Plan Review Notes
Plan Review Notes For Permit 06111067
Permit Number 06111067
Review Stop P
Sequence Number 6
Notes
Date Text
2008-03-19 09:06:14 
  
  
  
 PASSED/PROVISO
  
 SHTS P101A & P101B INDICATES THE LAV AS FIXTURE MARK
 P-3B AND THE URINAL AS FIXTURE MARK P-2. THIS DOES NOT
 RELFECT THE FIXTURE SCHEDULE ON P601. REVISION
 REQUIRED.
  
 SHT P101B SHOWS RISER CW/52 - HW/52. RISER CW/52 -
 HW/52 NOT SUBMITTED. REVISION REQUIRED.
  
 SHT P403 SHOWS FIXTURE MARK P-8 FOR THE TUB IN DETAIL
 #4. P-8 IN THE FIXTURE SCHEDULE IS INDICATED AS A
 LAUNDRY ROOM SINK. REVISION REQUIRED.
  
 SHT P502 SAN/47 SHOWS FIXTURE MARK P-7, (INDICATED AS A
 BREAK ROOM SINK ON FIXTURE SCHEDULE), AND P-8,
 (INDICATED AS A LAUNDRY ROOM SINK ON THE FIXTURE
 SCHEDULE), BUT ARE SHOWN AS SHOWER & TUB ON THE FLOOR
 PLAN. REVISION REQUIRED.
  
 SHT P502 SAN/48 SHOWS FIXTURES IN THE CEILING. NO
 FIXTURES ARE SHOWN ON THE FLOOR PLAN FOR THIS RISER.
 REVISION REQUIRED.
  
 SHT P505 RISERS 40, 41, 42, 45, 46, 47 & 63 STILL SHOW
 WATER SUPPLY UNDER THE SLAB. REVISION REQUIRED.
  
 SHT P507 WATER HAMMER ARRESTORS ARE REQUIRED AT THE
 DISH SANITIZER. SECTION 604.9. REVISION REQUIRED.
  
  
  
  
 .