Plan Review Notes
Plan Review Notes For Permit 06111067
Permit Number 06111067
Review Stop E
Sequence Number 7
Notes
Date Text
2008-10-03 11:55:52 
 ** DENIED **
  
  
  
  
 1) NOTE: PLEASE PROVIDE INFORMATION ON THE COMPACT
 CONDUCTORS AS NOTED ON THE RISER FOR THE NEW 800MCC
 ALUMINUM. PLEASE SEE TABLE 5A IN NEC CHAPTER 9 AS
 800MCM IS NOT A SIZE SHOWN. AREA FOR SQ INCHES NEEDS TO
 BE VERIFIED. PLEASE ALSO VERIFY TYPE OF CONDUIT. PLEASE
 KEEP IN MIND IF PVC AND ANY AREAS ARE SUBJECT TO
 PHYSICAL DAMAGE SCHEDULE 80 MAY BE REQUIRED.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717