| Notes |
| Date |
Text |
| 2008-10-03 11:55:52 | | | | ** DENIED ** | | | | | | | | | | | | | | | 1) NOTE: PLEASE PROVIDE INFORMATION ON THE COMPACT | | | CONDUCTORS AS NOTED ON THE RISER FOR THE NEW 800MCC | | | ALUMINUM. PLEASE SEE TABLE 5A IN NEC CHAPTER 9 AS | | | 800MCM IS NOT A SIZE SHOWN. AREA FOR SQ INCHES NEEDS TO | | | BE VERIFIED. PLEASE ALSO VERIFY TYPE OF CONDUIT. PLEASE | | | KEEP IN MIND IF PVC AND ANY AREAS ARE SUBJECT TO | | | PHYSICAL DAMAGE SCHEDULE 80 MAY BE REQUIRED. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|