2009-03-09 13:03:31PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS/PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. THE NOTE AT GAS METER & REGULATOR ASSEMBLY SHOULD BE
 CHANGED TO 1950 CFH
  
 2. THE CFH AFTER THE FIRST TEE SHOULD BE 1550
  
 3. THE NOTE 3/4" @ 600 CFH SHOULD BE 750 CFH
  
 4. THE PIPE SECTION FROM THE METER, BEFORE THE FIRST
 TEE SHOULD BE LABELED AS 1 1/4" (FROM TABLE 402.4 (3)
 ).
  
 5. THE 350 CFH DROP AT THE END IS NOT LABELED AS TO
 WHICH APPLIANCE OR WHICH REGULATOR IS BEING USED.
  
 6. ***NOTE*** THE PIPE SIZES ARE NOT CONSISTENT, SUCH
 AS, 1" PIPE ENTERING THE BUILDING YET 3" PIPE OVERHEAD
 AND A 3/4" DROP WITH 2" PIPE FEEDING THE FOUR WATER
 HEATERS.
  