| Date |
Text |
| 2007-10-02 08:59:20 | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |
| 2007-01-09 18:36:46 | BUILDING PLAN REVIEW |
| | PERMIT:06111071 |
| | ADD:2455 METROCENTRE BLVD |
| | CONT:AUTO BUILDERS GENERAL CONT.SVCS. INC |
| | TEL: (561)622-3515 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | HOMEWOOD SUITES |
| | 5 - STORY 114 UNITS. |
| | |
| | REVIEW 1ST |
| | ACTION: DENIED |
| | |
| | 1) -----VERY INPORTANT STATEMENT ------ |
| | PLEASE DO NOT IGNORE ! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION ON THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN VE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2 ) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| | NOT ACTUALLY |
| | COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, |
| | SUCH NOTICE IS NULL & VOID. |
| | |
| | 3)FBC. 1802.2.1 QUESTIONABLE SOIL . |
| | WHERE THE SAFE-SUSTAINING POWER OF THE SOIL IS IN |
| | DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT |
| | SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION |
| | BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE |
| | PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 4)109.3.6*WPB ADMINISTRATIVE CODE- THIS BUILDING IS |
| | CONSIDERED A "THRESHOLD BUILDING" WHICH WILL REQUIRE |
| | THREE (3) SETS OF PLANS, REPORTS AND SUBMITTALS TO THE |
| | BUILDING DEPARTMENT FOR REVIEW. |
| | |
| | 5)FL.S. 553.71(7). "THRESHOLD BUILDING" MEANING ANY |
| | BUILDING WHICH IS GREATER THAN THREE STORIES OR 50 FEET |
| | (15 240 MM) IN HEIGHT, OR WHICH HAS AN ASSEMBLY |
| | OCCUPANCY CLASSIFICATION THAT EXCEEDS 5,000 SQUARE FEET |
| | IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER OR ARCHITECT |
| | OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST BE |
| | SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE ISSUANCE |
| | OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| | THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| | INSPECTION PLANS IS TO PROVIDE SPECIFIC INSPECTION |
| | PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| | ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| | DOCUMENTS. |
| | |
| | 6)FBC.109.3.6.6CONSTRUCTION SERVICES DEPARTMENT |
| | REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS |
| | REQUIRED BYSEC. 553.79(5) FLORIDA STATUTES TO THE |
| | MINIMUM INSPECTIONS REQUIRED BY THIS CODE. CONTACT |
| | HARALD PISKURA MANAGER OF THE SPECIAL INSPECTOR PROGRAM |
| | AT (561) 805-6711 FOR FURTHER INFORMATION BEFORE THE |
| | PERMIT MAY BE ISSUED. |
| | |
| | 7)109.3.6.4.4 ALL PLANS FOR THE BUILDING WHICH ARE |
| | REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR |
| | ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | MINIMUM BUILDING CODES AND THE APPLICABLE FIRE-SAFETY |
| | STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN |
| | ACCORDANCE WITH THIS SECTION AND CHAPTER 633, FLORIDA |
| | STATUTES. |
| | |
| | 8)PLEASE NOTE:109.3.10* RESERVED. IMPACT OF |
| | CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY |
| | THIS CODE SHALL BE PERFORMED IN A MANNER SO AS NOT TO |
| | ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY, |
| | UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID |
| | PROPERTY PURSUANT TO A CONSENT GRANTED BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS OR CONDITIONS |
| | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| | INCLUDES, BUT IS NOT LIMITED TO, THE CONTROL OF DUST, |
| | NOISE, WATER OR DRAINAGE RUN-OFFS, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, AND |
| | MAY REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE POSITIVE DRAINAGE |
| | PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| | DEVELOPERS, CONTRACTORS AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800 |
| | SQUARE FEET OF PERMEABLE LAND AREA ON ANY PARCEL SHALL, |
| | AS A PERMIT CONDITION, PROVIDE A PROFESSIONALLY |
| | PREPARED DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE |
| | WITH THIS PARAGRAPH. UPON COMPLETION OF THE |
| | IMPROVEMENT, A CERTIFICATION FROM A LICENSED ENGINEER |
| | SHALL BE SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE |
| | APPROVAL OF THE FINAL INSPECTION. |
| | |
| | 9)PLEASE NOTE: 109.3.10.1 HURRICANE PROTECTION. IT |
| | SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION |
| | RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE |
| | OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 |
| | HOURS AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT, AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| | PERSON WHO FAILS TO REMOVE OR SECURE THE CONSTRUCTION |
| | MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 HOURS AFTER A |
| | HURRICANE WATCH HAS BEEN ISSUED SHALL BE SUBJECT TO A |
| | FINE NOT TO EXCEED $500. IN ADDITION TO THE ABOVE, A |
| | LICENSED CONTRACTOR WHO VIOLATES THIS SECTION SHALL BE |
| | SUBJECT TO DISCIPLINE PURSUANT TO SECTION 113 OF THIS |
| | CHAPTER. |
| | |
| | 10)PLEASE NOTE: 104.6*/1069.1.4/1714.5 STANDARDS FOR |
| | WIND-BORNE DEBRIS INPACT PROTECTION. RECOGNIZING SUCH |
| | CONCERNS AS ABSENTEE OWNERS,OR CASES WHERE LONGER TIME |
| | & EFFORT IS NECESSARY TO SECURE SHUTTERS ON LARGE OR |
| | MULTI-STORY BUILDINGS, WHAT MEASURES ARE BEING |
| | RECOMMENDED OR IMPLEMENTED TO ENSURE THAT COMPLETE |
| | INSTALLATION OR SECURING IS DONE SUFFICIENTLY IN |
| | ADVANCE OF THE HURRICANE? |
| | |
| | IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE |
| | GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE, |
| | SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING, |
| | CHAPTER 1, |
| | |
| | ADMINISTRATIVE CODE 2004 EDITION AS AMENDED BY THE CITY |
| | OF WEST PALM BEACH,PROVDES THE ABILITY FOR THE BUILDING |
| | OFFICIAL TO IMPLEMENT REQUIREMENTS FOR ENSURING |
| | STABILITY, STRENGHT, AND THE PROPER OPERATION OF |
| | EXISTING BUILDINGS. |
| | |
| | IN ORDER TO ESSURE THE SECURING OF SHUTTERS ON LARGE OR |
| | MULTI-STORY BUILDINGS, OR MULTIPLE BUILDINGS ON THE |
| | SAME PROPERTY,PRE-STORM PREPARATION PLANS MUST BE |
| | SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS FOR |
| | REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY |
| | SUCH PLAN SHALL INCLUDE, AT A MINMUM, ON SITE LOCATION |
| | OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE |
| | SHUTTERS (SAID PARTY MUST BE LOCATED WITHIN PALMBEACH |
| | COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND |
| | THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS. |
| | PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN |
| | TWELVE (12) HOURS OR LESS OF THE OFFICIAL NOTIFICATION |
| | BY THE NATIONAL WEATHER SERVICES OF A HURRICANE WATCH. |
| | |
| | PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD) |
| | ARE NOT INTENDED TO PROHIBIT TO USE OF ALTERNATE |
| | MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO |
| | REVIEW AND APPROVEANY ALTERNATE DEEMED EQUIVALENT IN |
| | QUALITY,STRENGHT, EFFICTIVENESS, FIRE RESISTANCE, |
| | DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED |
| | UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE |
| | MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE |
| | PASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO |
| | SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE. |
| | |
| | 11)1609.1.4 PROTECTION OF OPENINGS. |
| | IN WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT |
| | RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3 |
| | M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE |
| | BALANCE OF GLAZED OPENINGS IN THE REST OF THE BUILDING |
| | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT |
| | RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR |
| | PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE |
| | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996, |
| | OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN |
| | AS FOLLOWS: |
| | 1.GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) |
| | OF GRADE SHALL MEET THE REQUIREMENTS OF THE LARGE |
| | MISSILE TEST. |
| | 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 |
| | M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| | MISSILE TEST. |
| | |
| | 12) 106.3.3* PRODUCT APPROVALS- 2004 |
| | THOSE PRODUCTS THAT ARE RGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITTING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 13) 61G1-16.004FL. ADMIN. CODE.PLANS |
| | PREPARED BY A REGISTERED ARCHITECT SHALL |
| | INCLUDE A TITLE BLOCK WHICH MUST: |
| | - STATE THE FIRM NAME, ADDRESS AND |
| | TELEPHONE NUMBER |
| | - STATE THE FIRM LICENSE NUMBER |
| | - STATE PROJECT NAME OR IDENTIFICATION |
| | - STATE DATE PREPARED |
| | - INCLUDE AN ORIGINAL SIGNATURE AND |
| | DATED SEAL |
| | - INCLUDE THE PRINTED NAME OF THE |
| | ARCHITECT SEALING THE PLANS |
| | |
| | 14) 61G15-23.002(2)FL. ADMIN. CODE. |
| | PLANS SIGNED & SEALED BY A PROFESSIONAL |
| | ENGINEER SHALL INCLUDE EITHER THE NAME, |
| | ADDRESS AND LICENSE NUMBER OF THE |
| | ENGINEER OR, THE NAME AND LICENSE NUMBER |
| | OF THE ENGINEER AND THE NAME, ADDRESS |
| | AND CERTIFICATE OF AUTHORIZATION NUMBER |
| | OF THE ENGINEERING BUSINESS THROUGH |
| | WHICH THE ENGINEER IS PRACTICING |
| | (471.025 F.S. AND 471.023 F.S.). |
| | |
| | 15) 471.023 F.S.CERTIFICATE OF |
| | AUTHORIZATION.THE TITLE BLOCK FOR ANY |
| | SHEET BEARING THE NAME OF AN ENGINEER |
| | PRACTICING UNDER A FICTITIOUS NAME, A |
| | CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING |
| | SERVICES, SHALL INCLUDE THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER. |
| | ADD THE NUMBER TO EACH SHEET.THIS MAY BE ADDED BY |
| | HAND. |
| | |
| | 16) 110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. OK |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. OK |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | ------------------------------------- |
| | ) NUMBERBER OF ROOMS |
| | ) SQ. FT. LIV SPACE/ FL |
| | ) SQ. FT. FOOTPRINT |
| | ) SQ. FT. UNDER ROOF (TOTAL) |
| | ) OCCUPANT LOAD |
| | ) FLOOD ZONE |
| | ) FLOOD ELEVATION |
| | )L.O.M.R. |
| | |
| | 17) 108.3* THE CLAIMED VALUE IS LOW. IF IN THE OPINION |
| | OF THE BUILDING OFFICIAL THE CLAIMED VALUATION OF |
| | BUILDING, ALTERATION STRUCTURE, ELECTRICAL,GAS, |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| | UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| | DENIED. FOR PERMITTING PURPOSES VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO |
| | INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, |
| | INTERIOR FINISH, NORMAL SITE WORK, ARCHITECTURAL AND |
| | DESIGN FEES, MARKETING COST, OVERHEAD AND PROFIT; |
| | EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY |
| | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSISSERVICES (MARSHALL-SWIFT, |
| | MEANS,ETC.) WITH REGIONAL ADJUSTMENTS FOR LOCATION AS |
| | PUBLISHED BY INTERNATIONAL CODE CONGRESS. |
| | |
| | 18)THE NUMBER OF GUEST ROOMS ON SHEET G-000 IS 130, |
| | THEN ON SHEET G-OO2 INDICATE 114 GUEST ROOMS. |
| | |
| | 19)SHEET A-101 FBC. 707.13REFUUSE AND LAUNDRY |
| | CHUTES,ACCESS AND TREMINATION ROOMS AND INCINERATOR |
| | ROOMS SHALL MEET THE REQUIREMENTS OF SECTIONS 707.13.1 |
| | THROUGH 707.13.6 |
| | |
| | 20)ON SHEET A-603, INDICATE THE DOOR RATING FOR THE |
| | TERMINATION ROOM OF THE REFUSE AND LAUNDRY CHUTES PER |
| | TABLE 715.3. THE DOOR RATINGS SHALL BE INDICATED IN |
| | MINIUTES OR HOURS. STATING THE RATING AS "PER CODE". IS |
| | INSUFFICIENT INFORMATION. BE MORE SPECIFIC USING |
| | SECTION 715 FBC AND TABLE 715.3, |
| | |
| | 21) |
| | |
| | |
| | |
| | |
| | |
| | |
| | |