| 2008-04-24 14:58:13 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | ** REVISION TO MECHANICAL PLAN PAGE M-101 ** | | | *** DENIED *** | | | | | | 1)PAGE M-101 SEE YELLOW HIGH LIGHTED WALLS THAT ARE | | | SHOWN AS RATED WALLS ON PAGE A-401, IF SO SEE RED LINE | | | SHOWING WERE FIRE DAMPERS WILL BE NEEDED. IF NOT RATED | | | CORRECT ARCHITECTURAL PLANS, SEE 2004 FBC/M 607.5.1. | | | | | | 2) PLEASE COORDINATE ALL FIRE RESISTANCE RATED WALL | | | LOCATION CHANGES WITH ARCHITECT AND MECHANICAL | | | ENGINEER. | | | | | | *** REVISION TO MECHANICAL PLANS M-001, M-102, M-103, | | | M-104, M-105, AND M-106 WERE REVIEWED AND STAMPED. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|