICE WHICH ARE |
| | GOING TO BE PART OF THE DESIGN SHALL CORRELATE WITH THE |
| | SYMBOL LEGEND. PLEASE BE SURE ALL OVER RIDE DEVICES |
| | STATE THE MAXIMUM OVER RIDE TIMES AS PERMITTED BY CODE. |
| | PLEASE SEE 30MINS MAXIMUM FOR OCCUPANCY TYPE AND 4HRS |
| | MAXIMUM FOR TIMER TYPE DEVICES. |
| | PLEASE SEE 13-415.1.ABC.1.4 AND 13-415.1.ABC.2 FOR |
| | EXTERIOR BUILDING LIGHTING ALLOWANCES. |
| | |
| | ** PLEASE SEE ALL OF FBC CHAPTER 13 AS ALL SECTIONS AS |
| | REQUIRED CAN NOT BY TYPED IN NOTES AS GIVEN. PLEASE SEE |
| | SOME OF THE KEY ITEMS AND SECTIONS HAVE BEEN GIVEN TO |
| | COMPLY. |
| | |
| | 11) NOTE: PLEASE SUBMIT WIND LOAD INFORMATION FOR ALL |
| | SITE LIGHTING. PLEASE SEE THE FBC IN THE WIND REGION IS |
| | 140 MPH 3 SECOND GUSTS. PLEASE KNOW THIS WILL BE |
| | REQUIRED TO BE STATED ON PLANS AND STRUCTURAL |
| | CALCULATIONS FOR ALL POLES WITH THE EPA (EFFECTIVE |
| | PROJECTED AREA) OF LIGHT FIXTURE WILL BE CONFIRMED |
| | BASED ON THE FIXTURES AS NOTED ON PLANS. |
| | |
| | 12) NOTE:PLEASE SEE THE BASE PLANS FOR THIS BUILDING |
| | SHALL CONTAIN THE COMPLETE FIRE SPRINKLER LAYOUT AND |
| | BASE FIRE ALARM SYSTEM PLEASE KNOW THAT BOTH OF THESE |
| | WILL STILL BE SUBMITTED FOR SEPARATE PERMITS PLANS AND |
| | FEES AT A LATER DATE ONCE THE BUILDING PERMIT IS |
| | ISSUED. |
| | FBC ADMIN SECTION 106.3.5.1.1 (5). |
| | |
| | 13) NOTE: PLEASE SEE FBC 2004 11-4.28.2, .3(4). PLEASE |
| | STATE ALL MINIMUM LEVELS AS REQUIRED FOR ALL AREAS. |
| | PLEASE KNOW IS NOTED THAT THE LEVELS FOR ACCESSIBLE |
| | UNITS ARE NOTED ON PLANS, HOWEVER THIS IS REQUIRED FOR |
| | ALL OTHER AREAS AS STATED IN 11-4.28.1 |
| | |
| | 14) NOTE: PLEASE SEE FIRE REVIEW COMMENTS AS THERE |
| | SEEMS FOR MANY LOCATIONS WHICH SMOKE DETECTORS ARE |
| | MISSING AND WILL BE REQUIRED. |
| | PLEASE SEE THESE WILL BE STATED BY FIRE REVIEW AND IS |
| | ONLY GIVEN AS A NOTE AT THIS TIME AS SOME AREAS WHICH |
| | DO NOT CONTAIN ANY NOTATION FOR THESE DEVICES WILL |
| | REQUIRE THESE.(PUMP ROOM) ETC |
| | PLEASE SEE NFPA-72 AND NFPA-101 AND FBC 905 |
| | |
| | 15) NOTE: PLEASE SEE SOME OF THE CODES REFLECTED ON |
| | PLANS ARE NO LONGER IN USE IN THE STATE OF FLORIDA. |
| | PLEASE SEE THE FOLLOWING CODES SHALL BE LISTED ON ALL |
| | PLANS AND ANY CODES RELEVANT TO THE SPECIFIC TRADES |
| | SHEETS SHALL BE STATED ON THOSE SHEETS. (ELECTRICAL) |
| | PLEASE LIST THE FOLLOWING AT A MINIMUM AS REQUIRED FOR |
| | ELECTRICAL REVIEW. |
| | 2002 NFPA-70 (NEC) STATED ON COVER SHEET HOWEVER SHOULD |
| | ALSO BE STATED ON E-TITLE SHEET. |
| | 2002-NFPA-72 NATIONAL FIRE ALARM CODE, 2003 NFPA-20 |
| | NATIONAL FIRE PUMP CODE, AND 2003 NFPA-101 LIFE SAFETY |
| | CODE. |
| | |
| | 16) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL |
| | EGRESS PATHS UNDER NORMAL LIGHTING LEVELS AND UNDER |
| | EMERGENCY LIGHTING LEVELS TO THE PUBLIC RIGHT OF WAY |
| | OUT AND AWAY FROM BUILDING. |
| | PLEASE SEE NFPA-101 7.8 AND 7.9. |
| | PLEASE ALSO SEE 7.8.1.3 AND 7.9.2.2 AS ALL STAIRS SHALL |
| | INDICATE THE 10FT CANDLES MINIMUM UNDER NORMAL AND THE |
| | ALLOWED DE-RATED LEVELS UNDER EMERGENCY CONDITIONS TO |
| | 1FT CANDLE. |
| | FBC 106.1.2 ADMIN SECTION. |
| | REVIEW FOR COMPLIANCE OF THIS CAN NOT BE DONE AT THIS |
| | TIME. |
| | |
| | 17) NOTE: PLEASE SEE NEC 620.22, 620.23 AND 620.24 FOR |
| | ALL THE REQUIRED DEDICATED BRANCH CIRCUITS FOR ELEVATOR |
| | EQUIPMENT ROOMS. PLEASE SEE 620.23 MORE SPECIFICALLY AS |
| | THE LIGHTING FOR ROOMS ARE ALSO BEING SHOWN CIRCUITED |
| | TO OTHER AREAS WHICH ARE NOT PERMITTED. |
| | |
| | 18) NOTE: PLEASE SEE PLANS INDICATE DISCONNECTS FOR THE |
| | ELEVATOR EQUIPMENT AS "ASSUMED" 400A MAINS? PLEASE |
| | EXPLAIN RATIONAL AND WHY THE SPECIFIC SIZE IS NOT IN |
| | DESIGN. |
| | PLEASE ALSO SEE BOTH ARE BEING NOTED TO MDP-1 WHICH |
| | DOES NOT INDICATE CIRCUITING. PLEASE SEE THE FOLLOWING |
| | COMMENT. |
| | FBC 106.1.2, NEC 408.4, 310.16 ETC |
| | |
| | 19) NOTE: PLEASE LIST THE CIRCUITING ON THE MDP WITH |
| | THE RESPECTIVE CIRCUITS AS WOULD BE LOCATED ON A PANEL |
| | SCHEDULE. PLEASE SEE THE CIRCUITING FOR OTHER PANELS |
| | SUBMITTED. |
| | 1,3,5,7,9 / 2,4,6,8, ETC. |
| | PLEASE SEE THE CIRCUITING ON PLANS FOR ALL OF THESE |
| | ITEMS SHALL CORRELATE. |
| | FBC 106.1.2, NEC, 408.4, 310.16, 240.4 ETC |
| | |
| | 20) NOTE: PLEASE SEE THAT ALL OF THE FOLLOWING ROOMS |
| | WILL BE REQUIRED TO CONTAIN AN EMERGENCY BATTERY BACK |
| | UP LIGHT OF SOME KIND. |
| | MAIN ELECTRICAL ROOM, FIRE PUMP ROOM, BOTH ELEVATOR |
| | CONTROL/MACHINE ROOMS. |
| | 90.4, LS 101 7.8, 7.9, 700.12E, 700.16. |
| | |
| | 21) NOTE: PLEASE KNOW THE REVIEW OF THE NOTE ON E-502 |
| | FOR WHICH STATES (THE ELECTRICAL DESIGN HAS TAKEN INTO |
| | ACCOUNT OF A 22K AIC RATING AND FOR THE ELECTRICAL |
| | CONTRACTOR TO VERIFY THE ACTUAL AVAILABLE FAULT CURRENT |
| | ETC) IS NOT PERMITTED TO THIS OFFICE FOR DESIGN ON |
| | PLANS. |
| | PLEASE KNOW IT IS THE RESPONSIBILITY OF THE DESIGN |
| | PROFESSIONAL TO OBTAIN THIS INFORMATION AHEAD OF TIME |
| | FROM THE LOCAL POWER SUPPLIER WHICH IS FLORIDA POWER |
| | AND LIGHT AND BE SURE THAT ALL INFORMATION ON THE PLANS |
| | FOR DESIGN MEETS OR EXCEEDS THE AVAILABLE FAULT CURRENT |
| | AT THE SERVICE. |
| | PLEASE SEE 110.9, 110.10, 240.12 ETC. |
| | PLEASE ALSO SEE THE NOTES WITH RESPECT TO THE FIRE PUMP |
| | CONTROLLER WHICH SHALL ALSO STATE THE MINIMUM RATINGS. |
| | |
| | 22) NOTE: PLEASE SUBMIT ALL MANUFACTURE SPEC/CUTS |
| | SHEETS FOR THE FIRE PUMP AND FIRE PUMP CONTROLLER. |
| | PLEASE SEE NO INFORMATION FOR LOCKED ROTOR CURRENT |
| | SETTING IS STATED ON PLANS BY NOTE OR ANY OTHER MEANS. |
| | PLEASE SEE AS NO INFORMATION WAS SUBMITTED OF EQUIPMENT |
| | AS STATED ABOVE REVIEW FOR NUMEROUS ITEMS FOR CODE |
| | COMPLIANCE CAN NOT BE DONE AT THIS TIME. |
| | PLEASE SEE NFPA-20 2003 CHAPTER 9 AND CHAPTER 10. |
| | PLEASE ALSO SEE NEC 695.4 |
| | ** PLEASE KNOW REFERENCES TO THE CHAPTERS ARE GIVEN AND |
| | NOT SPECIFIC SECTIONS AS THERE ARE TOO MANY TO LIST. |
| | DISCONNECTING MEANS, ISOLATION SWITCH, LOCKED ROTOR, |
| | ETC. |
| | PLEASE BE SURE EQUIPMENT SHEETS CONTAIN THE LISTING |
| | FROM A NRTL PER 695.10 AND NFPA-20 10.1.2.1. |
| | |
| | ** PLEASE KNOW DETERMINATION FOR WHETHER OR NOT ON-SITE |
| | GENERATOR BACK UP FOR THE FIRE PUMP HAS NOT YET BEEN |
| | CONFIRMED WITH THE FIRE MARSHAL'S OFFICE. |
| | PLEASE KNOW AS FLORIDA HAS BECOME PRONE TO HURRICANES |
| | AND TROPICAL STORMS ON MORE OF A SUBSTANTIAL TIME FRAME |
| | FROM YEARS PAST AND THE POWER NOT BEING AVAILABLE FOR |
| | THE FIRE PUMP IN AN EMERGENCY HAS BECOME A CONCERN OF |
| | THIS OFFICE AND THE FIRE MARSHAL'S OFFICE. PLEASE KNOW |
| | THIS MAY BE CONSIDERED AS REQUIRED PER 695.3, NFPA-20 |
| | 9.2.1.1 THAT A ON-SITE POWER MAY BE REQUIRED. PLEASE |
| | SEE THE NEXT COMMENT. |
| | |
| | 23) NOTE: PLEASE BE SURE TO PLACE NOTE(S) ON PLANS FOR |
| | ALL SIGNAGE REQUIRED FOR SERVICE LOCATIONS AND FIRE |
| | PUMP LOCATION. 230.2E |
| | PLEASE ALSO SEE 9.3.2.2.3.2 WHICH STATES A PLACARD |
| | SHALL BE PLACED ADJACENT TO THE FIRE PUMP CONTROLLER |
| | STATING THE LOCATION OF THIS DISCONNECTING MEANS AND |
| | THE LOCATION OF THE KEY (IF THE DISCONNECTING MEANS IS |
| | LOCKED). |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 24) NOTE: PLEASE SEE FIXTURE LEGEND SHALL STATE THE |
| | MINIMUM TIMES ON THE EMERGENCY AND EXIT LIGHTS AS |
| | REQUIRED PER LS 101 7.9.2.1 |
| | |
| | 25) NOTE: PLEASE SEE SOME DEVICES SHOWN ON PLANS COULD |
| | NOT BE LOCATED ON THE DEVICE SYMBOL LEGEND. PLEASE |
| | COMPLETE FOR REVIEW OF THESE ITEMS. |
| | FBC ADMIN SECTION 106.1.2, 106.3.5.1.2 |
| | |
| | 26) NOTE: PLEASE KNOW BASED ON THE REQUIREMENTS OF MANY |
| | OF THE REVIEW COMMENTS AND FBC CHAPTER 13, THE PLAN |
| | KEYNOTES WILL MOST LIKELY BE ADJUSTED. |
| | PLEASE BE SURE TO CORRELATE. |
| | |
| | 27) NOTE: PLEASE SEE E-301 KEYNOTE #7 WHICH HAS TO DO |
| | WITH THE LOCATION OF THE CONTROL FOR THE SPORTS COURT |
| | LIGHTS WHICH DEVICE COULD NOT BE LOCATED AND YET PLEASE |
| | SEE THE CIRCUITING AND NOTE ON E-601 #9 MENTIONS |
| | CONTROL AT FRONT DESK? |
| | PLEASE CORRELATE |
| | FBC 106.1.2 |
| | |
| | 28) NOTE: PLEASE LABEL THE TYPICAL FLOOR LIGHTING PLANS |
| | TO THE RESPECTIVE FLOORS. IE; 2, 3 ETC |
| | FBC 106.1.2 |
| | |
| | 29) NOTE: PLEASE SEE PANEL "L1C" IS BEING FED FROM |
| | "H1B" WITH A SINGLE POLE 20A BREAKER? |
| | PLEASE SEE THIS IS A 277/480V PANEL AND RISER SHOWS |
| | THROUGH A TRANSFORMER ETC. PLEASE ADJUST PLANS AND |
| | CORRELATE. |
| | REVIEW OF 240.21C, 450.3, 408.16 CAN NOT BE DONE AT |
| | THIS TIME. |
| | |
| | 30) NOTE: PLEASE SEE 210.60 WHICH REFERENCES TO 210.52 |
| | FOR ITEMS REQUIRED. |
| | PLEASE SEE THERE ARE SEVERAL ITEMS FOR THIS. |
| | |
| | 31) NOTE: PLEASE SEE MISSING THE SMALL APPLIANCE |
| | CIRCUITS AS REQUIRED PER 210.52B1, 210.11C1 AND 220.16 |
| | PLEASE KNOW THAT NO OTHER OUTLETS MAY BE FED FROM THESE |
| | CIRCUITS. |
| | |
| | 32) NOTE: PLEASE SEE 210.52B1 AS THERE ARE RECEPTACLES |
| | LOCATED IN THE KITCHEN/BREAKFAST/DINING AREAS WHICH ARE |
| | FED FROM THE LIGHTING CIRCUITS WHICH IS NOT PERMITTED. |
| | PLEASE SEE 210.11C1, 220.16 AS NOTED IN NOTE #31 |
| | |
| | 33) NOTE: PLEASE SEE MISSING RECEPTSPER 210.52 FOR |
| | 2FT OF WALL , KITCHEN AREA, KITCHEN WALL OVER 2FT, |
| | WITHIN 6FT OF DOORS ETC. |
| | PLEASE KNOW AS THE CODE DOES PERMIT THE SPACING FOR |
| | HOTEL/MOTELS AND GUEST SUITES TO BE SPACE FOR FURNITURE |
| | LAYOUTS, IT ALSO STILL REQUIRES THE SAME NUMBER OF |
| | RECEPTS WHICH WOULD BE REQUIRED IN A DWELLING TO BE |
| | INSTALLED. |
| | 210.60 |
| | |
| | 34) NOTE: PLEASE SEE AREAS WHICH SEEM TO BE COUNTER |
| | PENINSULAR AREAS OFF OF KITCHEN WHICH SOME SHOW RECEPTS |
| | AND SOME DO NOT? |
| | PLEASE SEE 210.52C3 |
| | |
| | 35) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING |
| | KITCHEN COUNTER SPACES AND THE LIKE SHALL BE GFI/GFI |
| | PROTECTED. |
| | |
| | 36) NOTE: PLEASE CLARIFY THE ARC FAULT PROTECTION ONLY |
| | BEING SHOWN ON ONE CIRCUIT IN SLEEPING ROOMS? 210.12 |
| | |
| | 37) NOTE: PLEASE COMPLETE ALL PANEL BOARDS WITH THE |
| | CONDUCTOR SIZES FOR ALL BRANCH CIRCUITS. |
| | PLEASE SEE 310.16, 240.4, FBC 106.1.2, 106.3.5.1.2 |
| | REVIEW FOR CONDUCTORS CAN NOT BE DONE AT THIS TIME. |
| | |
| | 38) NOTE: PLEASE SUBMIT AND SHOW A COMPLETE GROUNDING |
| | ELECTRODE RISER UP THROUGH THE BUILDING. PLEASE SEE |
| | 250.58, 250.66 |
| | MAY BE PLACED ON RISER SHEET. |
| | |
| | 39) NOTE: PLEASE SHOW THE ATTACHMENT LOCATION FOR EACH |
| | TRANSFORMER PER 250.66, 250.30, 250.50 |
| | |
| | 40) NOTE: PLEASE SUBMIT A COMPLETED GROUNDING ELECTRODE |
| | SYSTEM. PLEASE SEE PLANS DID NOT SHOW ANY AS REQUIRED |
| | PER 250.50. |
| | PLEASE ALSO SEE 250.104 FOR ANY WATER AND OTHER TYPES |
| | OF METAL PIPING. (SPRINKLER ETC) |
| | |
| | 41) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEM |
| | AT DETACHED BUILDINGS/STRUCTURES PER 250.32 |
| | |
| | |
| | |
| | 42) NOTE: PLEASE SEE MISSING PANEL SCHEDULE FOR PANEL |
| | "P". |
| | PLEASE SUBMIT AND COMPLETE EVEN FOR FUTURE LOAD ETC. |
| | THE MDP DOES LIST THE PANEL, YET LOADS CAN NOT BE |
| | VERIFIED FOR PANEL SCHEDULE. |
| | CONTINUOUS LOADS ETC. |
| | 220, 215.3, 230.42. |
| | FBC 106.1.2 |
| | |
| | 43) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS AND |
| | SUMMARY FOR ALL LOADS AND SHOW ALL CONTINUOUS/LARGEST |
| | MOTOR LOADS AT 125%. |
| | 220.3,220.10,220.11,220.13, 230.42, 215.3 ETC. |
| | |
| | 44) NOTE: PLEASE SEE PANEL "L1B" WHICH IS BEING FED |
| | FROM A 400A BREAKER ON #2 AWG AT THE MDP. |
| | PLEASE SEE 240.4, 310.16, 450.3 ETC. |
| | |
| | 45) NOTE: PLEASE SEE 240.13 AND 230.95 AS THE MAIN IS |
| | BEING SHOWN WITH GFI PROTECTION WHICH IS THAT FOR |
| | PERSONNEL PROTECTION AND CODE REQUIRES GFP (GROUND |
| | FAULT PROTECTION WHICH IS NOT THE SAME. PLEASE ADJUST. |
| | |
| | 46) NOTE: PLEASE SEE POOL AREA LIGHTS ARE BEING SHOWN |
| | FED FROM AT 277V ?? |
| | PLEASE SEE SOME ARE SHOWN ON SITE PLANS HOWEVER ACTUAL |
| | DISTANCES COULD NOT BE SCALED. PLEASE PLACE NOTE ON |
| | PLANS, OR SHOW DISTANCES. |
| | FBC 106.1.2, NEC 680.22 |
| | |
| | 47) NOTE: PLEASE SEE MISSING NEUTRAL CONDUCTOR TO THE |
| | FIRE PUMP/FIRST MEANS OF DISCONNECT. PLEASE SEE |
| | 250.24B, 250.24, 250.6. EVEN AS A MOTOR LOAD, THIS IS |
| | REQUIRED. |
| | PLEASE SEE AS NOTED, (250.6) NO EQUIPMENT GROUNDING |
| | CONDUCTOR IS INSTALLED BEFORE THE FIRST MEANS OF |
| | DISCONNECT. |
| | THIS WOULD CREATE OBJECTIONABLE CURRENTS. |
| | |
| | 48) NOTE: PLEASE PROVIDE INFORMATION FOR KEY CARD |
| | ACCESS CONTROL SYSTEM. PLEASE SEE NFPA-1017 7.2.1, |
| | 7.1.9, 7.2.1.5 WHICH REQUIRES THAT ANY ACCESS CONTROL |
| | OR DOOR LOCK SYSTEM NOT TO IMPEDED EGRESS IN ANY |
| | FASHION UNDER NORMAL OR EMERGENCY CONDITIONS. PLEASE |
| | ALSO SEE FIRE REVIEW'S POSSIBLE COMMENTS. |
| | |
| | 49) NOTE: PLEASE SEE NFPA-72 11.8.3 WHICH REQUIRES |
| | LOCATIONS OF SMOKE DETECTORS TO BE INSTALLED WITH |
| | MINIMUM CRITERIA. PLEASE SEE AREAS WHERE THERE ARE |
| | SLOPED CEILINGS AS SHOWN ON THE ARCHITECTURAL SHEETS, |
| | THE SD SHALL BE INSTALLED WITHIN 3FT OF THE PEAK OF |
| | THAT SLOPE. (LOUNGE) ETC. PLEASE NOTE THE REQUIREMENTS |
| | AS LISTED. (3FT FROM BATH ROOM AND KITCHEN |
| | DOORS/OPENINGS ETC. PLANS DO ALREADY CONTAIN A NOTE FOR |
| | THE SMOKE DEVICE BEING PHOTO-ELECTRIC IN SOME AREAS. |
| | THIS COMMENT MAYBE EXPANDED UPON. |
| | PLEASE SE PREVIOUS NOTE WITH RESPECT TO LOCATION |
| | MISSING WHICH WILL REQUIRE ADDITIONAL. |
| | |
| | 50) NOTE: PLEASE CLARIFY THE DISCONNECTING MEANS AND |
| | GROUNDING AT THE DETACHED STORAGE/DUMPSTER BUILDING. |
| | 250.31-225.39 AND 250.32 AS PREVIOUSLY NOTED FOR THE |
| | POOL HOUSE BUILDING. |
| | |
| | *** PLEASE KNOW AS THERE ARE MANY ITEMS NOT SUBMITTED |
| | FOR REVIEW, PLANS NOT DESIGNED TO FBC CHAPTER 13 ETC, |
| | THERE MAY BE FUTURE REVIEW COMMENTS ON THE FOLLOW UP |
| | REVIEW. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-01-03 06:52:21 | 2007-01-03 06:52:21 |
| | NOTES IN PROGRESS |
| 2007-01-02 21:02:38 | 2007-01-02 21:02:38 |
| | REVIEW STOPPED, NOTES TO FOLLOW. |
| 2007-01-02 07:13:43 | 2007-01-02 07:13:43 |
| | REVIEW IN PROGRESS |
| 2007-01-01 16:03:37 | 2007-01-01 16:03:37 |
| | REVIEW STOPPED, REVIEW WILL GO INTO A "F" STATUS. |
| | REVIEW NOTES TO FOLLOW ONCE REVIEW IS COMPLETED. |
| 2007-01-01 15:28:40 | 2007-01-01 15:28:40 |
| | IN ELEC FOR REVIEW, REVIEW IN PROGRESS. |