Plan Review Notes
Plan Review Notes For Permit 06111071
Permit Number 06111071
Review Stop E
Sequence Number 1
Notes
Date Text
2007-01-03 07:20:09*** UNSAT ***
  
 HOMEWOOD SUITES
 5-STORY 114 UNITS.
  
 ** PLEASE SEE MANY OF THE NOTES WILL CONTAIN
 ABBREVIATIONS FOR REQUIRED ITEMS.
 PLEASE SEE SOME OF THE FOLLOWING WHICH WILL BE COMMON *
 ANY REFERENCE TO THE FBC CHAPTER 1, ARE SECTIONS TO THE
 ADMINISTRATIVE SECTION OF THE FBC 2004 AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
 * PLEASE SEE MANY REFERENCE TO THE FLORIDA STATUTES
 WILL BE DONE AS FS.
 * PLEASE SEE MANY REFERENCES TO THE FLORIDA
 ADMINISTRATIVE CODE WILL BE FAC.
  
 1) NOTE: PLEASE KNOW AS THIS WILL BE A THRESHOLD
 PROJECT AND THREE SETS OF ALL PLANS DOCUMENTS SHALL BE
 SUBMITTED FOR REVIEW AND STAMPING.
 FBC ADMIN SECTIONS 109.3.6, 106.1.2
  
 2) NOTE: PLEASE SEE FS 471.025 AND FAC 61G15-23.002 AS
 ALL PLANS SHALL BEAR THE ORIGINAL AND LEGAL SIGNATURE
 FOR THE ENGINEER OF RECORD ON ALL DOCUMENTS. PLEASE SEE
 ONE SET OF PLANS SUBMITTED IN FACT CONTAIN A RAISED
 SEAL OVER A PHOTO-COPIED SIGNATURE AND DATE. PLEASE
 KNOW THE COMMENT IS FOR ALL MEP PLANS WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADE(S).
 PLEASE ALSO KNOW ONE SET WILL BE RETAINED BY THIS
 OFFICE.
  
 3) NOTE: PLEASE SEE MISSING TITLE BLOCKS ON ALL
 ENGINEERING SHEETS WHICH ARE REQUIRED PER FAC
 61G15-23.002 AND FS 471.023
 PLEASE ALSO SEE MISSING THE FOLLOWING.
 THE PRINTED NAME AND LICENSE NUMBER OF THE ENGINEER.
 THE CERTIFICATE OF AUTHORIZATION NUMBER/ALSO KNOWN AS
 THE ENGINEERING BUSINESS #.
 PLEASE KNOW THIS IS REQUIRED ON ALL SHEETS AND FOR ALL
 TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADE(S).
  
 4) NOTE: PLEASE SEE MISSING THE COMPLETE INFORMATION OF
 THE TITLE BLOCKS FOR THE ARCHITECTURAL FIRM. FAC
 61G1-16.004, FS 481.219
 PLEASE SEE MISSING THE PRINTED NAME AND LICENSE NUMBER
 OF THE ARCHITECT.
 PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER. THIS MAY ALSO BE KNOWN AS THE FIRM LICENSE
 NUMBER.
 THIS IS REQUIRED ON ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES.
  
 5) NOTE: PLEASE SEE FBC ADMIN SECTION 109.3.6,
 109.3.6.4.4 WHICH REQUIRES THE STATEMENT FOR THRESHOLD
 PROJECTS ON ALL ARCH AND ENG SHEETS.
 " TO THE BEST OF THE ARCHITECT'S /OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND CHAPTER
 633 OF THE FLORIDA STATUTES".
 THIS IS REQUIRED FOR EACH DESIGN PROFESSIONAL ON
 PLANS.
  
 6) NOTE: PLEASE SEE THE MECHANICAL AND PLUMBING SHEETS
 WHICH ARE SEALED WITH A RAISED SEAL WHICH IS NO LONGER
 VALID FOR USE IN THE STATE OF FLORIDA. PLEASE SEE THE
 FAC 61G1-16.001 WHICH RULED IN FEBRUARY OF 2004 THAT
 ALL SEALS SHALL BEAR THE WORDING OF "LICENSE" AND THE
 PREVIOUS WORDING OF "CERTIFICATE" WOULD NO LONGER BE
 PERMITTED IN THE STATE OF FLORIDA. PLEASE KNOW AN
 EXTENSION WAS GRANTED TO THE DATE OF DECEMBER 31ST,
 2005 HOWEVER ALL PLANS AFTER THIS DATE SHALL CONTAIN
 THE NEW WORDING OF LICENSE. PLEASE OBTAIN NEW SEAL.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADE(S).
  
 7) NOTE: PLEASE SEE THAT ONCE THE ADDRESS FOR SAID
 PROJECT IS FINALIZED; PLEASE BE SURE THE TITLE BLOCKS
 FOR ALL SHEETS CONTAIN THE CORRECT ADDRESS.
 PLEASE SEE A PRELIMINARY ADDRESS OF 2455 METROCENTRE
 BLVD IS CURRENTLY IN OUR SYSTEM FOR THE PCN/ PARCEL
 CONTROL NUMBER APPLIED WITH APPLICATION HOWEVER THIS
 ADDRESS MAY CHANGE AS DETERMINED BY THE ADDRESSING
 REVIEWER AND THE FIRE MARSHAL?S OFFICE.
 FAC 61G1-16.004, FAC 61G15-23.002
 * THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES.
  
 8) NOTE: PLEASE SEE ALL SEALS SHALL BE CLEAR AND
 VISIBLE WITH ALL INFORMATION ON SAID SEAL EASILY
 READABLE. PLEASE SEE FAC 61G15-23.001, AND 61G1-16.003
 PLEASE SEE SOME SHEETS THE SEALS ARE NOT CLEAR EVEN IF
 SHADOWING WITH LEAD/DUST RUB.
  
 9) NOTE: PLEASE KNOW AS THE PLANS SUBMITTED CONTAIN A
 POOL, PLEASE KNOW THIS WILL BE UNDER A SEPARATE PERMIT
 WITH PLANS, FEES AND PERMIT APPLICATION.
 PLEASE KNOW THAT ALL PLANS FOR THIS TYPE OF PUBLIC
 SWIMMING POOL WILL BE REQUIRED TO BE SUBMITTED TO THE
 PALM BEACH COUNTY HEALTH DEPARTMENT FOR ANY REVIEW OF
 COMPLETED PHOTO-METRICS FOR ANY AFTER DUSK SWIMMING.
 PLEASE ALSO SEE ANY PLUMBING REVIEW COMMENTS WHICH MAY
 ALSO REQUIRED THESE PLANS WHEN SUBMITTING FOR SEPARATE
 PERMIT TO ALSO BE STAMPED FOR REVIEW BY THE SAME.
  
 10) NOTE: PLEASE SEE NO ENERGY CALCULATIONS PER FBC
 2004 CHAPTER 13 WERE SUBMITTED FOR REVIEW.
 13-415.1.AB.1
 **PLEASE SEE THE 2004 FBC CHAPTER 13.
 **PLEASE SEE 13-413.1ABC.1 WHICH REQUIRES WORST CASE
 VOLTAGE DROP TO BE SHOWN ON PLANS FOR FEEDERS AND
 BRANCH CIRCUITS. THE NOTE FOR CONDUCTOR LENGTH INCREASE
 IS NOTED, HOWEVER PLEASE PROVIDE ABOVE AS REQUIRED.
 **PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE
 SEE A COMPLETE LIGHTING CONTROL SYSTEM AND/OR OTHER
 METHODS FOR AUTOMATIC LIGHTING CONTROLS ARE REQUIRED.
 PLEASE SEE AS NO SYSTEM OR DEVICES WERE SUBMITTED,
 REVIEW FOR CODE COMPLIANCE OF SUCH ITEMS COULD NOT BE
 DONE AT THIS TIME.
 ** PLEASE SEE 13-415.2, 13-415.2.ABC.1 FOR PERFORMANCE
 CALCULATIONS REQUIRED.
 ** PLEASE BE SURE WITH SYSTEM AND/OR DEVICE WHICH ARE
 GOING TO BE PART OF THE DESIGN SHALL CORRELATE WITH THE
 SYMBOL LEGEND. PLEASE BE SURE ALL OVER RIDE DEVICES
 STATE THE MAXIMUM OVER RIDE TIMES AS PERMITTED BY CODE.
 PLEASE SEE 30MINS MAXIMUM FOR OCCUPANCY TYPE AND 4HRS
 MAXIMUM FOR TIMER TYPE DEVICES.
 PLEASE SEE 13-415.1.ABC.1.4 AND 13-415.1.ABC.2 FOR
 EXTERIOR BUILDING LIGHTING ALLOWANCES.
  
 ** PLEASE SEE ALL OF FBC CHAPTER 13 AS ALL SECTIONS AS
 REQUIRED CAN NOT BY TYPED IN NOTES AS GIVEN. PLEASE SEE
 SOME OF THE KEY ITEMS AND SECTIONS HAVE BEEN GIVEN TO
 COMPLY.
  
 11) NOTE: PLEASE SUBMIT WIND LOAD INFORMATION FOR ALL
 SITE LIGHTING. PLEASE SEE THE FBC IN THE WIND REGION IS
 140 MPH 3 SECOND GUSTS. PLEASE KNOW THIS WILL BE
 REQUIRED TO BE STATED ON PLANS AND STRUCTURAL
 CALCULATIONS FOR ALL POLES WITH THE EPA (EFFECTIVE
 PROJECTED AREA) OF LIGHT FIXTURE WILL BE CONFIRMED
 BASED ON THE FIXTURES AS NOTED ON PLANS.
  
 12) NOTE:PLEASE SEE THE BASE PLANS FOR THIS BUILDING
 SHALL CONTAIN THE COMPLETE FIRE SPRINKLER LAYOUT AND
 BASE FIRE ALARM SYSTEM PLEASE KNOW THAT BOTH OF THESE
 WILL STILL BE SUBMITTED FOR SEPARATE PERMITS PLANS AND
 FEES AT A LATER DATE ONCE THE BUILDING PERMIT IS
 ISSUED.
 FBC ADMIN SECTION 106.3.5.1.1 (5).
  
 13) NOTE: PLEASE SEE FBC 2004 11-4.28.2, .3(4). PLEASE
 STATE ALL MINIMUM LEVELS AS REQUIRED FOR ALL AREAS.
 PLEASE KNOW IS NOTED THAT THE LEVELS FOR ACCESSIBLE
 UNITS ARE NOTED ON PLANS, HOWEVER THIS IS REQUIRED FOR
 ALL OTHER AREAS AS STATED IN 11-4.28.1
  
 14) NOTE: PLEASE SEE FIRE REVIEW COMMENTS AS THERE
 SEEMS FOR MANY LOCATIONS WHICH SMOKE DETECTORS ARE
 MISSING AND WILL BE REQUIRED.
 PLEASE SEE THESE WILL BE STATED BY FIRE REVIEW AND IS
 ONLY GIVEN AS A NOTE AT THIS TIME AS SOME AREAS WHICH
 DO NOT CONTAIN ANY NOTATION FOR THESE DEVICES WILL
 REQUIRE THESE.(PUMP ROOM) ETC
 PLEASE SEE NFPA-72 AND NFPA-101 AND FBC 905
  
 15) NOTE: PLEASE SEE SOME OF THE CODES REFLECTED ON
 PLANS ARE NO LONGER IN USE IN THE STATE OF FLORIDA.
 PLEASE SEE THE FOLLOWING CODES SHALL BE LISTED ON ALL
 PLANS AND ANY CODES RELEVANT TO THE SPECIFIC TRADES
 SHEETS SHALL BE STATED ON THOSE SHEETS. (ELECTRICAL)
 PLEASE LIST THE FOLLOWING AT A MINIMUM AS REQUIRED FOR
 ELECTRICAL REVIEW.
 2002 NFPA-70 (NEC) STATED ON COVER SHEET HOWEVER SHOULD
 ALSO BE STATED ON E-TITLE SHEET.
 2002-NFPA-72 NATIONAL FIRE ALARM CODE, 2003 NFPA-20
 NATIONAL FIRE PUMP CODE, AND 2003 NFPA-101 LIFE SAFETY
 CODE.
  
 16) NOTE: PLEASE SUBMIT COMPLETE PHOTO-METRICS FOR ALL
 EGRESS PATHS UNDER NORMAL LIGHTING LEVELS AND UNDER
 EMERGENCY LIGHTING LEVELS TO THE PUBLIC RIGHT OF WAY
 OUT AND AWAY FROM BUILDING.
 PLEASE SEE NFPA-101 7.8 AND 7.9.
 PLEASE ALSO SEE 7.8.1.3 AND 7.9.2.2 AS ALL STAIRS SHALL
 INDICATE THE 10FT CANDLES MINIMUM UNDER NORMAL AND THE
 ALLOWED DE-RATED LEVELS UNDER EMERGENCY CONDITIONS TO
 1FT CANDLE.
 FBC 106.1.2 ADMIN SECTION.
 REVIEW FOR COMPLIANCE OF THIS CAN NOT BE DONE AT THIS
 TIME.
  
 17) NOTE: PLEASE SEE NEC 620.22, 620.23 AND 620.24 FOR
 ALL THE REQUIRED DEDICATED BRANCH CIRCUITS FOR ELEVATOR
 EQUIPMENT ROOMS. PLEASE SEE 620.23 MORE SPECIFICALLY AS
 THE LIGHTING FOR ROOMS ARE ALSO BEING SHOWN CIRCUITED
 TO OTHER AREAS WHICH ARE NOT PERMITTED.
  
 18) NOTE: PLEASE SEE PLANS INDICATE DISCONNECTS FOR THE
 ELEVATOR EQUIPMENT AS "ASSUMED" 400A MAINS? PLEASE
 EXPLAIN RATIONAL AND WHY THE SPECIFIC SIZE IS NOT IN
 DESIGN.
 PLEASE ALSO SEE BOTH ARE BEING NOTED TO MDP-1 WHICH
 DOES NOT INDICATE CIRCUITING. PLEASE SEE THE FOLLOWING
 COMMENT.
 FBC 106.1.2, NEC 408.4, 310.16 ETC
  
 19) NOTE: PLEASE LIST THE CIRCUITING ON THE MDP WITH
 THE RESPECTIVE CIRCUITS AS WOULD BE LOCATED ON A PANEL
 SCHEDULE. PLEASE SEE THE CIRCUITING FOR OTHER PANELS
 SUBMITTED.
 1,3,5,7,9 / 2,4,6,8, ETC.
 PLEASE SEE THE CIRCUITING ON PLANS FOR ALL OF THESE
 ITEMS SHALL CORRELATE.
 FBC 106.1.2, NEC, 408.4, 310.16, 240.4 ETC
  
 20) NOTE: PLEASE SEE THAT ALL OF THE FOLLOWING ROOMS
 WILL BE REQUIRED TO CONTAIN AN EMERGENCY BATTERY BACK
 UP LIGHT OF SOME KIND.
 MAIN ELECTRICAL ROOM, FIRE PUMP ROOM, BOTH ELEVATOR
 CONTROL/MACHINE ROOMS.
 90.4, LS 101 7.8, 7.9, 700.12E, 700.16.
  
 21) NOTE: PLEASE KNOW THE REVIEW OF THE NOTE ON E-502
 FOR WHICH STATES (THE ELECTRICAL DESIGN HAS TAKEN INTO
 ACCOUNT OF A 22K AIC RATING AND FOR THE ELECTRICAL
 CONTRACTOR TO VERIFY THE ACTUAL AVAILABLE FAULT CURRENT
 ETC) IS NOT PERMITTED TO THIS OFFICE FOR DESIGN ON
 PLANS.
 PLEASE KNOW IT IS THE RESPONSIBILITY OF THE DESIGN
 PROFESSIONAL TO OBTAIN THIS INFORMATION AHEAD OF TIME
 FROM THE LOCAL POWER SUPPLIER WHICH IS FLORIDA POWER
 AND LIGHT AND BE SURE THAT ALL INFORMATION ON THE PLANS
 FOR DESIGN MEETS OR EXCEEDS THE AVAILABLE FAULT CURRENT
 AT THE SERVICE.
 PLEASE SEE 110.9, 110.10, 240.12 ETC.
 PLEASE ALSO SEE THE NOTES WITH RESPECT TO THE FIRE PUMP
 CONTROLLER WHICH SHALL ALSO STATE THE MINIMUM RATINGS.
  
 22) NOTE: PLEASE SUBMIT ALL MANUFACTURE SPEC/CUTS
 SHEETS FOR THE FIRE PUMP AND FIRE PUMP CONTROLLER.
 PLEASE SEE NO INFORMATION FOR LOCKED ROTOR CURRENT
 SETTING IS STATED ON PLANS BY NOTE OR ANY OTHER MEANS.
 PLEASE SEE AS NO INFORMATION WAS SUBMITTED OF EQUIPMENT
 AS STATED ABOVE REVIEW FOR NUMEROUS ITEMS FOR CODE
 COMPLIANCE CAN NOT BE DONE AT THIS TIME.
 PLEASE SEE NFPA-20 2003 CHAPTER 9 AND CHAPTER 10.
 PLEASE ALSO SEE NEC 695.4
 ** PLEASE KNOW REFERENCES TO THE CHAPTERS ARE GIVEN AND
 NOT SPECIFIC SECTIONS AS THERE ARE TOO MANY TO LIST.
 DISCONNECTING MEANS, ISOLATION SWITCH, LOCKED ROTOR,
 ETC.
 PLEASE BE SURE EQUIPMENT SHEETS CONTAIN THE LISTING
 FROM A NRTL PER 695.10 AND NFPA-20 10.1.2.1.
  
 ** PLEASE KNOW DETERMINATION FOR WHETHER OR NOT ON-SITE
 GENERATOR BACK UP FOR THE FIRE PUMP HAS NOT YET BEEN
 CONFIRMED WITH THE FIRE MARSHAL'S OFFICE.
 PLEASE KNOW AS FLORIDA HAS BECOME PRONE TO HURRICANES
 AND TROPICAL STORMS ON MORE OF A SUBSTANTIAL TIME FRAME
 FROM YEARS PAST AND THE POWER NOT BEING AVAILABLE FOR
 THE FIRE PUMP IN AN EMERGENCY HAS BECOME A CONCERN OF
 THIS OFFICE AND THE FIRE MARSHAL'S OFFICE. PLEASE KNOW
 THIS MAY BE CONSIDERED AS REQUIRED PER 695.3, NFPA-20
 9.2.1.1 THAT A ON-SITE POWER MAY BE REQUIRED. PLEASE
 SEE THE NEXT COMMENT.
  
 23) NOTE: PLEASE BE SURE TO PLACE NOTE(S) ON PLANS FOR
 ALL SIGNAGE REQUIRED FOR SERVICE LOCATIONS AND FIRE
 PUMP LOCATION. 230.2E
 PLEASE ALSO SEE 9.3.2.2.3.2 WHICH STATES A PLACARD
 SHALL BE PLACED ADJACENT TO THE FIRE PUMP CONTROLLER
 STATING THE LOCATION OF THIS DISCONNECTING MEANS AND
 THE LOCATION OF THE KEY (IF THE DISCONNECTING MEANS IS
 LOCKED).
 FBC 106.1.2 ADMIN SECTION.
  
 24) NOTE: PLEASE SEE FIXTURE LEGEND SHALL STATE THE
 MINIMUM TIMES ON THE EMERGENCY AND EXIT LIGHTS AS
 REQUIRED PER LS 101 7.9.2.1
  
 25) NOTE: PLEASE SEE SOME DEVICES SHOWN ON PLANS COULD
 NOT BE LOCATED ON THE DEVICE SYMBOL LEGEND. PLEASE
 COMPLETE FOR REVIEW OF THESE ITEMS.
 FBC ADMIN SECTION 106.1.2, 106.3.5.1.2
  
 26) NOTE: PLEASE KNOW BASED ON THE REQUIREMENTS OF MANY
 OF THE REVIEW COMMENTS AND FBC CHAPTER 13, THE PLAN
 KEYNOTES WILL MOST LIKELY BE ADJUSTED.
 PLEASE BE SURE TO CORRELATE.
  
 27) NOTE: PLEASE SEE E-301 KEYNOTE #7 WHICH HAS TO DO
 WITH THE LOCATION OF THE CONTROL FOR THE SPORTS COURT
 LIGHTS WHICH DEVICE COULD NOT BE LOCATED AND YET PLEASE
 SEE THE CIRCUITING AND NOTE ON E-601 #9 MENTIONS
 CONTROL AT FRONT DESK?
 PLEASE CORRELATE
 FBC 106.1.2
  
 28) NOTE: PLEASE LABEL THE TYPICAL FLOOR LIGHTING PLANS
 TO THE RESPECTIVE FLOORS. IE; 2, 3 ETC
 FBC 106.1.2
  
 29) NOTE: PLEASE SEE PANEL "L1C" IS BEING FED FROM
 "H1B" WITH A SINGLE POLE 20A BREAKER?
 PLEASE SEE THIS IS A 277/480V PANEL AND RISER SHOWS
 THROUGH A TRANSFORMER ETC. PLEASE ADJUST PLANS AND
 CORRELATE.
 REVIEW OF 240.21C, 450.3, 408.16 CAN NOT BE DONE AT
 THIS TIME.
  
 30) NOTE: PLEASE SEE 210.60 WHICH REFERENCES TO 210.52
 FOR ITEMS REQUIRED.
 PLEASE SEE THERE ARE SEVERAL ITEMS FOR THIS.
  
 31) NOTE: PLEASE SEE MISSING THE SMALL APPLIANCE
 CIRCUITS AS REQUIRED PER 210.52B1, 210.11C1 AND 220.16
 PLEASE KNOW THAT NO OTHER OUTLETS MAY BE FED FROM THESE
 CIRCUITS.
  
 32) NOTE: PLEASE SEE 210.52B1 AS THERE ARE RECEPTACLES
 LOCATED IN THE KITCHEN/BREAKFAST/DINING AREAS WHICH ARE
 FED FROM THE LIGHTING CIRCUITS WHICH IS NOT PERMITTED.
 PLEASE SEE 210.11C1, 220.16 AS NOTED IN NOTE #31
  
 33) NOTE: PLEASE SEE MISSING RECEPTSPER 210.52 FOR
 2FT OF WALL , KITCHEN AREA, KITCHEN WALL OVER 2FT,
 WITHIN 6FT OF DOORS ETC.
 PLEASE KNOW AS THE CODE DOES PERMIT THE SPACING FOR
 HOTEL/MOTELS AND GUEST SUITES TO BE SPACE FOR FURNITURE
 LAYOUTS, IT ALSO STILL REQUIRES THE SAME NUMBER OF
 RECEPTS WHICH WOULD BE REQUIRED IN A DWELLING TO BE
 INSTALLED.
 210.60
  
 34) NOTE: PLEASE SEE AREAS WHICH SEEM TO BE COUNTER
 PENINSULAR AREAS OFF OF KITCHEN WHICH SOME SHOW RECEPTS
 AND SOME DO NOT?
 PLEASE SEE 210.52C3
  
 35) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTS SERVING
 KITCHEN COUNTER SPACES AND THE LIKE SHALL BE GFI/GFI
 PROTECTED.
  
 36) NOTE: PLEASE CLARIFY THE ARC FAULT PROTECTION ONLY
 BEING SHOWN ON ONE CIRCUIT IN SLEEPING ROOMS? 210.12
  
 37) NOTE: PLEASE COMPLETE ALL PANEL BOARDS WITH THE
 CONDUCTOR SIZES FOR ALL BRANCH CIRCUITS.
 PLEASE SEE 310.16, 240.4, FBC 106.1.2, 106.3.5.1.2
 REVIEW FOR CONDUCTORS CAN NOT BE DONE AT THIS TIME.
  
 38) NOTE: PLEASE SUBMIT AND SHOW A COMPLETE GROUNDING
 ELECTRODE RISER UP THROUGH THE BUILDING. PLEASE SEE
 250.58, 250.66
 MAY BE PLACED ON RISER SHEET.
  
 39) NOTE: PLEASE SHOW THE ATTACHMENT LOCATION FOR EACH
 TRANSFORMER PER 250.66, 250.30, 250.50
  
 40) NOTE: PLEASE SUBMIT A COMPLETED GROUNDING ELECTRODE
 SYSTEM. PLEASE SEE PLANS DID NOT SHOW ANY AS REQUIRED
 PER 250.50.
 PLEASE ALSO SEE 250.104 FOR ANY WATER AND OTHER TYPES
 OF METAL PIPING. (SPRINKLER ETC)
  
 41) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEM
 AT DETACHED BUILDINGS/STRUCTURES PER 250.32
  
  
  
 42) NOTE: PLEASE SEE MISSING PANEL SCHEDULE FOR PANEL
 "P".
 PLEASE SUBMIT AND COMPLETE EVEN FOR FUTURE LOAD ETC.
 THE MDP DOES LIST THE PANEL, YET LOADS CAN NOT BE
 VERIFIED FOR PANEL SCHEDULE.
 CONTINUOUS LOADS ETC.
 220, 215.3, 230.42.
 FBC 106.1.2
  
 43) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS AND
 SUMMARY FOR ALL LOADS AND SHOW ALL CONTINUOUS/LARGEST
 MOTOR LOADS AT 125%.
 220.3,220.10,220.11,220.13, 230.42, 215.3 ETC.
  
 44) NOTE: PLEASE SEE PANEL "L1B" WHICH IS BEING FED
 FROM A 400A BREAKER ON #2 AWG AT THE MDP.
 PLEASE SEE 240.4, 310.16, 450.3 ETC.
  
 45) NOTE: PLEASE SEE 240.13 AND 230.95 AS THE MAIN IS
 BEING SHOWN WITH GFI PROTECTION WHICH IS THAT FOR
 PERSONNEL PROTECTION AND CODE REQUIRES GFP (GROUND
 FAULT PROTECTION WHICH IS NOT THE SAME. PLEASE ADJUST.
  
 46) NOTE: PLEASE SEE POOL AREA LIGHTS ARE BEING SHOWN
 FED FROM AT 277V ??
 PLEASE SEE SOME ARE SHOWN ON SITE PLANS HOWEVER ACTUAL
 DISTANCES COULD NOT BE SCALED. PLEASE PLACE NOTE ON
 PLANS, OR SHOW DISTANCES.
 FBC 106.1.2, NEC 680.22
  
 47) NOTE: PLEASE SEE MISSING NEUTRAL CONDUCTOR TO THE
 FIRE PUMP/FIRST MEANS OF DISCONNECT. PLEASE SEE
 250.24B, 250.24, 250.6. EVEN AS A MOTOR LOAD, THIS IS
 REQUIRED.
 PLEASE SEE AS NOTED, (250.6) NO EQUIPMENT GROUNDING
 CONDUCTOR IS INSTALLED BEFORE THE FIRST MEANS OF
 DISCONNECT.
 THIS WOULD CREATE OBJECTIONABLE CURRENTS.
  
 48) NOTE: PLEASE PROVIDE INFORMATION FOR KEY CARD
 ACCESS CONTROL SYSTEM. PLEASE SEE NFPA-1017 7.2.1,
 7.1.9, 7.2.1.5 WHICH REQUIRES THAT ANY ACCESS CONTROL
 OR DOOR LOCK SYSTEM NOT TO IMPEDED EGRESS IN ANY
 FASHION UNDER NORMAL OR EMERGENCY CONDITIONS. PLEASE
 ALSO SEE FIRE REVIEW'S POSSIBLE COMMENTS.
  
 49) NOTE: PLEASE SEE NFPA-72 11.8.3 WHICH REQUIRES
 LOCATIONS OF SMOKE DETECTORS TO BE INSTALLED WITH
 MINIMUM CRITERIA. PLEASE SEE AREAS WHERE THERE ARE
 SLOPED CEILINGS AS SHOWN ON THE ARCHITECTURAL SHEETS,
 THE SD SHALL BE INSTALLED WITHIN 3FT OF THE PEAK OF
 THAT SLOPE. (LOUNGE) ETC. PLEASE NOTE THE REQUIREMENTS
 AS LISTED. (3FT FROM BATH ROOM AND KITCHEN
 DOORS/OPENINGS ETC. PLANS DO ALREADY CONTAIN A NOTE FOR
 THE SMOKE DEVICE BEING PHOTO-ELECTRIC IN SOME AREAS.
 THIS COMMENT MAYBE EXPANDED UPON.
 PLEASE SE PREVIOUS NOTE WITH RESPECT TO LOCATION
 MISSING WHICH WILL REQUIRE ADDITIONAL.
  
 50) NOTE: PLEASE CLARIFY THE DISCONNECTING MEANS AND
 GROUNDING AT THE DETACHED STORAGE/DUMPSTER BUILDING.
 250.31-225.39 AND 250.32 AS PREVIOUSLY NOTED FOR THE
 POOL HOUSE BUILDING.
  
 *** PLEASE KNOW AS THERE ARE MANY ITEMS NOT SUBMITTED
 FOR REVIEW, PLANS NOT DESIGNED TO FBC CHAPTER 13 ETC,
 THERE MAY BE FUTURE REVIEW COMMENTS ON THE FOLLOW UP
 REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-03 06:52:212007-01-03 06:52:21
 NOTES IN PROGRESS
2007-01-02 21:02:382007-01-02 21:02:38
 REVIEW STOPPED, NOTES TO FOLLOW.
2007-01-02 07:13:432007-01-02 07:13:43
 REVIEW IN PROGRESS
2007-01-01 16:03:372007-01-01 16:03:37
 REVIEW STOPPED, REVIEW WILL GO INTO A "F" STATUS.
 REVIEW NOTES TO FOLLOW ONCE REVIEW IS COMPLETED.
2007-01-01 15:28:402007-01-01 15:28:40
 IN ELEC FOR REVIEW, REVIEW IN PROGRESS.