Plan Review Notes
Plan Review Notes For Permit 06111067
Permit Number 06111067
Review Stop M
Sequence Number 6
Notes
Date Text
2008-04-24 14:58:13PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** REVISION TO MECHANICAL PLAN PAGE M-101 **
 *** DENIED ***
  
 1)PAGE M-101 SEE YELLOW HIGH LIGHTED WALLS THAT ARE
 SHOWN AS RATED WALLS ON PAGE A-401, IF SO SEE RED LINE
 SHOWING WERE FIRE DAMPERS WILL BE NEEDED. IF NOT RATED
 CORRECT ARCHITECTURAL PLANS, SEE 2004 FBC/M 607.5.1.
  
 2) PLEASE COORDINATE ALL FIRE RESISTANCE RATED WALL
 LOCATION CHANGES WITH ARCHITECT AND MECHANICAL
 ENGINEER.
  
 *** REVISION TO MECHANICAL PLANS M-001, M-102, M-103,
 M-104, M-105, AND M-106 WERE REVIEWED AND STAMPED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]