| 2008-05-28 15:27:24 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 06111067 |
| | ADD: 2437 METROCENTRE BLVD |
| | CONT: AUTOBUILDERS |
| | TEL: (561)310-7735 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | SPRINGHILL SUITES BY MARIOTT |
| | FIVE STORY/ 130 UNITS |
| | |
| | REVISION "H"REVIEW |
| | ACTION: DENIED |
| | SHEETS: |
| | 1) A-101A : ELEVATOR LOBBY REVISION, DELTA H,DETAIL# |
| | 7/ A702THIS REVISION IS NOT FOUND IN THE REVISION SET |
| | OF PLANS? ADDITIONAL INFORMATION REQUIRED, 106.1.2. |
| | |
| | 2) A-102 A-102ELEVATOR LOBBY 234 INDICATES A GUEST |
| | PHONE NICHE, PLEASE PROVIDE COMPLIANCE WITH 11-4.31.2- |
| | 11-4.31.9. |
| | |
| | 3) A-102A ELEVATOR LOBBY 234 INDICATES A GUEST PHONE |
| | NICHE, PLEASE PROVIDE COMPLIANCE WITH 11-4.31.2- |
| | 11-4.31.9. |
| | |
| | 4) A-103 ELEVATOR LOBBY 334 INDICATES A GUEST PHONE |
| | NICHE, PLEASE PROVIDE COMPLIANCE WITH 11-4.31.2- |
| | 11-4.31.9. |
| | |
| | 5) A-103A ELEVATOR LOBBY 334 INDICATES A GUEST PHONE |
| | NICHE, PLEASE PROVIDE COMPLIANCE WITH 11-4.31.2- |
| | 11-4.31.9. |
| | |
| | 6) A104) ELEVATOR LOBBY 434 INDICATES A GUEST PHONE |
| | NICHE, PLEASE PROVIDE COMPLIANCE WITH 11-4.31.2- |
| | 11-4.31.9. |
| | |
| | 7) A-105 ELEVATOR LOBBY 534 INDICATES A GUEST PHONE |
| | NICHE, PLEASE PROVIDE COMPLIANCE WITH 11-4.31.2- |
| | 11-4.31.9. |
| | |
| | 8) A-105A ELEVATOR LOBBY 534 INDICATES A GUEST PHONE |
| | NICHE, PLEASE PROVIDE COMPLIANCE WITH 11-4.31.2- |
| | 11-4.31.9. |
| | |
| | 9) A-402 THE REFRIGARANT LINE WALLS DO NOT INDICATE THE |
| | TYPE OF WALL DESIGNATION. SEE ROOM # * 12 WILL NEED TO |
| | BE A 1 HR RATED WALL WITH A SOUND COEFFIICENT OF 50 |
| | PLEASE PROVIDE WALL TYPE TAG. |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 10) PROVISO: A-801 THE MICROWAVE WILL NEED TO MEET THE |
| | REACH RANGE REQUIREMENTS OF 11-4.2.5OR 11-4.2.6 AND |
| | 11-4.27.3 CONTROLS AND OPERATING MECHANISMS HEIGTH |
| | REQUIREMENTS WITHIN THE HANDICAPPED UNITS. |
| | |
| | 11) A-805 REGISTRATION STATION PLEASE PROVIDE DETAIL |
| | INDICATING COMPLIANCE WITH 11-7.2 (2) . |
| | |
| | 12) A-806DETAIL# 4 FOR HANDICAPPED ACCESSIBLE ROOMS, |
| | THE MICROWAVE WILL NEED TO MEET THE REACH RANGE |
| | REQUIREMENTS OF 11-4.2.5OR 11-4.2.6 AND 11-4.27.3 |
| | CONTROLS AND OPERATING MECHANISMS HEIGTH REQUIREMENTS. |
| | |
| | 13) A-808 & A-811 TELEPHONES WILL NEED TO MEET THE |
| | REQUIREMERNTS OF 11-4.31.1- 11-4.31.9. |
| | |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |